Maytag MLG33PDAWW Скачать руководство пользователя страница 13

113413-1

Telephone: (641) 787-7000

13

Important

No more than 4 dryers should be connected to 1
main common duct.

The illustration below shows the minimum cross-sectional
area for multiple dryer round or square venting.  These figures
must be increased if the main duct run from the last dryer to
where it exhausts to the outdoors is longer than 12 feet (3.656
meters) or has more than 1 elbow in it.

!

NOTE 1 Opening from combustible materials must be 2-inches (5.08 cm)

larger than the duct (all the way around).  The duct must be centered
within this opening.

NOTE 2 Distance should be 2 times the diameter of the duct to the nearest

obstruction.

A = 8-inches (20.32 cm)
B = 12 feet (3.656 meters)

NUMBER OF DRYERS

4

3

2

1

MINIMUM CROSS-

SECTIONAL AREA

SQ IN

164

120

80

54

SQ CM

1058

774.2

516.1

348.4

MINIMUM ROUND
DUCT DIAMETER

IN

14

12

10

8

CM

35.56

30.48

25.4

20.32

MLG33

Important

Failure to comply with these codes or ordinances,
and/or the requirements stipulated in this manual

can result in personal injury or component failure.

Note

Component failure due to improper installation will
void the warranty.

Each pocket should be connected to an independently
protected branch circuit.  The dryer must be connected with
copper wire only.  Do not use aluminum wire, which could
cause a fire hazard.  The copper conductor wire/cable must
be of proper ampacity and insulation in accordance with
electric codes for making all service connections.

Note

The use of aluminum wire will void the warranty.

An individual ground circuit must be provided to

each pocket, do not daisy chain.

Component failure due to improper voltage application will
void the warranty.

The manufacturer reserves the right to make changes in
specifications at any time without notice or obligation.

Important

A separate protected circuit must be provided to
each pocket.

The dryer must be connected to the electric supply shown
on the data label.  In the case of 208 VAC or 240 VAC, the
supply voltage must match the electric service
specifications of the data label exactly.

The wire size must be properly sized to handle the related
current.

Warning

208 VAC and 240 VAC are not the same.  Any
damage done to dryer components due to

improper voltage connections will automatically void the
warranty.

Warning (Gas Models Only)

Dryers built for use with a voltage between 200
and 240 must verify the input voltage during

installation.  If the nominal voltage is outside of the
medium tolerances shown on the diagram below, adjust
the autotransformers, located near the burner assemblies.
To adjust the autotransformer wiring, place the red wire on
the appropriate tap (HIGH, MED, LOW) of the
autotransformer.  For additional wiring details, refer to the
electrical diagram located on the inside of the control
panel.

!

!

!

!

!

Electrical Information_________________

Electrical Requirements

All electrical connections must be made by a properly licensed
and competent electrician.  This is to ensure that the electrical
installation is adequate and conforms to local, state, and
national regulations or codes of the country of origin.  In the
absence of such codes, all electrical connections, materials,
and workmanship must conform to the applicable
requirements of the National Electrical Code ANSI/NFPA NO.
70-LATEST EDITION or in Canada, the Canadian Electrical
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.

TERM

LINE VOLTAGE

50 Hz

60 Hz

HIGH

260
226

283
249

MED

239
208

260
230

LOW

217
189

236
208

!

Multiple Dryer Venting with 8-Inch (20.32 cm) Diameter

720 cfm (20.39 cmm) Exhaust Connections at Common Duct

NOT AVAILABLE

Содержание MLG33PDAWW

Страница 1: ...ent professional AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incendie ou d explosion ou pour viter tout dommage mat riel to...

Страница 2: ...__________________________________ MODELNO _________________ DEALER SNAME _________________________________________________________________________________________ Serial Number s ____________________...

Страница 3: ...Personal injury or fire could result The dryer must never be operated without the lint filter screen in place even if an external lint collection system is used FOR YOUR SAFETY Do not dry mop heads in...

Страница 4: ...mage plastics or rubber and also may be a fire hazard A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer...

Страница 5: ..._________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ______...

Страница 6: ...ER POCKET 40 000 Btu hr 10 080 kcal hr EXHAUST CONNECTION DIAMETER PER POCKET 4 10 16 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T 3 8 M B S...

Страница 7: ...113413 1 Telephone 641 787 7000 7 Specifications _____________________________________________________________________ NOT AVAILABLE...

Страница 8: ...EAT INPUT PER POCKET 55 000 Btu hr 13 860 kcal hr EXHAUST CONNECTION DIAMETER PER POCKET 6 15 24 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T...

Страница 9: ...113413 1 Telephone 641 787 7000 9 MLG33 Specifications _____________________________________________________________...

Страница 10: ...ed in this manual refer to Exhaust Requirements section Important The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clea...

Страница 11: ...ch results in slow drying increased use of energy and shutdown of the burner by the airflow sail switch burner hi limits or lint chamber hi limit protector thermostat The dryer must be installed with...

Страница 12: ...90 elbows should be used in the exhaust duct run If more than the equivalent of 4 90 elbows are used the cross sectional area of the ductwork must be increased Multiple Dryer Common Venting Important...

Страница 13: ...to make changes in specifications at any time without notice or obligation Important A separate protected circuit must be provided to each pocket The dryer must be connected to the electric supply sh...

Страница 14: ...ct voltage When fuses are used they must be dual element time delay current limiting class RK1 or RK5 ONLY Calculate determine correct fuse value by applying either local and or National Electrical Co...

Страница 15: ...strain relief must be installed where the wiring enters the dryer For CE Models Only The means for disconnection from the supply must be incorporated into wiring having a minimum contact separation o...

Страница 16: ...ning Fire or explosion could result due to failure of isolating or disconnecting the gas supply as noted Note Undersized gas piping will result in ignition problems slow drying increased use of energy...

Страница 17: ...M3 H 36 2 705 1 Butane G30 3 175 28 30 40 000 11 72 0 845 kg H 44 2 184 1 Propane G31 2 500 37 40 000 11 72 0 845 kg H 44 2 184 1 Butane G30 3 175 28 30 50 40 000 11 72 0 845 kg H 39 2 527 1 6 1 Prop...

Страница 18: ..._____________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ __________...

Страница 19: ...e the gas train out of the gas train enclosure The carbon ignitor located at the far end of the gas train is very fragile Remove 2 burner tube mounting screws and remove burner tube in order to gain a...

Страница 20: ...gas train engages into the mounting slot Connect the union and the 3 electrical plugs Repeat these steps for the other burner Open all shutoff valves reconnect electrical power to the dryer and test f...

Страница 21: ...ack of the steam coils Important Coil failure due to improper pH level will void the warranty Gas Pressure Testing__________________ For proper operation the gas pressure must be correct consistent an...

Страница 22: ...am Pressure Maximum 125 psig 861 85 kPa Heat Input Normal Load 1 75 Bhp Consumption Approximate 125 psi 8 6 bar 63 lb hr 28 58 kg hr Water pockets in the supply line caused by low points will provide...

Страница 23: ...tumbler drum by hand to be sure it moves freely Check bolts nuts screws terminals and fittings for tightness and security Check that the vent is connected to the dryer and is exhausted to the outdoor...

Страница 24: ...rt and the L C D will display the Dry Cycle selected and the remaining time The dryer will continue through the drying and cooling cycles until the vended time has expired Note To stop the dryer open...

Страница 25: ...r from whom you purchased the equipment and request a dryer warranty form If the dealer cannot be contacted or is unknown warranty information can be obtained from the Maytag Co Note Whenever contacti...

Страница 26: ...Clean lint accumulation from lint chamber thermostat and microprocessor temperature sensor area Warning To avoid the hazard of electrical shock discontinue electrical supply to the dryer Steam Dryers...

Страница 27: ...gas electric or steam 2 Serial Number Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular dryer gas either natura...

Страница 28: ...Part No 113413 1 06 02 05 0...

Отзывы: