is no need to add refrigerant. If the connecting pipe is longer than 7.5m, it is required to add refrigerant. In the
above table, the amounts of refrigerant to be added for the models are listed for each additional meter of pipe
length.
2. The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able to withstand the pressure of 6.0
MPa.
3. The longer the connecting pipe, the less effective the cooling or the heating will be.
Connection of Pipeline:
(1)
Align the flared end of the copper pipe with the center of the thread joint. Manually tighten the flared end
nut.
(2)
Use torque spanner to tighten the flared end nut until the spanner clatters (See Fig.11-1
7
).
Fig. 11-1
6
Fig. 11-1
7
The following table describes the torques for tightening nuts of different pipe diameters.
Pipe Diameter
Tightening Torque
ij
6.34mm
15-30 (N·m)
ij
9.52mm
35-40 (N·m)
ij
15.88mm
60-65 (N·m)
ij
12.7mm
45-50 (N·m)
ij
19.05mm
70-75 (N·m)
ij
22.05mm
80-85 (N·m)
(3)
The bending angle of the fitting pipe shall not be too small, and otherwise the pipe may break. Please use a
bender when bending the fitting pipes.
(4)
Use sponge to wrap the connecting pipe and joint without thermal insulation, and use plastic tape to bundle
the sponge.
(5)
Remove the cap of the liquid valve and the gas valve.
(6)
Use an inner hexagon spanner to turn the spool of the liquid valve for 1/4 circle. At the same time, use a
screwdriver to lift the spool. Then there is discharge of gas.
(7)
Refrigerant gas shall appear after the gas is discharged for 15 seconds. Now close the one way valve
immediately and tighten the bonnet.
(8)
Fully open the spools of the liquid valve and the gas valve (refer to
Fig. 11-1
7
).
(9)
Tighten the valve cover. Then use soap water or leakage detector to check if there is leakage at the position
where the indoor unit or the outdoor unit is connected with pipelines.
(10)
If possible, use a vacuum pump to remove air out from the valve. Refer to Fig. 11-1
8
Fitting Pipe for
Indoor Unit
Flaring Nuts
Fitting Pipe
Torque Spanner
Spanner
Liquid Valve
Gas Valve
One-Way Valve
Valve Cap
Valve Stem
Inner Hexagon
Spanner
Screwdriver
Note
:
1 The standard pipe length is 7.5m. When the length (L) of the connecting pipe is less than or equals 7.5m, there
42