background image

Page 8 / IM 778

Operating Limits

Standard Range

Geothermal Range

Units

Units

Cooling

Heating

Cooling

Heating

Min. Ambient Air

50˚F/10˚C 50˚F/10˚C

40˚F/5˚C 

40˚F/5˚C  

Normal Ambient Air

80˚F/27˚C 70˚F/21˚C

80˚F/27˚C 70˚F/21˚C

Max. Ambient Air

100˚F/38˚C 85˚F/29˚C 100˚F/38˚C 85˚F/29˚C

Min. Ent. Air 

➀ ➁

50˚F/10˚C 50˚F/10˚C

50˚F/10˚C

40˚F/5˚C

Normal Ent. Air,

80/67˚F

70˚F

80/67˚F

70˚F

dw/wb

27/19˚C

21˚C

27/19˚C

21˚C

Max. Ent. Air

100/83˚F

80˚F

100/83˚F

80˚C

db/wb 

➀ ➁

38/28˚C

27˚C

38/28˚C

27˚C

At ARI flow rate.

Maximum and minimum values may not be combined. If one
value is at maximum or minimum, the other two conditions
may not exceed the normal condition for standard units.
Extended range units may combine any two maximum or
minimum conditions, but not more than two, with all other
conditions being normal conditions.

This equipment is designed for indoor installation only.
Sheltered locations such as attics, garages, etc., generally
will not provide sufficient protection against extremes in

Environment

Standard Range units FCV

Units are designed to start-up in an ambient of 50°F (10°C),
with entering air at 50°F (10°C), with entering water at 70°F
(21°C), with both air and water flow rates used in the ARI
Standard 320-86 rating test, for initial start-up in winter.

Note: This is not a normal or continuous operating con-

dition. It is assumed that such a start-up is for the purpose
of bringing the building space up to occupancy 
temperature.

Geothermal range units FCW

Geothermal range heat pump conditioners are designed to
start-up in an ambient of 40°F (5°C), with entering air at
40°F (5°C), with entering water at 25°F (-4°C), with both air
and water at flow rates used in the ARI Standard 330-86
rating test, for initial start-up in winter.

Note: This is not a normal or continuous operating con-

dition. It is assumed that such a start-up is for the purpose
of bringing the building space up to occupancy 
temperature.

temperature and/or humidity, and equipment performance,
reliability, and service life may be adversely affected.

Air limits

Water limits

Standard Range

Geothermal Range

Units

Units

Cooling

Heating

Cooling

Heating

Min. Ent. Water 

➀ ➁

55°F/13°C 55°F/13°C

30°F/-1°C 20°F/-6°C

Normal Ent. Water

85°F/29˚C 70˚F/21°C

77°F/25˚C

40˚F/5°C

Max. Ent. Water 

➀ ➁

110°F/43˚C 90°F/32°C 110°F/43˚C 90°F/32°C

Additional Information For Initial Start-up Only

Operating voltages

115/60/1 . . . . . . . . . . . . . . . 104 volts min.; 127 volts max.
208-230/60/1 . . . . . . . . . . . 197 volts min.; 253 volts max.
265/60/1 . . . . . . . . . . . . . . . 238 volts min.; 292 volts max.
230/50/1 . . . . . . . . . . . . . . . 197 volts min.; 253 volts max.
460/60/3 . . . . . . . . . . . . . . . 414 volts min.; 506 volts max.
380/50/3 . . . . . . . . . . . . . . . 342 volts min.; 418 volts max.
575/60/3 . . . . . . . . . . . . . . . 515 volts min.; 632 volts max.

Note: Voltages listed are to show voltage range. However,
units operating with over voltage and under voltage for
extended periods of time will experience premature com-
ponent failure. Three phase system unbalance should not
exceed 2%.

Содержание Enfinity series

Страница 1: ...ng Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 Options for Mark IV AC Units 17 21 Field Installed Options on MicroTech U...

Страница 2: ...the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly marked on submittal drawings 6 The installing contractor will find it b...

Страница 3: ...controls are required boilerless system space must be provided for the enclosure to mount around the corner from the electrical entrances Do not locate the side of the unit too close to a wall See Fi...

Страница 4: ...he return air duct should be internally lined with acoustic insulation for sound attenuation Glass fiber duct board material is more absorbing and may permit omission of the flexible connector Return...

Страница 5: ...lance by measuring differential temperature reading across the water connections For proper water flow the differential flow should be 10 F to 14 F 5 C to 8 C for units in cooling mode A direct return...

Страница 6: ...be off and the supplementary heat control set at 80 F 27 C While circulating water the contractor should check and repair any leaks in the piping Drains at the lowest point s in the system should be o...

Страница 7: ...xceeds 35 F 19 C then the water flow rate is inade quate 6 Check the elevation and cleanliness of the condensate line If the air is too dry for sufficient dehumidification slowly pour enough water int...

Страница 8: ...assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature Geothermal range units FCW Geothermal range heat pump conditioners are designed to start up i...

Страница 9: ...er primary wire 2 All temperature and pressure switches are nor mally closed 3 Component layout shown below is typical Some components may not be used on this model or voltage 4 Mark IV AC controller...

Страница 10: ...y is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...or 208V operation If 230V power supply is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer...

Страница 12: ...On Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On In heating mode only The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high pres sure an...

Страница 13: ...it Controller Figure 16 MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied On 5 1 2 sec Off 1 2 sec Tena...

Страница 14: ...during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling the compressor and fan start immediately Compressor run time is cal culat...

Страница 15: ...hours of operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm automatically resets when the atta...

Страница 16: ...IA204 4 for ther mostat 668054201 installation details Includes Thermostat and Wall Plate Refer to the installation operation application guide LIA217 for thermo stat 107095901 installation details 1...

Страница 17: ...ite connections are short flying leads pre attached to the board The diagrams shown are some connection examples Auxiliary Relay P N 106059701 WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W...

Страница 18: ...ontrol box clos est to the thermostat The G W Y C and L con nections are short flying leads pre attached to the board A maximum of 3 boards may be used together if up to 4 units must be connected and...

Страница 19: ...rminal must be used as a pump restart signal to other equipment then wire the auxiliary relay s yellow wire to Y1 white wire to W1 and orange wire to C then the valve will open on a call for occupied...

Страница 20: ...SK is required for each unit To use the BSK kit you attach the sheet metal enclosure to the unit as shown route the 4 wire harness through knockouts and connect to the Mark IV AC board mount and conne...

Страница 21: ...oop pump if Off The pump restart relay kit is typically mounted within one WSHP or within the LWC panel whichever is more conve nient diagrams are provided below for each location To install the relay...

Страница 22: ...Auxiliary Module Kit 107239001 must be used and these additional output con trol signals will be connected to the Auxiliary board The Auxiliary board is provided in all 2 circuit units 1 circuit unit...

Страница 23: ...t Pump and not accessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s ther mostat...

Страница 24: ...ure lockout A Cool mode check water flow B Heating mode check air flow C Check reversing valve for proper valve position Check compressor overload make sure it is closed Check compressor to ground or...

Страница 25: ...nges Check filters at 60 day intervals for the first year until experience is acquired If light cannot be seen through the filter when held up to sunlight or a bright light it should be changed A more...

Страница 26: ...ulb and Capillary Tube Compressor Coil Air to Refrigerant Heat Exchanger Normal Low Troubleshooting Refrigeration Circuit Cooling Refrigeration Cycle When the wall thermostat is calling for COOLING th...

Страница 27: ...o to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an...

Отзывы: