McQuay Enfinity series Скачать руководство пользователя страница 12

Page 12 / IM 778

Unit Operation

The Mark IV/AC circuit board is an optional control sys-

tem with built-in features such as random start, compressor
time delay, night setback, load shed, shutdown, conden-
sate overflow protection, defrost cycle, brownout, and
LED/fault outputs. Figure 13 shows the LED and fault out-
put sequences. 

The unit has been designed for operation with a 24 volt

mercury bulb type wall thermostat or a microelectronic wall
thermostat selected by the manufacturer. Do not operate
the unit with any other type of wall thermostat.

Each unit has a printed circuit board control system. The

low voltage output from the low voltage terminal strip can
be either AC voltage or DC voltage to the wall thermostat.
This is dependent on what terminals you use. R is A/C volt-
age output and F is D/C voltage output to the wall stat.

The 24 volt low voltage terminal strip is set up so R-G or

F-G energizes the fan, R-Y1 or F-Y1 energizes the com-
pressor for cooling operation, R-W1 or F-W1 energizes the
compressor and reversing valve for heating operation. The
reversing valve is energized in the heating mode. The circuit
board has a fan interlock circuit to energize the fan whenev-
er the compressor is on if the thermostat logic fails to do so. 

Remember the output to the wall stat can be AC current

or DC current. Terminal (R) on the wall stat can be connect-
ed to terminal (R) on the PC board for AC voltage or to ter-
minal (F) on the PC board for DC voltage.

AC current

DC current

R to G = fan only 

F to G = fan only

R to Y1 = cooling

F to Y1 = cooling

R to W1 = heat

F to W1 = heat

The Mark IV/AC control board has a lockout circuit to

stop compressor operation if any one of its safety switches
opens (high pressure switch and low pressure switch on
unit sizes 024 through 060). If the low temperature switch
opens, the unit will go into the cooling mode for 60 seconds
to defrost any slush in the water-to-refrigerant heat
exchanger. After 60 seconds the compressor is locked out.
If the condensate sensor detects a filled drain pan, the
compressor operation will be suspended only in the cooling
mode. The unit is reset by opening and closing the discon-
nect switch on the main power supply to the unit in the
event the unit compressor operation has been suspended
due to low temperature (freezestat) switch, high pressure
switch, or low pressure switch on unit sizes 048 thru 060.
The unit does not have to be reset on a condensate over-
flow detection.

The Mark IV/AC control board fault output sends a sig-

nal to an LED on a wall thermostat. Figure 13 shows for
which functions the fault output is “on” (sending a signal to
the LED).

Figure 13.

LEDs

Fault

Indication

Yellow

Green

Red

Output

Normal Mode

Off

On

Off

Off

High Pressure Fault

Off

Off

Flash

On

Low Temperature Fault*

Flash

Off

Off

On

Condensate Overflow

On

Dim

Off

On

Brownout

Off

Flash

Off

On

Load Shed

Off

Off

On

Off

Unoccupied Mode

On

On

Off

Off

Unit Shutdown

Off

Flash

Off

On

*In heating mode only

The Remote Reset feature provides the means to

remotely reset automatic lockouts generated by high-pres-
sure and/or low-temperature (in heating) faults. When the
Mark IV board is in automatic lockout due to one of these
faults, and the cause of the fault condition has been allevi-
ated, energizing the O-terminal for 10 seconds or more will
force the Mark IV board to clear the lockout. A unit power
cycle can also be used to clear an automatic lockout if the
conditions causing the fault have been alleviated.

The Fault Retry feature helps to minimize nuisance trips

of automatic lockouts caused by high-pressure and/or low-
temperature (in heating) faults. This feature clears faults the
first two times they occur within a 24-hour period and trig-
gers an automatic lockout on the 3rd fault. The retry count
is reset to zero every 24 hours.

The Mark IV/AC control circuit has built-in night setback

operation. A “grounded’ signal to the “U” terminal on the
low voltage terminal strip puts the unit into the unoccupied
mode for night setback operation. Fan operation terminates
and unit control reverts to the night setback terminal on the
thermostat, W2; day heating and cooling operation is
locked out. R-W2 energizes the compressor and reversing
valve for heating operation. Night setback operation can be
overridden for two hours by toggling the fan switch (inter-
mittently closing the R to O terminals) on the Deluxe Auto
Changeover thermostat. Day thermostat setpoints then
control the heating and cooling operation. The Mark IV/AC
control system also accommodates load shed and shut-
down operation on receipt of a “grounded” signal to the “L”
and “E” terminals, respectively, on the low voltage terminal
strip.

Figure 14.

The P and C terminals of the Mark IV/AC board are used

for pump restart. These terminals pass a voltage signal
whenever the unit compressor is turned on. This signal is
detected by a pump restart relay board providing a N.O. or
N.C. set of contacts for heat pump loop circulation pump
control. When used with the Loop Water Controller, the
relay operation accommodates turning off circulation
pumps during unoccupied periods with a safety override
dependent, at minimum, on WSHP’s need. The P and C ter-
minals may be “daisy chained” between 200 units. See
page 19.

Field supplied relays installed on the input terminals W1,

W2, Y1, Y2 or G may introduce electrical noise. Never install
relay coils in series with the inputs.

Chassis
Ground

Unit

1

Unit

2

Unit

3

To

Additional

Units

Time

Clock

To activate the unoccupied mode for units on the same clock schedule,
a single wire can be “daisy chained” between units and simply ground-
ed through the time clock contacts. The same system can also be done
to activate the load shed and unit shutdown modes by running addi-
tional wires between units to ground.

Three types of units are available: Mark IV/AC control units or units equipped with a MicroTech™ 2000 or BACnet

®

Water

Source Heat Pump Controller.

Mark IV/AC Control Units

Содержание Enfinity series

Страница 1: ...ng Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 Options for Mark IV AC Units 17 21 Field Installed Options on MicroTech U...

Страница 2: ...the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly marked on submittal drawings 6 The installing contractor will find it b...

Страница 3: ...controls are required boilerless system space must be provided for the enclosure to mount around the corner from the electrical entrances Do not locate the side of the unit too close to a wall See Fi...

Страница 4: ...he return air duct should be internally lined with acoustic insulation for sound attenuation Glass fiber duct board material is more absorbing and may permit omission of the flexible connector Return...

Страница 5: ...lance by measuring differential temperature reading across the water connections For proper water flow the differential flow should be 10 F to 14 F 5 C to 8 C for units in cooling mode A direct return...

Страница 6: ...be off and the supplementary heat control set at 80 F 27 C While circulating water the contractor should check and repair any leaks in the piping Drains at the lowest point s in the system should be o...

Страница 7: ...xceeds 35 F 19 C then the water flow rate is inade quate 6 Check the elevation and cleanliness of the condensate line If the air is too dry for sufficient dehumidification slowly pour enough water int...

Страница 8: ...assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature Geothermal range units FCW Geothermal range heat pump conditioners are designed to start up i...

Страница 9: ...er primary wire 2 All temperature and pressure switches are nor mally closed 3 Component layout shown below is typical Some components may not be used on this model or voltage 4 Mark IV AC controller...

Страница 10: ...y is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...or 208V operation If 230V power supply is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer...

Страница 12: ...On Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On In heating mode only The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high pres sure an...

Страница 13: ...it Controller Figure 16 MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied On 5 1 2 sec Off 1 2 sec Tena...

Страница 14: ...during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling the compressor and fan start immediately Compressor run time is cal culat...

Страница 15: ...hours of operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm automatically resets when the atta...

Страница 16: ...IA204 4 for ther mostat 668054201 installation details Includes Thermostat and Wall Plate Refer to the installation operation application guide LIA217 for thermo stat 107095901 installation details 1...

Страница 17: ...ite connections are short flying leads pre attached to the board The diagrams shown are some connection examples Auxiliary Relay P N 106059701 WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W...

Страница 18: ...ontrol box clos est to the thermostat The G W Y C and L con nections are short flying leads pre attached to the board A maximum of 3 boards may be used together if up to 4 units must be connected and...

Страница 19: ...rminal must be used as a pump restart signal to other equipment then wire the auxiliary relay s yellow wire to Y1 white wire to W1 and orange wire to C then the valve will open on a call for occupied...

Страница 20: ...SK is required for each unit To use the BSK kit you attach the sheet metal enclosure to the unit as shown route the 4 wire harness through knockouts and connect to the Mark IV AC board mount and conne...

Страница 21: ...oop pump if Off The pump restart relay kit is typically mounted within one WSHP or within the LWC panel whichever is more conve nient diagrams are provided below for each location To install the relay...

Страница 22: ...Auxiliary Module Kit 107239001 must be used and these additional output con trol signals will be connected to the Auxiliary board The Auxiliary board is provided in all 2 circuit units 1 circuit unit...

Страница 23: ...t Pump and not accessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s ther mostat...

Страница 24: ...ure lockout A Cool mode check water flow B Heating mode check air flow C Check reversing valve for proper valve position Check compressor overload make sure it is closed Check compressor to ground or...

Страница 25: ...nges Check filters at 60 day intervals for the first year until experience is acquired If light cannot be seen through the filter when held up to sunlight or a bright light it should be changed A more...

Страница 26: ...ulb and Capillary Tube Compressor Coil Air to Refrigerant Heat Exchanger Normal Low Troubleshooting Refrigeration Circuit Cooling Refrigeration Cycle When the wall thermostat is calling for COOLING th...

Страница 27: ...o to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an...

Отзывы: