McQuay MicroTech 2000 Скачать руководство пользователя страница 3

McQuay IM 660-3

 1

Introduction

This manual provides information about the MicroTech 2000™ 
Water Source Heat Pump (WSHP) controller and control 
system used in the McQuay International WSHP product lines. 
The manual describes the controller’s components, input/output 
configurations, and service procedures.

For network installation or commissioning instructions for 
new projects, refer to the protocol information document ED 
14954. For general information on a particular WSHP unit, 
refer to the model-specific installation manual (see Table 1).

*50 Hz only

Table 1: Model-specific water source heat pump 
installation literature

Document number

WSHP unit model

lM 407

Vertical WSHP (007 to 060)

lM 439

Large Vertical WSHP (070 to 290)

IM 447 

Console Units WSHP

lM 494

WMH/CWH (007 to 019)

lM 526

Horizontal WSHP (007 to 120)

lM 544

CCH/HWH (006 to 060)*

lM 656

Horizontal WSHP (019 to 060) 

IM 742

Enfinity Horizontal WSHP (007 to 060)

IM 778

Enfinity Vertical WSHP (007 to 060)

WARNING

Electric shock hazard. 
Can cause equipment damage, personal injury, or death.

 

Properly ground equipment. Connections and service to the 
MicroTech WSHP controller control panel must be performed 
only by personnel knowledgeable in the operation of the 
equipment being controlled.

WARNING

Moisture in the control panel can cause personal injury and 
improper equipment operation. 

When servicing this equipment during rainy weather or high 
humidity conditions, protect the electrical components in the 
main control panel.

CAUTION

Temperature hazard. Can cause damage to system 
components.

The controller is designed to operate in ambient temperatures 
from 32°F to 140°F (O°C to 60°C), and in relative humidity up to 
95% (noncondensing). The controller can be stored in ambient 
temperatures from 40°F to 176°F (40°C to 80°C), and in relative 
humidity up to 95% (noncondensing).

CAUTION

Properly commission (page 6) the water source heat pump 
before using for temporary heating or cooling. Failure to 
properly commission can cause equipment damage not covered 
by warranty.

CAUTION

Static sensitive components. Static discharge while 
handling electronic circuit boards can cause damage to the 
components.

Discharge any static electrical charge by touching the bare 
metal inside the main control panel before performing any 
service work. Never unplug cables, circuit board terminal blocks, 
relay modules, or power plugs while power is applied to the 
panel.

CAUTION

This equipment generates and uses radio frequency energy. If 
not installed and used in accordance with this manual, it can 
cause interference to radio communications. It has been tested 
and found to comply with the limits for a Class B digital device, 
pursuant to part 15 of the FCC rules. Operation is subject to the 
following conditions:
1. This device may not cause harmful interference.
2. This device must accept any interference received, including 

interference that may cause undesired operation.

These limits are designed to provide reasonable protection 
against harmful interference when the equipment is operated in 
a commercial environment. Operation of this equipment in a 
residential area is likely to cause harmful interference, in which 
case users are required to correct the interference at their own 
expense. McQuay International disclaims any liability resulting 
from any interference or for the correction thereof.

Содержание MicroTech 2000

Страница 1: ... 2005 McQuay International MicroTech 2000 Water Source Heat Pump Unit Controller Installation and Maintenance IM 660 3 Group WSHP Part Number 106018961 Date May 2005 ...

Страница 2: ...om Set Point Adjustment 5 Tenant Override 5 Commissioning 6 Pre Start 6 Required tools and literature 6 Water Source Heat Pump Identification 6 Field Wiring Check 6 Wall Sensor Packages 6 Network Communications Units 6 Set Points 6 Start up 6 Procedure for WSHP 7 Description of Operation 8 Fan Operation 8 Unoccupied Operating Mode 8 Cooling Operation 8 Heating Operation 8 Occupied Operating Mode 8...

Страница 3: ...designed to operate in ambient temperatures from 32 F to 140 F O C to 60 C and in relative humidity up to 95 noncondensing The controller can be stored in ambient temperatures from 40 F to 176 F 40 C to 80 C and in relative humidity up to 95 noncondensing CAUTION Properly commission page 6 the water source heat pump before using for temporary heating or cooling Failure to properly commission can c...

Страница 4: ... other for a field wiring harness that terminates to a screw type terminal strip on the unit s exterior The controller uses set points and fixed preprogrammed parameters to maintain unit control many of the set points and preprogrammed parameters can be adjusted with a PC over the network Yellow Status LED A yellow on board status LED aids in diagnostics by indicating the water source heat pump op...

Страница 5: ...pressor Once the overflow alarm disappears the unit controller automatically resets the WSHP unit The condensate overflow sensor is an exposed ring terminal located in the condensate drain pan The condensate overflow alarm occurs only when the unit is in cooling mode Brownout Alarm The on board brownout feature is meant to protect the compressor contactors from low voltage or brownout conditions I...

Страница 6: ... point and de energizes when the space temperature exceeds the heating set point plus a configurable differential set point defaulted to 3 F Motorized Valve Relay The relay provides output to the motorized valve to shut off water through the unit when the compressor is not operating Fresh Air Damper Relay The relay provides output to the open damper whenever the fan is operating in the occupied cy...

Страница 7: ...tional features The wall mounted sensor must be field installed and field wired to the water source heat pump Terminal Board 1 provides the connections for all room temperature sensor field wiring Refer to the unit wiring diagram provided and to IM 529 MicroTech Room Temperature Sensors for information on wall sensor package installation Figure 5 Wall mounted temp sensor wiring Remote Room Set Poi...

Страница 8: ...e following check lists thoroughly check the electrical installation Wall Sensor Packages 1 Check that the cable is twisted and shielded with drain wire Belden 8729 or equivalent 2 Check that four conductors are available 3 Check that the conductors are terminated at the unit and at the wall sensor package to screw terminal board 1 in accordance with the field wiring diagram on which terminals are...

Страница 9: ... set point 70 F 21 C 35 F to 120 F 1 7 C to 49 C Occupied cooling set point 74 F 23 C 35 F to 120 F 1 7 C to 49 C Fan occupied On On cycle heat cycle cool on Unoccupied heating set point 60 F 16 C 35 F to 120 F 1 7 C to 49 C Unoccupied cooling set point 85 F 29 C 35 F to 120 F 1 7 C to 49 C Fan unoccupied Cycle On cycle Tenant override 1st press 1 00 Off 0 30 to 8 00 Tenant override 2nd press Off ...

Страница 10: ...point to a maximum temperature of USHS DIFF The fan also de energizes when the space temperature rises above the UHS set point however the controller code prevents the fan from stopping until 12 seconds after the compressor stops Note During normal non alarm operation the compressor is disabled if the stop to stop minimum off timer has not expired 5 minutes fixed Occupied Operating Mode The descri...

Страница 11: ... than 10 seconds causes the Neuron chip to broadcast a message over the Lon network containing its unique 48 bit Neuron ID This is useful during network commissioning Load Shed Mode LONWORKS only When the network load shed level is less than or equal to the load shed threshold setting in the unit load shedding is activated The amount the controller adjusts the set points depends upon the network t...

Страница 12: ...ate the cause of a manual reset fault before placing the unit back into service Alarm Fault Descriptions Table 6 below describes the alarm faults how they are triggered the factory settings that trigger them and how they are reset A detailed discussion of each follows High Pressure Fault The High Pressure fault indicates that the high pressure switch input J4 9 sensed an open circuit while the con...

Страница 13: ...indicates the water source heat pump is sensing low voltage levels It is designed to protect the compressor and contactors from low line voltage or brownout conditions The controller is programmed with a brownout set point that corresponds to 82 of the water source heat pump s nameplate line voltage value If the water source heat pump controller senses a voltage level less than its set point for m...

Страница 14: ...P controller diagnostics Approximately 40 seconds after power is applied to the WSHP the status LED should illuminate as shown in Table 2 on page 2 If not either there is a software problem or the WSHP controller is defective Power Supply Problems The WSHP controller requires a 24 VAC power supply It is connected to the board at the section labeled 24V GND and 24 VAC terminals J41 and J42 Refer to...

Страница 15: ...the digital input circuit 4 Measure the resistance through the switch contacts with at least one wire disconnected The switches normally are closed Brownout Fault The WSHP controller senses the AC voltage at the power input section terminals J41 and J42 see unit wiring diagram If the voltage at these terminals is less than 19 68 VAC for at least 1 second the brownout fault occurs The fault automat...

Страница 16: ...mperature sensor common J6 1 7 Auxiliary module connections Table 11 Thermistor chart C 10 k ohm F C 10 k ohm F 18 8 654 0 28 0 8777 82 17 8 173 1 29 0 8408 84 16 7 722 3 30 0 8056 86 15 7 298 5 31 0 7721 88 14 6 900 7 32 0 7402 90 13 6 526 9 33 0 7098 91 12 6 175 10 34 0 6808 93 11 5 845 12 35 0 6531 95 10 5 534 14 36 0 6267 97 9 5 242 16 37 0 6015 99 8 4 967 18 38 0 5774 100 7 4 708 19 39 0 5545...

Страница 17: ...McQuay IM 660 3 15 ...

Страница 18: ...McQuay IM 660 3 16 ...

Страница 19: ......

Страница 20: ...pment its care should be a high priority For training information on all McQuay HVAC products please visit us at www mcquay com and click on training or call 540 248 9646 and ask for the Training Department This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com ...

Отзывы: