42
AGZ 030A through 065A
Product Manual AGZ-2
1.05
DELIVERY AND HANDLING
A.
Chillers shall be delivered to the job site completely assembled and charged with
refrigerant and oil by the manufacturer.
B.
Comply with the manufacturers instructions for rigging and handling equipment.
1.06.
WARRANTY
The refrigeration equipment manufacturer’s warranty shall be for a period of one year from
date of equipment start up but not more than 18 months from shipment. The warranty shall
cover material and workmanship that prove defective within the above period, excluding
refrigerant.
1.07
MAINTENANCE
Maintenance of the chillers shall be the responsibility of the owner and performed in
accordance with the manufacturer’s instructions.
PART 2--PRODUCTS
2.01
ACCEPTABLE MANUFACTURERS
A.
McQuay International
B.
(Approved Equal)
2.02
UNIT DESCRIPTION
Provide and install as shown on the plans factory assembled, factory charged, and factory run
tested air-cooled scroll compressor packaged chillers in the quantity specified. Each chiller
shall consist of hermetic tandem scroll compressors, multi-circuit direct expansion
evaporator, air-cooled condenser section, control system and all components necessary for
safe and controlled unit operation.
2.03
DESIGN REQUIREMENTS
A.
General: Provide a complete scroll compressor packaged chiller as specified herein
and as shown on the drawings. The unit shall be in accordance with the standards
referenced in section 1.02 and any local codes in effect.
B.
Performance: Refer to the schedule of performance on the drawings. The chiller
shall be capable of stable operation to a minimum of 30 percent of full load without
hot gas bypass. Performance shall be in accordance with ARI Standard 590.
C.
Acoustics: Sound pressure levels for the unit shall not exceed the following
specified levels. The manufacturer shall provide the necessary sound treatment to
meet these levels if required. Sound data shall be provided with the quotation and be
measured at 30 feet from the unit and one meter above the unit base line
Octave Band
63
125
250
500
1000
2000
4000
8000
dBA
____ _____ ____ ____ _____ ____ ____ _____ _____