background image

Page 14 / IM 778

McQuay Enfinity vertical water source heat pumps are
available with a factory mounted and tested  Alerton BACnet
unit controller as a special. The unit controller is factory pro-
grammed and tested with all the logic required to control the
unit, and is designed to communicate over a BACnet MS/TP
communications network to an Alerton BACtalk building
automation system (BAS). The controller operates the com-
pressor, fan, and reversing valve as required to maintain the
space temperature within the current setpoints. Data
regarding equipment status, water and air temperatures,
and fault conditions can be monitored by an Alerton BACtalk
BAS. Setpoints and other system preferences may be
changed remotely using an Alerton BACtalk workstation or
Alerton service tool software.

The controller makes operational data and commands
available on the Alerton BACtalk network using BACnet
objects and properties. Each heat pump controller connects
to the BACtalk network using a BACnet MS/TP LAN, which
is a simple twisted-pair communications connection that
operates at up to 76.8 Kbps. DIP switches on the controller
enable the MS/TP MAC address to be set in the range 0-
127. A status LED on the unit indicates communication
activity on the MS/TP LAN.

Each BACnet-compliant unit includes discharge air and
leaving water temperature sensors, as well as all safety
sensors, signals, and switches. Wall-mounted room sen-
sors are available from Alerton to control heating and cool-
ing operation. Available sensors include tamper-resistant
stainless steel wall sensors with optional push-button for
status override; wall-mounted sensors with tenant setpoint
adjustment lever and timed-override button; wall-mounted
sensors with LED status, timed-override button, tenant set-
point adjustment buttons, password-protected field service
access to operational data, and optional humidity sensor;
and wall-mounted sensors with LCD and programmable
operation.

Figure 18. BACnet

®

WSHP unit controller

Each BACnet-compliant controller has the following operat-
ing features:

Start-up – The unit will not operate until all the inputs
and safety controls are checked for normal conditions.

Fan operation – Fan operation can be customized in
software to run continuously during occupied mode, or to
cycle ON or OFF appropriately on a call for heating and
cooling.

Cooling mode – On a call for cooling, the compressor
and fan start immediately. Compressor run-time is cal-
culated as a percent of full cycle time (17 minutes) using
proportional-integral control to maximize efficiency.

Heating mode – On a call for heating, the compressor
and fan start immediately, and compressor run-time is
calculated as a percent of full cycle time (17 minutes)
using proportional-integral control to maximize 
efficiency.

Short Cycle Protection and Random Start – A start
delay of 180 seconds plus the compressor’s MAC
address in seconds prevents short-cycling and simulta-
neous start-up. A minimum 2-minute on time and 5-
minute off time for the compressor further ensures short-
cycle protection.

Occupied Mode – A simple software control signal from
the building automation system or a wall-mounted unit
puts the unit into occupied mode. The unit controls com-
pressor and fan operation to maintain occupied set-
points. High and low limits for occupied setpoints are
software configurable.

Unoccupied Mode – A simple software control signal
from the building automation system or a wall-mounted
unit puts the unit into unoccupied mode for night setback
operation. The unit controls compressor and fan opera-
tion to maintain unoccupied heating and cooling set-
points, which are also software configurable.

After-hours Override Mode – A simple software control
signal from the building automation system or a wall-
mounted unit can initiate after-hours heating or cooling
in half-hour increments. Maximum override time is soft-
ware configurable up to 9.5 hours. This feature can also
be disabled in software.

Reversing valve delay – When the compressor turns
off after heating mode, the reversing valve remains ener-
gized for 60 seconds before it returns to the normal cool-
ing position to eliminate swishing. The reversing valve
energizes 10 seconds before the compressor.

Load Shed – Load shedding can be orchestrated by the
building automation system using the occupied/unoccu-
pied command in software.

Brownout Protection – An onboard sensor measures
input voltage and suspends compressor and fan opera-
tion if the supply voltage drops below 82% of the normal
line voltage for a minimum of 10 seconds, creating an
alarm available in software. The alarm automatically
resets when the supply voltage returns to above 90% of
normal.

BACnet

®

WSHP Unit Controller

Содержание Enfinity series

Страница 1: ...ng Flushing System 6 Start up 7 Operating Limits 8 Typical Wiring Diagrams 9 11 Unit Operation 12 14 Thermostat Connections 16 Options for Mark IV AC Units 17 21 Field Installed Options on MicroTech U...

Страница 2: ...the location and routing of water piping conden sate drain piping and electrical wiring The locations of these items are clearly marked on submittal drawings 6 The installing contractor will find it b...

Страница 3: ...controls are required boilerless system space must be provided for the enclosure to mount around the corner from the electrical entrances Do not locate the side of the unit too close to a wall See Fi...

Страница 4: ...he return air duct should be internally lined with acoustic insulation for sound attenuation Glass fiber duct board material is more absorbing and may permit omission of the flexible connector Return...

Страница 5: ...lance by measuring differential temperature reading across the water connections For proper water flow the differential flow should be 10 F to 14 F 5 C to 8 C for units in cooling mode A direct return...

Страница 6: ...be off and the supplementary heat control set at 80 F 27 C While circulating water the contractor should check and repair any leaks in the piping Drains at the lowest point s in the system should be o...

Страница 7: ...xceeds 35 F 19 C then the water flow rate is inade quate 6 Check the elevation and cleanliness of the condensate line If the air is too dry for sufficient dehumidification slowly pour enough water int...

Страница 8: ...assumed that such a start up is for the purpose of bringing the building space up to occupancy temperature Geothermal range units FCW Geothermal range heat pump conditioners are designed to start up i...

Страница 9: ...er primary wire 2 All temperature and pressure switches are nor mally closed 3 Component layout shown below is typical Some components may not be used on this model or voltage 4 Mark IV AC controller...

Страница 10: ...y is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer primary wire Place an insulation cap...

Страница 11: ...or 208V operation If 230V power supply is used transformer must be rewired by disconnecting the power lead from the red transformer primary wire and connecting the power lead to the orange transformer...

Страница 12: ...On Off Unoccupied Mode On On Off Off Unit Shutdown Off Flash Off On In heating mode only The Remote Reset feature provides the means to remotely reset automatic lockouts generated by high pres sure an...

Страница 13: ...it Controller Figure 16 MicroTech 2000 Unit Controller LED Indication Status LED State Mode On Continually Occupied Occupied Load Shed On 1 2 sec Off 5 1 2 sec Unoccupied On 5 1 2 sec Off 1 2 sec Tena...

Страница 14: ...during occupied mode or to cycle ON or OFF appropriately on a call for heating and cooling Cooling mode On a call for cooling the compressor and fan start immediately Compressor run time is cal culat...

Страница 15: ...hours of operation the attained temperature does not meet the software configurable setpoint for heating or cooling as appropriate a software alarm occurs The alarm automatically resets when the atta...

Страница 16: ...IA204 4 for ther mostat 668054201 installation details Includes Thermostat and Wall Plate Refer to the installation operation application guide LIA217 for thermo stat 107095901 installation details 1...

Страница 17: ...ite connections are short flying leads pre attached to the board The diagrams shown are some connection examples Auxiliary Relay P N 106059701 WSHP Mark IV AC Board Low Voltage Terminal Strip O W2 G W...

Страница 18: ...ontrol box clos est to the thermostat The G W Y C and L con nections are short flying leads pre attached to the board A maximum of 3 boards may be used together if up to 4 units must be connected and...

Страница 19: ...rminal must be used as a pump restart signal to other equipment then wire the auxiliary relay s yellow wire to Y1 white wire to W1 and orange wire to C then the valve will open on a call for occupied...

Страница 20: ...SK is required for each unit To use the BSK kit you attach the sheet metal enclosure to the unit as shown route the 4 wire harness through knockouts and connect to the Mark IV AC board mount and conne...

Страница 21: ...oop pump if Off The pump restart relay kit is typically mounted within one WSHP or within the LWC panel whichever is more conve nient diagrams are provided below for each location To install the relay...

Страница 22: ...Auxiliary Module Kit 107239001 must be used and these additional output con trol signals will be connected to the Auxiliary board The Auxiliary board is provided in all 2 circuit units 1 circuit unit...

Страница 23: ...t Pump and not accessible to the end user For example HP LT and COF are not available for use by the end user Typically the Mark IV AC board s R 24vac terminal is used to drive the board s ther mostat...

Страница 24: ...ure lockout A Cool mode check water flow B Heating mode check air flow C Check reversing valve for proper valve position Check compressor overload make sure it is closed Check compressor to ground or...

Страница 25: ...nges Check filters at 60 day intervals for the first year until experience is acquired If light cannot be seen through the filter when held up to sunlight or a bright light it should be changed A more...

Страница 26: ...ulb and Capillary Tube Compressor Coil Air to Refrigerant Heat Exchanger Normal Low Troubleshooting Refrigeration Circuit Cooling Refrigeration Cycle When the wall thermostat is calling for COOLING th...

Страница 27: ...o to www mcquay com This document contains the most current product information as of this printing For the most up to date product information please go to www mcquay com Products Manufactured in an...

Отзывы: