![McQuay AGZ 030AM Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/mcquay/agz-030am/agz-030am_product-manual_1756096016.webp)
16
AGZ 030A through 065A
Product Manual AGZ-2
Table 6, Recommended Horizontal or Downflow Suction Line Size
Connection
Recommended Suction Line Sizes
Unit Model
Size
Up to
Up to
Up to
Up to
Up to
At Unit
50 Equiv. Ft
75 Equiv. Ft
100 Equiv. Ft
125 Equiv. Ft
150 Equiv. Ft
AGZ030AM
1 5/8"
1 5/8"
1 5/8"
1 5/8"
1 5/8"
2 1/8"
AGZ035AM
1 5/8"
1 5/8"
1 5/8"
2 1/8"
2 1/8"
2 1/8"
AGZ040AM
1 5/8"
1 5/8"
1 5/8"
2 1/8"
2 1/8"
2 1/8"
AGZ045AM
1 5/8"
1 5/8"
2 1/8"
2 1/8"
2 1/8"
2 1/8"
AGZ050AM
1 5/8"
1 5/8"
2 1/8"
2 1/8"
2 1/8"
2 1/8"
Note: For horizontal and vertical downflow only
Table 7, Minimum Line Size (R-22) For Oil Carry Up a Suction Riser
Unit Size OD
AGZ 030
AGZ 035
AGR 040
AGZ 045
AGZ 050
Line Size
1 5/8
1 5/8
1 5/8
1 5/8
1 5/8
Table 8, Refrigerant Piping Derates
Unit Model
Capacity Loss Factor Due to Refrigerant Piping
At Unit
50 Equiv. Ft
75 Equiv. Ft
100 Equiv. Ft
125 Equiv. Ft
150 Equiv. Ft
AGZ030AM
1.0
0.984
0.975
0.966
0.957
0.987
AGZ035AM
1.0
0.973
0.960
0.987
0.984
0.981
AGZ040AM
1.0
0.971
0.957
0.984
0.980
0.976
AGZ045AM
1.0
0.957
0.985
0.980
0.975
0.971
AGZ050AM
1.0
0.957
0.981
0.975
0.969
0.962