17
4. 2 1/2” or 3” diameter pipe can be used in place of 2”
diameter pipe.
5.
Increased Clearance Configurations using (2) 45 deg.
Long Sweep elbows should be considered equivalent
to one 90 deg. elbow.
6. One 90° elbow should be secured to the combustion
air intake connection.
note: f
or
InstallatIons
at
or
aBoVe
7,000
feet
altItuDe
,
use
3”
VentIng
.
V
ent
/f
lue
P
IPe
t
erMInatIons
12" MIN.
VENT/FLUE TEE (
or
45° ELBOW
TURNED DOWN or
90° ELBOW TURNED
DOWN
OPTIONAL)
H
orIZontal
t
erMInatIon
(s
Ingle
P
IPe
)
a
BoVe
H
IgHest
a
ntIcIPateD
s
now
l
eVel
f
Igure
12
note: I
f
eItHer
a
90
Degree
or
45
Degree
elBow
Is
useD
for
terMInatIon
,
It
Must
Be
PoInteD
DownwarD
.
The vent/flue pipe may terminate vertically, as through a
roof, or horizontally, as through an outside wall.
Vertical vent/flue pipe terminations should be as shown
in the following figure. Refer to
Vent/Flue Pipe and
Combustion Air Pipe - Termination Locations
for details
concerning location restrictions. The penetration of the
vent through the roof must be sealed tight with proper
flashing such as is used with a plastic plumbing vent.
Horizontal vent/flue pipe terminations should be as
shown in the following figure. Refer to
Vent/Flue Pipe and
Combustion Air Pipe.
To secure the pipe passing through
the wall and prohibit damage to piping connections, a
coupling should be installed on either side of the wall and
solvent cemented to a length of pipe connecting the two
couplings. The length of pipe should be the wall thickness
plus the depth of the socket fittings to be installed on the
inside and outside of the wall. The wall penetration should
be sealed with silicone caulking material.
note: t
erMInate
BotH
PIPes
In
tHe
saMe
Pressure
Zone
(
saMe
sIDe
of
roof
,
no
Major
oBstacles
Between
PIPes
,
etc
.).
a
lternate
c
oMBustIon
a
Ir
P
roVIsIon
(Upflow / Horizontal models only)
When using the alternate venting location, either in
a horizontal left side down installation or a vertical
installation using down – venting, an alternate combustion
air opening can be used. A locating dimple is located on
the right side of the furnace cabinet. The locating dimple
is 1 7/8” measured from the front edge of the cabinet in
line with the knock out. To use the alternate combustion
air location:
1.
Remove screws and combustion air flange from
cabinet.
2. Insert cabinet plug in unused combustion air hole.
3.
Drill a pilot hole at the cabinet dimple (size dictated by
knockout tool used).
4.
Use a knockout tool to create a 3” diameter hole.
5.
Install combustion air flange and secure with screws
removed in step one.
6.
Install screws removed in step 1 securing flange to
cabinet.
n
on
-D
Irect
V
ent
(s
Ingle
P
IPe
) P
IPIng
Non-direct
vent
installations require only a vent/flue pipe.
The vent pipe can be run horizontally with an exit through
the side of the building or run vertically with an exit through
the roof of the building. The vent can also be run through
an existing
unused
chimney; however, it must extend a
minimum of 12 inches above the top of the chimney. The
space between the vent pipe and the chimney must be
closed with a weather-tight, corrosion-resistant flashing.
Although
non-direct
vent
installations do not require a
combustion air intake
pipe
, a minimum of one 90° elbow
should be attached to the furnace’s combustion air
intake
if
: an upright installation uses the standard intake
location, or a horizontal installation uses the alternate air
intake location. This elbow will guard against inadvertent
blockage of the air intake.
V
ent
/f
lue
P
IPe
l
engtHs
anD
D
IaMeters
note: f
or
InstallatIons
at
or
aBoVe
7,000
feet
altItuDe
,
use
3”
VentIng
. I
f
eItHer
a
90
Degree
or
45
Degree
elBow
Is
useD
for
terMInatIon
,
It
Must
Be
PoInteD
DownwarD
.
Refer to the table on the preceding page for applicable
length, elbows, and pipe diameter for construction of the
vent/flue pipe system of a non-direct vent installation. In
addition to the vent/flue pipe, a single 90° elbow should be
secured to the combustion air intake to prevent inadvertent
blockage. The tee used in the vent/flue termination must
be included when determining the number of elbows in the
piping system.
1. Maximum allowable limits listed on individual lengths
for inlet and flue and NOT a combination.
2.
Minimum requirement for each vent pipe is five (5)
feet in length and one elbow/tee.
3.
Tee used in the vent/flue termination must be included
when determining the number of elbows in the piping
system.
Содержание Amana CVC96 BA Series
Страница 55: ...55 THIS PAGE IS INTENTIONALLY LEFT BLANK...