4. Mounting

The EMBSIN 101 I can be mounted on a top-hat rail.

Note 

“Environmental conditions” 

in Section 

“3. Technical data” when determining the place of 
installation!

Simply clip the device onto the top-hat rail (EN 50 022) (see 
Fig. 1).

Fig. 1. Mounting onto a top-hat rail 35 

×

 15 or 35 

×

 7.5 mm.

5. Electrical connections

Connect the leads acc. to the instructions on nameplate.

Make sure that all cables are not live when 
making the connections!

Impending danger by high power supply 
voltage!
Take care of current transformers!

Also note that, …
… the data required to carry out the prescribed mea-

surement must correspond to those marked on the 
nameplate of the EMBSIN 101 I (

 measuring 

input, 

 measuring output and 

 power 

supply, see Fig. 6)!

… the resistance in the output circuit 

  –  may not 

overrange

 the

 

value

R

ext

 max.  [kΩ] ≤

15 V

I

AN

 [mA]

  (I

AN

 = current output end value)

 – 

with 

 

power supply via output leads

 (2-wire 

connection, output 4 - 20 mA) dependent on 
power supply H (12 - 32 V DC)

   

1000

0

12

24

32

0

600

Exter

nal 

resistance [Ω]

H = Power supply [V]

R

ext

 max.  [kΩ] =

H [V] – 12 V

20 mA

 – 

may 

not 

underrange 

the

 

value

R

ext

 min.  [kΩ] ≥

U

AN

 [V] 

10 mA

  (U

AN

 = voltage output end value)

… the measurement output cables should be twisted 

pairs and run as far as possible away from heavy 
current cables!

In all other respects, observe all local regulations when 
selecting the type of electrical cable and installing them!

Fig. 6. Declaration to type label.

Measuring output
Output signal

Manufacturer

Works No.

Measuring input
Measuring range
Measured quantity

Conformity
marks

Power supply

1 2 3 4

5 6 7 8

3,7

EMBSIN 101I

Mat: 128349 / 4161903

0...5A 50/60 Hz

4–20mA

230 VAC

1 2 3 4

5 6 7 8

– +

I

Fig. 2. AC power supply

1 2 3 4

5 6 7 8

– +

I

– +

Fig. 3. DC power supply.

1 2 3 4

5 6 7 8

I

+

R

ext

+

-

Fig. 4. Power supply via
output leads.

1 2 3 4

5 6 7 8

– +

I

Fig. 5. DC, AC power supply,
in version with built-in
DC, AC power pack.

  = Current measuring input      

  = Measuring output

  = Power supply