McQuay IM 660-3

 5

Interface Features

MicroTech Network

Control sequencing, stop/start, equipment protection 
monitoring, and fault resets can be accomplished through a 
network connection. The following unique values and 
parameters can be accessed for each unit (refer to Protocol 
Document ED15054 for more information):

Return air and discharge air temperatures

Compressor, fan and reversing valve status

High pressure, low temperature, brownout and drain pan 
status

Occupied and unoccupied heat and cool set points 

Auto/manual and occupied/unoccupied fan control

Mode, fault, system, schedule and set point operation

Compressor starts and fan run hours

Load shed level (L

ON

W

ORKS

 only)

Tenant override status

In addition, the following unique operation and maintenance 
parameters can display for each unit:

Leaving water temperature

Return air temperature set point (wall sensor adjustment)

Adaptive optimal start (L

ON

W

ORKS

 only)

Occupied/unoccupied (on/cycle) fan mode

Room temperature warning

Filter changes from fan hours

Compressor management: on/off differential, minimum off 
time, minimum on time

Communications Failure (L

ON

W

ORKS

): 

If the network 

communication link fails for any reason, the affected WSHP 
controller remains operational. Its operating mode will be the 
last received over the network unless power is cycled, and then 
it defaults to occupied. Its minimum position, heating, and 
cooling set points will be those last received over the network, 
regardless of whether power is cycled.

Communications Failure (L

ON

M

ARK

): 

If the network 

communication link fails for any reason, the affected WSHP 
controller remains operational. The status of its heating and 
cooling set points as well as its occupancy and other network 
adjustable settings depends upon whether the BAS is using 
L

ON

W

ORKS

 bindings with associated heartbeats.

Wall-Mounted Sensor

There are four optional wall sensor packages available. All 
include a remote status LED and tenant override button. Set 
point adjustment and thermometer are optional features. 

The wall-mounted sensor must be field installed and field 
wired to the water source heat pump. Terminal Board #1 
provides the connections for all room temperature sensor field 
wiring. Refer to the unit wiring diagram provided and to IM 
529, MicroTech Room Temperature Sensors, for information 
on wall sensor package installation.

Figure 5: Wall-mounted temp sensor wiring

Remote Room Set Point Adjustment

The remote set point adjustment potentiometer allows the room 
set point to be adjusted up or down by as much as 3°F (1.7°C). 
It is available with several of the optional wall sensor packages.

Tenant Override

A wall-mounted tenant override switch is standard on all McQuay 
MicroTech Room Temperature Sensors. Pressing and holding the 
tenant override button for 1.0 to 6.0 seconds puts the unit into 
tenant override mode for a set time period (default = 60 minutes). 
Press the tenant override button again for 1.0 to 6.0 seconds and 
the unit returns to unoccupied mode by default. A separate 
configuration property is available that allows users to extend the 
tenant override period for up to 60 minutes with a second button 
press. Except for the fact that it is temporary, the tenant override 
operating mode is identical to the occupied operating mode.

L

ON

W

ORKS

 only:

 Pressing and holding the tenant override 

button for at least 6 seconds but not more than 10 seconds 
activates the network “query address” mode, indicating the 
unit address in question at the MicroTech gateway panel.

L

ON

W

ORKS

 only:

 Pressing and holding the tenant override 

button more than 10 seconds activates the network 
“self-configure” mode, requesting the assignment of the next 
sequential address from the MicroTech gateway panel.

L

ON

M

ARK

 only:

 Similar to pressing the service pin, pressing 

and holding the tenant override button for more than 10 
seconds causes the Neuron chip to broadcast a message over 
the L

ON

W

ORKS

 network containing its unique 48-bit Neuron 

ID. This is useful during network commissioning.

Table 4: Maximum wire length to sensors

Gauge

Length (ft.)

18 AWG

625

20 AWG

380

22 AWG

260

WSHP

Wall sensor

Sensor LED

Tenant override

Sensor input

Sensor common

Red

Green

White

Black

TB1-1

TB1-4

TB1-3

TB1-2

Содержание MicroTech 2000

Страница 1: ... 2005 McQuay International MicroTech 2000 Water Source Heat Pump Unit Controller Installation and Maintenance IM 660 3 Group WSHP Part Number 106018961 Date May 2005 ...

Страница 2: ...om Set Point Adjustment 5 Tenant Override 5 Commissioning 6 Pre Start 6 Required tools and literature 6 Water Source Heat Pump Identification 6 Field Wiring Check 6 Wall Sensor Packages 6 Network Communications Units 6 Set Points 6 Start up 6 Procedure for WSHP 7 Description of Operation 8 Fan Operation 8 Unoccupied Operating Mode 8 Cooling Operation 8 Heating Operation 8 Occupied Operating Mode 8...

Страница 3: ...designed to operate in ambient temperatures from 32 F to 140 F O C to 60 C and in relative humidity up to 95 noncondensing The controller can be stored in ambient temperatures from 40 F to 176 F 40 C to 80 C and in relative humidity up to 95 noncondensing CAUTION Properly commission page 6 the water source heat pump before using for temporary heating or cooling Failure to properly commission can c...

Страница 4: ... other for a field wiring harness that terminates to a screw type terminal strip on the unit s exterior The controller uses set points and fixed preprogrammed parameters to maintain unit control many of the set points and preprogrammed parameters can be adjusted with a PC over the network Yellow Status LED A yellow on board status LED aids in diagnostics by indicating the water source heat pump op...

Страница 5: ...pressor Once the overflow alarm disappears the unit controller automatically resets the WSHP unit The condensate overflow sensor is an exposed ring terminal located in the condensate drain pan The condensate overflow alarm occurs only when the unit is in cooling mode Brownout Alarm The on board brownout feature is meant to protect the compressor contactors from low voltage or brownout conditions I...

Страница 6: ... point and de energizes when the space temperature exceeds the heating set point plus a configurable differential set point defaulted to 3 F Motorized Valve Relay The relay provides output to the motorized valve to shut off water through the unit when the compressor is not operating Fresh Air Damper Relay The relay provides output to the open damper whenever the fan is operating in the occupied cy...

Страница 7: ...tional features The wall mounted sensor must be field installed and field wired to the water source heat pump Terminal Board 1 provides the connections for all room temperature sensor field wiring Refer to the unit wiring diagram provided and to IM 529 MicroTech Room Temperature Sensors for information on wall sensor package installation Figure 5 Wall mounted temp sensor wiring Remote Room Set Poi...

Страница 8: ...e following check lists thoroughly check the electrical installation Wall Sensor Packages 1 Check that the cable is twisted and shielded with drain wire Belden 8729 or equivalent 2 Check that four conductors are available 3 Check that the conductors are terminated at the unit and at the wall sensor package to screw terminal board 1 in accordance with the field wiring diagram on which terminals are...

Страница 9: ... set point 70 F 21 C 35 F to 120 F 1 7 C to 49 C Occupied cooling set point 74 F 23 C 35 F to 120 F 1 7 C to 49 C Fan occupied On On cycle heat cycle cool on Unoccupied heating set point 60 F 16 C 35 F to 120 F 1 7 C to 49 C Unoccupied cooling set point 85 F 29 C 35 F to 120 F 1 7 C to 49 C Fan unoccupied Cycle On cycle Tenant override 1st press 1 00 Off 0 30 to 8 00 Tenant override 2nd press Off ...

Страница 10: ...point to a maximum temperature of USHS DIFF The fan also de energizes when the space temperature rises above the UHS set point however the controller code prevents the fan from stopping until 12 seconds after the compressor stops Note During normal non alarm operation the compressor is disabled if the stop to stop minimum off timer has not expired 5 minutes fixed Occupied Operating Mode The descri...

Страница 11: ... than 10 seconds causes the Neuron chip to broadcast a message over the Lon network containing its unique 48 bit Neuron ID This is useful during network commissioning Load Shed Mode LONWORKS only When the network load shed level is less than or equal to the load shed threshold setting in the unit load shedding is activated The amount the controller adjusts the set points depends upon the network t...

Страница 12: ...ate the cause of a manual reset fault before placing the unit back into service Alarm Fault Descriptions Table 6 below describes the alarm faults how they are triggered the factory settings that trigger them and how they are reset A detailed discussion of each follows High Pressure Fault The High Pressure fault indicates that the high pressure switch input J4 9 sensed an open circuit while the con...

Страница 13: ...indicates the water source heat pump is sensing low voltage levels It is designed to protect the compressor and contactors from low line voltage or brownout conditions The controller is programmed with a brownout set point that corresponds to 82 of the water source heat pump s nameplate line voltage value If the water source heat pump controller senses a voltage level less than its set point for m...

Страница 14: ...P controller diagnostics Approximately 40 seconds after power is applied to the WSHP the status LED should illuminate as shown in Table 2 on page 2 If not either there is a software problem or the WSHP controller is defective Power Supply Problems The WSHP controller requires a 24 VAC power supply It is connected to the board at the section labeled 24V GND and 24 VAC terminals J41 and J42 Refer to...

Страница 15: ...the digital input circuit 4 Measure the resistance through the switch contacts with at least one wire disconnected The switches normally are closed Brownout Fault The WSHP controller senses the AC voltage at the power input section terminals J41 and J42 see unit wiring diagram If the voltage at these terminals is less than 19 68 VAC for at least 1 second the brownout fault occurs The fault automat...

Страница 16: ...mperature sensor common J6 1 7 Auxiliary module connections Table 11 Thermistor chart C 10 k ohm F C 10 k ohm F 18 8 654 0 28 0 8777 82 17 8 173 1 29 0 8408 84 16 7 722 3 30 0 8056 86 15 7 298 5 31 0 7721 88 14 6 900 7 32 0 7402 90 13 6 526 9 33 0 7098 91 12 6 175 10 34 0 6808 93 11 5 845 12 35 0 6531 95 10 5 534 14 36 0 6267 97 9 5 242 16 37 0 6015 99 8 4 967 18 38 0 5774 100 7 4 708 19 39 0 5545...

Страница 17: ...McQuay IM 660 3 15 ...

Страница 18: ...McQuay IM 660 3 16 ...

Страница 19: ......

Страница 20: ...pment its care should be a high priority For training information on all McQuay HVAC products please visit us at www mcquay com and click on training or call 540 248 9646 and ask for the Training Department This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com ...