background image

 

Service manual V1.0 

 

Page 

7

 of 10

 

 

     www.mcedsystems.com

 

 

4.3.

 

R

EPLACE MOTOR OF CIRCULATING PUMP 

 

BEF-04,

 

BEF-05

 

&

 

BEF-075 

1. 

Unplug the motor and the unit from their electrical circuit. 

2. 

Remove the pump mounting screw (1).  

3. 

Remove the motor mounting screws (4). 

4. 

Replace the defective motor pump and the damper coupling by new ones. 

5. 

Tighten the motor mounting screws (4). 

6. 

Tighten the pump mounting screw (1). 

NOTE: Make sure the pump is properly aligned with the damper coupling and the motor. 

7. 

Reconnect the unit and the motor to their electrical circuit. 

4.4.

 

R

EPLACE TEMPERATURE CONTROLLER

 

NOTE: Before doing any work on electrical components, disconnect the unit from its electrical circuit. 

1.  Dismantle the temperature controller housing.  

 

TIP:

 Keep pictures and notes of the wire connections.  

2.  Remove wire connectors using a small slotted screwdriver. 

3.  Slide off the plastic retainer by applying pressure with a small screw driver on each side. Pull 

out the temperature controller of the housing.

 

4.  Connect wires to the correct numbers on new thermostat and reassemble into housing. 

 

NOTE: Firmly tighten the wire clamp screws. 

Refer to section 0 for the correct wiring. 

5.  Re-install the temperature controller and the plastic retainer.

 

6.  Re-install the housing on the support plate.

 

7. 

Reconnect the unit to the electrical circuit. 

8.  Adjust the temperature controller, Refer to section 2.4. 

4.5.

 

R

EPLACE TEMPERATURE CONTROLLER RELAY

 

NOTE: Before doing any work on electrical components, disconnect the unit from its electrical circuit. 

1.  Dismantle the temperature controller housing.  

 

TIP:

 Keep pictures and notes of the wires connections.  

2.  Remove wire connectors using long nose pliers. 

3.  Remove relay mounting screws (2).

 

4.  Connect wires to correct position on new relay and tighten the mounting screws (2).

 

 

 

 

Содержание BEF-02

Страница 1: ...Service manual V1 0 Page 1 of 10 www mcedsystems com SERVICE MANUAL GLYCOL CHILLERS BEF 02 BEF 04 BEF 05 BEF 075 Version 1 0 Release June 2017 All rights reserved...

Страница 2: ...troller 5 3 Maintenance 6 4 Servicing 6 4 1 Replace circulation pump BEF 02 6 4 2 Replace circulation pump BEF 04 BEF 05 BEF 075 6 4 3 Replace motor of circulating pump BEF 04 BEF 05 BEF 075 7 4 4 Rep...

Страница 3: ...NEMA 5 15P NEMA 5 15P NEMA 5 15P NEMA 5 15P Amps Running 7 0 12 14 16 17 19 21 Refrigerant R134a R134a R134a R134a Refrigerant capacity oz 9 0 17 0 11 0 18 0 Normal refrigeration operating pressure PS...

Страница 4: ...cing Ambient temperature ranges from 60 F to 85 F for all models Make sure the unit is installed in a properly ventilated area Unit must be connected to a ground fault circuit breaker Power pack and p...

Страница 5: ...each pump 5 Fill the reservoir with propylene glycol solution mixed 2 parts water to 1 part glycol 6 Place back the upper deck on the unit 7 Plug the unit and the pump to an appropriate electrical cir...

Страница 6: ...ectrical circuit 2 Pinch the glycol lines to avoid any dumping 3 Disconnect the glycol line from the pump 4 Remove the pump mounting screws 4 5 Replace the defective circulation pump by a new one 6 Ti...

Страница 7: ...ire connectors using a small slotted screwdriver 3 Slide off the plastic retainer by applying pressure with a small screw driver on each side Pull out the temperature controller of the housing 4 Conne...

Страница 8: ...tallic part Refrigerant leak Perform a leak test and repair the leak Vacuum flush the refrigerant and fill with proper quantity Has to be performed by a certified refrigeration expert Dirty condenser...

Страница 9: ...om 6 ELECTRICAL WIRING DIAGRAMS NEVER modify the electrical circuit of the unit If required ONLY use 14 AWG wire Electrical repairs must be done by a professional electrician 6 1 ELECTRICAL DIAGRAM BE...

Страница 10: ...KA7437YXAXA X BEF 075 Condensing unit AJA7455YAADS X BEF 02 Relay K71 36 X BEF 04 Relay K71 41 X BEF 05 Relay K71 02 X BEF 075 Relay K71 13 X BEF 02 Start capacitor K146 55 X BEF 04 Start capacitor K1...

Отзывы: