Operating Instructions 

 

Transducer for AC current EMBSIN 101 I

Safety precautions to be strictly observed are marked with 
following symbols in the Operating Instructions

The instruments must only be dispo-
sed of in the correct way!

Contents

  1. Read fi rst and then …  ................................................ 6

  2. Brief description .......................................................... 6

  3. Technical data ............................................................. 6

  4. Mounting ..................................................................... 6

  5. Electrical connections ................................................. 6

  6. Commissioning and maintenance ............................... 8

  7. Releasing the transducer ............................................ 8

  8. Instrument admission .................................................. 8

  9. Dimensional drawing ................................................... 8

1. Read fi rst and then …

The proper and safe operation of the device 
assumes that the Operating Instructions is 

read carefully 

and the safety warnings given 

in the various Sections

4. Mounting
5.  Electrical connections

are 

observed

.

The device should only be handled by appropriately trained 
personnel who are familiar with it and authorised to work 
in electrical installations.
Unauthorized repair or alteration of the unit invalidates 
the warranty.

2. Brief description

The transducer EMBSIN 101 I is designed to convert a sinus-
oidal AC current into a DC current or voltage proportional to 
the measured value.

3. Technical data

Measuring input  

Nominal frequency:  

50/60 Hz

Nominal input current:  Acc. to type 0 - 1 or 0 - 5 A
 non-standard 

ranges 

 

0 - 0.8 to 0 - 1.2 A 

 

or 0 - 4 to 0 - 6 A

Own consumption: 

≤ 5 mV · I

N

 with input end value

Measuring output 

DC current:

 

0 - 1 to 0 - 20 mA resp. live-zero

 

0.2 - 1 to 4 - 20 mA

Burden voltage: 

15 V

External resistance: 

See Section “5. Electrical connec-
tions”

With 2-wire 
connection: 

Power supply via output leads,

 

4 - 20 mA,

 

External resistance see Section 
“5. Electrical connections”

Load-independent
DC voltage:

 

0 - 1 to 0 - 10 V resp. live-zero

 

0.2 - 1 to 2 - 10 V

External resistance: 

See Section “5. Electrical connec-
tions”

Response time: 

< 300 ms

Power supply 

 

AC voltage: 

24, 110, 115, 120, 230 or 400 V

 

± 15%, 50 / 60 Hz

 

Power consumption approx. 3 VA, 
see Fig. 2

Options

 

DC voltage: 

24 V, – 15 / + 33 %,

 

power consumption approx. 1.5 W, 
see Fig. 3

 

With 2-wire connection and output 

 

4…20 mA (power supply via output 
leads) 24 V, – 50/+ 33%, 

 

power consumption 1.5 W, 

 

see Fig. 4

DC or AC voltage: 

DC, AC power pack 

 

(DC or 40 - 400 Hz)

 

85 - 230 V DC/AC or

 

24 - 60 V DC/AC

 

DC – 15/+ 33%, AC ± 15%

 Power 

consumption 

 

≤ 1.5 W resp. ≤ 3 VA, see Fig. 5

Accuracy 

(acc. to IEC 688)

Reference value: 

Output end value

Accuracy: Class 

0.5

Safety

Pollution degree: 

2

Installation category: 

III

Reference conditions

Operating temperature: – 10 to + 55 °C

Storage temperature: 

–  40 to + 70 °C

Relative humidity of
annual mean: 

≤ 75 %

Altitude: 

2000 m max.

Indoor use statement