2. Electrical Service Specifications
IMPORTANT:
The dryer
must be
connected to the electric supply shown on the data label that is
affixed to the left side panel area behind the top control (access) door.
IMPORTANT:
The wire size
must be
properly sized to handle the related current.
NOTE:
Manufacturer reserves the right to make changes in specifications at any time without notice or
obligation.
0 5 2 1 0 3
M DG76PC (Gas)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
NOTES: A.
B.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or
RK5 ONLY. Calculate/determine correct fuse value, by applying either local and/or
National Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw rating and type of
breaker used.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW MINIMUM
WIRE SIZE
FUSING
Dual Element
Time Delay
CIRCUIT
BREAKER
60 Hz
50 Hz
120
1ø
2
13
---
*
20
20
* AWG Stranded Wire...size wire as per National Electrical Code or local codes.