14

Maytag Co.

113430 - 9

!

NOTE 1

Opening from combustible materials must be 2-inches (5.08 cm)
larger than the duct (all the way around).  The duct must be centered
within this opening.

NOTE 2

Distance should be 2 times the diameter of the duct to the nearest
obstruction.

Multiple Dryer (Common) Venting

Important

For extended ductwork runs, the cross-sectional
area of the ductwork can only be increased to an

extent.  When the ductwork approaches the maximum
limits as noted in this manual, a professional HVAC firm
should be consulted for proper venting information.

If it is not feasible to provide separate exhaust ducts for each
dryer, ducts from individual dryers may be channeled into a
“common main duct.”  The individual ducts should enter the
bottom or side of the main duct at an angle not more than 45º
in the direction of airflow.  The main duct should be tapered,
with the diameter increasing before each individual duct is
added.

A = 20 feet (6.10 meters)
B = MDG31: 6-inches (15.24 cm)

MDG51, MDG77: 8-inches (20.32 cm)

!

!

C = 12 feet (3.66 meters)
D = MDG31: 6-inches (15.24 cm)

MDG51, MDG77: 8-inches (20.32 cm)

!

Important

Exhaust back pressure measured by a
manometer/magnehelic in the exhaust duct must

be no less than 0 and must not exceed 0.6 in wc (1.48 mb).

Note

When the exhaust ductwork passes through a wall,
ceiling, or roof made of combustible materials, the

opening must be 2-inches (5.08 cm) larger than the duct
(all the way around).  The duct must be centered within this
opening.
As per the National Fuel Gas Code, “Exhaust ducts for type
2 clothes dryers shall be constructed of sheet metal or
other noncombustible material.  Such ducts shall be
equivalent in strength and corrosion resistance to ducts
made of galvanized sheet steel not less than 26 gauge
(0.0195-inches [0.50 mm]) thick.”

The ductwork for this appliance must be suitable for the
appliance category in accordance with national installation
regulations of the country of destination.

Outside Ductwork Protection

To protect the outside end of the horizontal ductwork from the
weather, a 90° elbow bent downward should be installed
where the exhaust exits the building.  If the ductwork travels
vertically up through the roof, it should be protected from the
weather by using a 180° turn to point the opening downward.
In either case, allow at least twice the diameter of the duct
between the duct opening and the nearest obstruction (refer
to the diagram).

Important

Do not use screens, louvers, or caps on the
outside opening of the exhaust ductwork.

Single Dryer Venting

Important

For extended ductwork runs, the cross-sectional
area of the ductwork can only be increased to an

extent.  When the ductwork approaches the maximum
limits as noted in this manual, a professional HVAC firm
should be consulted for proper venting information.

Horizontal Venting

When horizontal dryer venting is used, the length of the
ductwork from the dryer to the outside exhaust outlet, must
not exceed 20 feet (6.10 meters).  The minimum diameter of
this ductwork must be at least 6-inches (15.24 cm) for MDG31,
and 8-inches (20.32 cm) for MDG51 and MDG77.  Including
tumbler/dryer elbow connections or elbows used for outside
protection from the weather, no more than 1 elbow should be
used in the exhaust duct run.  If more than 1 elbow is used,
the cross-sectional area of the ductwork must be increased.

!

Vertical Venting

When vertical dryer venting is used, the length of the ductwork
from the dryer to the outside exhaust outlet, must not exceed
12 feet (3.66 meters).  The minimum diameter of this ductwork
must be at least 6-inches (15.24 cm) for MDG31, and 8-inches
(20.32 cm) for MDG51 and MDG77.  Including tumbler/dryer
elbow connections or elbows used for outside protection from
the weather, no more than 3 elbows should be used in the
exhaust duct run.  If more than 3 elbows are used, the
cross-sectional area of the ductwork must be increased.

Содержание MDG31

Страница 1: ...upplier AVERTISSEMENT Assurez vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d incendie ou d explosion ou pour éviter tout dommage matériel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne ...

Страница 2: ..._______________________________________________ MODELNO _________________ DISTRIBUTOR S NAME ____________________________________________________________________________________ Serial Number s ________________________________________________________________________________________ _______________________________________________________________________________________________________ _____________...

Страница 3: ...llowed to play on or near the dryer s Children should be supervised if near dryer s in operation Under no circumstances should the dryer door switch es lint door drawer switch es or heat safety circuit s ever be disabled The dryer must never be operated with any of the back guards outer tops or service panels removed Personal injury or fire could result The dryer must never be operated without the...

Страница 4: ... similarly textured rubber materials Drying in a heated tumbler may damage plastics or rubber and also may be a fire hazard A program should be established for the inspection and cleaning of lint in the burner area exhaust ductwork and area around the back of the dryer The frequency of inspection and cleaning can best be determined from experience at each location Warning The collection of lint in...

Страница 5: ..._________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ___________________________________________ ______________________________________...

Страница 6: ...SSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION 1 2 M N P T VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW EXHAUST CONNECTION DIAMETER COMPRESSED AIR CONNECTION COMPRESSED AIR VOLUME OVEN SIZE kW Btu hr kcal hr VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW STEAM CONSUMPTION OPERATING STEAM PRESSURE EXHAUST...

Страница 7: ...113430 9 Telephone 641 787 7000 7 MDG31 Specifications ________________________________________________________________ ...

Страница 8: ...m COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION 1 2 M N P T 1 2 F B S P T CE and Australia Only VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW EXHAUST CONNECTION DIAMETER COMPRESSED AIR CONNECTION COMPRESSED AIR VOLUME OVEN SIZE kW Btu hr kcal hr VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW STEAM ...

Страница 9: ...113430 9 Telephone 641 787 7000 9 MDG51 Specifications _________________________________________________________________ ...

Страница 10: ... cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION 1 2 M N P T 1 2 F B S P T CE and Australia Only VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW EXHAUST CONNECTION DIAMETER COMPRESSED AIR CONNECTION COMPRESSED AIR VOLUME OVEN SIZE kW Btu hr kcal hr VOLTAGE AVAILABLE N A APPROXIMATE NET WEIGHT APPROXIMATE SHIPPING WEIGHT AIRFLOW STEA...

Страница 11: ...113430 9 Telephone 641 787 7000 11 MDG77 Specifications ______________________________________________________________ ...

Страница 12: ... be achieved as noted in this manual refer to Exhaust Requirements section Important The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber Caution This dryer produces combustible lint and must be exhausted to the outdoors Every 6 months inspect the exhaust ducting and ...

Страница 13: ...ers are located at high altitudes or predominantly low pressure areas Note Component failure due to dry cleaning solvent fumes will void the warranty A 10 inches 25 4 cm B 11 inches 27 94 cm EXAMPLE For a bank of 4 MDG31 dryers 2 unrestricted openings measuring 10 inches by 11 inches 25 4 cm by 27 94 cm are acceptable Important Make up air must be free of dry cleaning solvent fumes Make up air tha...

Страница 14: ...appliance category in accordance with national installation regulations of the country of destination Outside Ductwork Protection To protect the outside end of the horizontal ductwork from the weather a 90 elbow bent downward should be installed where the exhaust exits the building If the ductwork travels vertically up through the roof it should be protected from the weather by using a 180 turn to...

Страница 15: ...oper installation will void the warranty Each dryer should be connected to an independently protected branch circuit The dryer must be connected with copper wire only Do not use aluminum wire which could cause a fire hazard The copper conductor wire cable must be of proper ampacity and insulation in accordance with electric codes for making all service connections Note The use of aluminum wire wil...

Страница 16: ...r or the dryer can be hard wired directly to the service breaker panel In both cases a strain relief must be installed where the wiring enters the dryer For CE Models Only The means for disconnection from the supply must be incorporated into wiring having a minimum contact separation of 3 0 mm in all poles Single Phase 1ø Wiring Connections Hookup The electrical input connections are made into the...

Страница 17: ...e or disconnect the dryer from supply as noted can cause irreparable damage to the gas valve voiding the warranty Note The dryer must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure test of the gas supply system at test pressures equal to or less than 1 2 psig 3 5 kPa for non CE dryers or 50 mb for CE dryers Warning Fire or explosion...

Страница 18: ... M3 H 22 3 988 2 6 9 Natural I2L 830 20 35 110 000 32 24 3 753 M3 H 22 3 988 2 9 5 Natural I2ELL 830 15 30 110 000 32 24 3 753 M3 H 22 3 988 2 9 5 Natural I2E 1 000 20 110 000 32 24 3 115 M3 H 31 3 048 2 830 25 110 000 32 24 3 753 M3 H 31 3 048 2 Butane I3 3 175 28 30 110 000 32 24 2 324 kg H 48 1 930 2 Propane I3 2 500 37 110 000 32 24 2 324 kg H 48 1 930 2 Butane I3B P 3 175 28 30 50 110 000 32 ...

Страница 19: ...aks with a flame Converting from One Family of Gas to Another ______________________ Warning CE Dryers This appliance must only be operated with the gas type indicated on the dryer s data plate If the appliance is converted gas type changed a data plate amendment must be obtained from Maytag dryer s serial number is required to purchase a conversion kit Important Any burner changes or conversions ...

Страница 20: ...wing 3 options the conversion to be performed Converting from unregulated L P to regulated natural gas use a flat screwdriver to remove the cap with blocking pin and install the regulator vent cap from the kit P N 140415 Locate the gas train and disconnect the union 3 electrical plugs and the gas train mounting screws from the burner Carefully slide the gas train out of the gas train enclosure The...

Страница 21: ...tions or codes It is the installer s or owner s responsibility to see that the required water pressure pipe size or connections are provided The manufacturer assumes no responsibility if the fire suppression system is not connected installed or maintained properly Converting from unregulated L P to unregulated natural gas no change to the regulator is required Converting from regulated L P to regu...

Страница 22: ...ply feed line Electrical Requirements No independent external power source or supply connection is necessary The 24 volt power to operate the fire suppression system is accomplished internally in the dryer from the dryer controls Warning Electrical power must be provided to the dryer at all times If the main electrical power supply to the dryer is disconnected the fire suppression system is inoper...

Страница 23: ...ctions is pressed Non Coin Models Microprocessor Controller Computer The L E D display reads READY no cycle in progress Press the letter on the keypad corresponding to the cycle desired e g key D The dryer will then start i e blower tumbler and heat The L E D display will read MANUAL DRYING CYCLE D ___MIN REMAIN Note The dryer can be stopped at any time by pressing the STOP CLEAR key at this time ...

Страница 24: ...uidelines in this section are met the dryer will provide many years of efficient trouble free and most importantly safe operation Warning Lint from most fabrics is highly combustible The accumulation of lint can create a potential fire hazard Keep dryer area clear and free from combustible materials gasoline and other flammable vapors and liquids Note Suggested time intervals shown are for average...

Страница 25: ... for a particular model 7 Gas Manifold Pressure For Gas Dryers This describes the manifold pressure taken at the gas valve tap CE Label Note Do not obstruct the flow of combustion and ventilation air Check back draft dampers in the exhaust ductwork Inspect and remove any lint accumulation which can cause the damper to bind or stick A back draft damper that is sticking partially closed can result i...

Страница 26: ...Part No 113430 9 02 15 08 0 ...

Отзывы: