10
Even though a 12-inch (30.48 cm) clearance is acceptable, it is recommended that the rear of the dryer be
positioned approximately 2 feet (0.61 meters) away from the nearest obstruction, i.e., wall, for ease of
installation, maintenance, and service.
9. The dryer
must be
installed with a proper exhaust duct connection to the outside.
10. The dryer
must be
installed with provisions for adequate combustion and make-up air supply.
CAUTION:
This dryer produces combustible lint and
must be
exhausted to the outdoors. Every 6
months, inspect the exhaust ducting and remove any lint build up.
C. DRYER ENCLOSURE REQUIREMENTS
Bulkheads and partitions
should be
made of noncombustible materials and
must be
located a minimum of
12-inches (30.48 cm) - (18-inches [45.72 cm] or more is recommended for ease of installation, maintenance, and
service) - above the dryer’s outer top, except along the front of the dryer which may be closed in if desired.
NOTE:
Even though a minimum of 12-inches (30.48 cm) above the dryer’s outer top is acceptable, a
clearance of 18-inches (45.72 cm) or more is suggested for ease of installation and service
(electrical power connections).
NOTE:
When fire sprinkler systems are located above the dryers, a minimum of 12-inches (30.48 cm)
above the dryer’s outer top
is
required
.
NOTE:
Allowances
must be
made for opening the control door.
Dryers may be positioned sidewall to sidewall. However, allowances
must be
made for opening and closing of
the control door and the lint door. It is suggested that the dryer be positioned about 2 feet (0.61 meters) away
from the nearest obstruction for ease of installation, maintenance, and service (to be measured from the back
guard). Refer to the
illustration
on the previous page for details.
NOTE:
Air considerations are important for proper and efficient operation.
Содержание MLG31PCA
Страница 18: ...14...
Страница 19: ...15...
Страница 22: ...18...
Страница 29: ...25...
Страница 51: ...Part No 113364 1 02 11 02 20 2 05 01 02 250...