A.
Compressors: The compressors shall be two sets of tandem hermetic scroll type with
discharge service valve, crankcase oil heater and suction strainer. Compressors shall
have a forced feed lubrication system with a reversible oil pump and factory oil
charge. The compressor motors shall be refrigerant gas cooled, high torque,
hermetic induction type, two-pole, with inherent thermal protection on all three
phases and shall be mounted on RIS vibration isolator pads.
B.
Evaporator: The evaporator shall be direct expansion, shell and tube with carbon
steel shell and high efficiency copper tubes rolled into steel tube sheets. Internal
baffles shall be polypropylene. The refrigerant heads shall have multi-pass baffles to
insure oil return and be removable to permit access to the tubes from either end.
The shall be insulated with 3/4 inch (19mm) closed cell polymer insulation with a
minimum K factor of 0.28 at 75
°
F (23
°
C) and be heated with an electric heater to
provide freeze protection to -20°F (-29°C) ambient temperature. The refrigerant
side working pressure shall be at least 225 psig (1552 kPa). The water side working
pressure shall be at least 175 psig (1207 kPa) The evaporator must be designed,
constructed, inspected, and stamped according to the ASME Code.
C.
Condenser: The condenser coils shall consist of 3/8 inch (10mm) seamless copper
tubes mechanically bonded into plate type fins. The fins shall have full drawn
collars to completely cover the tubes. A subcooling coil shall be an integral part of
the main condenser coil. Condenser fans shall be propeller type arranged for vertical
air discharge and individually driven by direct drive fan motors. Each fan shall be in
its own compartment to eliminate cross flow of condenser air during fan cycling and
shall be equipped with a heavy-gauge vinyl coated fan guard. Fan motors shall be
weather protected, three-phase, direct-drive, 1140 rpm, open drip-proof type.
External coils shall have wire mesh protective guards.
D.
Refrigerant Circuit: The refrigerant circuit shall include a liquid line shutoff valve,
refrigerant filter-drier, sight glass with moisture indicator, liquid line solenoid valve
(no exceptions), thermal expansion valve, and insulated suction line.
E.
Control System: A centrally located weatherproof control panel shall contain the
field power connection points, control interlock terminals, and control system.
Power and starting components shall include factory fusing of fan motors and
control circuit; individual contactors for each fan motor, solid-state start timer,
solid-state three-phase motor overload protection, inherent fan motor overload
protection and unit power terminal blocks for connection to remote disconnect
switch. Terminals shall also be provided for power supply to the evaporator heater
circuit. Hinged access doors shall be lockable. Barrier panels are required to
protect against accidental contact with line voltage when accessing the control
system. The operating and safety controls shall be: