7
Application Information
M5MSY
_(i)
Installation Guideline
Installation of Outdoor Unit
• The outdoor unit must be installed in such a way, so as to prevent short circuit of the hot discharged air or
obstruction to the smooth air
fl
ow. Please follow the installation clearance shown in the
fi
gures below. Select
the coolest possible place where intake air temperature is not greater than the outside air temperature
(maximum 45°C/113°F)
• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust air
fl
ow, follow the installation
guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
More than 100
Wall facing two sides
Wall facing one side
Wall facing three sides
More than 350
More than 50
More than 50
Top View
Top View
Side View
More
than 100
More than 350
More than 100
More than 350
More than 50
Unit : mm
1200
or less
• There are 2 holes on the base of Outdoor Unit for
condensed water to
fl
ow out. Insert the drain elbow
to one of the holes.
• To install the drain elbow,
fi
rst insert one portion
of the hook to the base (portion A), then pull the
drain elbow in the direction shown by the arrow
while inserting the other portion to the base. After
installation, check to ensure that the drain elbow
clings to base
fi
rmly.
• If the unit is installed in a snowy and chilly area,
condensed water may freeze in the base. In such
case, please remove plug at the bottom of unit to
smooth the drainage.
PLEASE REMOVE
ACCESS PANEL &
PLASTIC VALVE
COVER WHEN
CONNECTING
THE PIPING AND
CONNECTING
CORD.
PUSH & PULL UP
A
DRAIN
ELBOW
Plug
BASE
DRAIN
ELBOW
• Before installing the piping and connecting cord, please remove the access panel and plastic valve cover for
easy access. Refer to
fi
gures shown below.
Содержание M5MSY18BR
Страница 14: ...12 M5MSY_ i Application Information The diagrams below show the screws position for duct work connection...
Страница 35: ...33 Outline and Dimension M5MSY_ i Indoor Unit Model M5CMY 15 20 25ER Note Dimension in mm...
Страница 38: ...36 M5MSY_ i Wiring Diagram Indoor Unit Model M5WMY10 15JR LR Indoor Unit Model M5WMY20JR...
Страница 39: ...37 Wiring Diagram M5MSY_ i Indoor Unit Model M5CKY10 15 20CR Indoor Unit Model M5CCY10 15CR...
Страница 40: ...38 M5MSY_ i Wiring Diagram Indoor Unit Model M5CCY20CR Indoor Unit Model M5CMY15ER...