Operating instructions SG-RSV 206/X
170912 v3.1cd
Still unable to remedy the fault?
Ä
Contact Mayser-Support: Tel. +49 731 2061-0.
Error state
Possible cause
Remedy
Output is set to LOW
No or incorrect supply voltage
1. Check supply voltage, compare with
type plate
2. Check terminal assignment
Incorrect monitoring resistor in sensor
1 or 2
1. Check non-activated sensor;
resistance = 1k2 ±5%
2. Measured resistance deviates signifi-
cantly
Ä
Replace sensor
Cable break
1. Check activated sensor; resistance
< 400 ohms
2. Measured resistance deviates signifi-
cantly
Ä
Replace sensor
Sensor short circuit
1. Check non-activated sensor;
resistance = 1k2 ±5%
2. Measured resistance deviates signifi-
cantly
Ä
Replace sensor
Control unit faulty
Ä
Replace control unit
Control unit RSV 206/2
Pre-requisites: the control unit is connected to the supply voltage and sensors; the
sensors are not activated.