Operating instructions SG-RSV 206/X
Page11/14
Maintenance and cleaning
Maintenance
Cleaning
The control unit is maintenance-free.
Ä
Repeat the functional test monthly.
Ä
Clean the outside of the enclosure with a dry cloth.
Danger of injury from electric shock!
Ä
Disconnect the control unit – as well as all devices and live parts in the imme-
diate environment – from the power supply and secure them to prevent them
from being switched on again (see relevant operating instructions).
Ä
Check whether all devices and parts are de-energised.
DANGER
Troubleshooting and remedies
Error state
Possible cause
Remedy
Output remains set to
LOW when the state
changes
No or incorrect supply voltage
1. Check supply voltage, compare with
type plate
2. Check terminal assignment
Output is set to HIGH
Incorrect monitoring resistor in sensor
1 or 2, or sensor short circuit
1. Check non-activated sensor;
resistance = 1k2 ±5%
2. Measured resistance deviates signifi-
cantly
Ä
Replace sensor
Cable break
1. Check activated sensor; resistance
< 400 ohms
2. Measured resistance deviates signifi-
cantly
Ä
Replace sensor
If supply voltage is correctly connected and
sensor is OK: control unit is faulty
Ä
Replace control unit
Pre-requisites: the control unit is connected to the supply voltage and sensors; the
sensors are not activated.
Control unit RSV 206/1
Still unable to remedy the fault?
Ä
Contact Mayser-Support: Tel. +49 731 2061-0.