12
E. EXHAUST REQUIREMENTS
Exhaust ductwork
should be
designed and installed by a qualified professional. Improperly sized ductwork will
create excessive back pressure, which results in slow drying, increased use of energy, overheating of the dryer,
and shut down of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler) hi-heat thermostats.
The dryer
must be
installed with a proper exhaust duct connection to the outside.
CAUTION:
This dryer produces combustible lint and
must be
exhausted to the outdoors.
CAUTION: IMPROPERLY
SIZED
OR
INSTALLED
EXHAUST
DUCTWORK
CAN
CREATE
A
POTENTIAL
FIRE
HAZARD
.
The exhaust ductwork
should be
laid out in such a way that the ductwork travels as directly as possible to the
outdoors with as few turns as possible. When single dryer 10-inches (25.4 cm) vertical venting is used, the
ductwork from the dryer to the outside exhaust outlet
must not exceed
35 feet (10.67 meters) or for 10-inches
(25.4 cm) horizontal 10 feet (3.05 meters). In the case of multiple (common) dryer venting, the distance from
the last dryer to the outside exhaust outlet
must not exceed
15 feet (4.57 meters). The shape of the exhaust
ductwork is not critical so long as the minimum cross-sectional area is provided.
It is suggested that the use of 90º turns in ducting be avoided; use 30º or 45º angles instead. Excluding basket
(tumbler)/dryer elbow connections or elbows used for outside protection from the weather, no more than two (2)
elbows
should be
used in the exhaust duct run. If more than two (2) elbows are used the cross section area of
the ductwork
must be
increased in proportion to the number of elbows added.
1. Exhaust Connections of Top and Bottom Baskets (Tumblers)
There is no common venting connection provided with the dryer. Each basket (tumbler) exhaust duct is
provided with its own back draft damper. Each basket (tumbler) can be exhausted directly outdoors
independently or connected to a common duct. Both single or common ductwork can be rigid ducting or
flexible ducting. For common connections, a kit (
ADC
Part No. 882035) is available from the factory and
includes the necessary flex ducting, elbows, and “Y” assembly, etc., to join the top and bottom exhausts
together.
ALL
ductwork joints
must be
taped to prevent moisture and lint from escaping into the building.
IMPORTANT:
Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust
duct area
must be
no less than 0 and
must not exceed
0.3 inches (0.74 mb) water
column (W.C.) when both baskets (tumblers) are operating.
NOTE:
Common exhaust connections of top and bottom baskets (tumblers)
should be
installed in
such a manner that the back guards can be removed easily for servicing.
2. Single Dryer Venting
Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust ductwork
should be
laid out in such a way that the ductwork travels as directly as possible to the outdoors with as
few turns as possible. It is suggested that the use of 90º turns in ducting be avoided; use 30º or 45º angles
instead. The shape of the exhaust ductwork is not critical so long as the minimum cross-sectional area is
provided.