Maintenance and cleaning

Maintenance

Cleaning

The control unit is maintenance-free.

 

Ä

Repeat the functional test monthly.

 

Ä

Clean the outside of the enclosure with a dry cloth.

Danger of injury from electric shock!

 

Ä

Disconnect the control unit – as well as all devices and live parts in the imme-
diate environment – from the power supply and secure them to prevent them 
from being switched on again (see relevant operating instructions).

 

Ä

Check whether all devices and parts are de-energised.

DANGER

Troubleshooting and remedies

Error state

Possible cause

Remedy

Output remains set to 
LOW when the state 
changes

No or incorrect supply voltage

1.  Check supply voltage, compare with 

type plate

2.  Check terminal assignment

Output is set to HIGH

Incorrect monitoring resistor in sensor  
1 or 2, or sensor short circuit

1.  Check non-activated sensor;  

resistance = 1k2 ±5%

2.  Measured resistance deviates signifi-

cantly

 

Ä

Replace sensor

Cable break

1.  Check activated sensor; resistance  

< 400 ohms

2.  Measured resistance deviates signifi-

cantly

 

Ä

Replace sensor

If supply voltage is correctly connected and 
sensor is OK: control unit is faulty

 

Ä

Replace control unit

Pre-requisites: the control unit is connected to the supply voltage and sensors; the 
sensors are not activated.

Control unit RSV 206/1

Still unable to remedy the fault?

 

Ä

Contact Mayser-Support: Tel. +49 731 2061-0.

Содержание SG-RSV 206 Series

Страница 1: ...GmbH Co KG rlinger Strasse 1 3 89073 Ulm GERMANY Tel 49 731 2061 0 Fax 49 731 2061 222 E mail info ulm mayser com Website www mayser com Control unit SG RSV 206 X 1002565 SG RSV 206 1 12 24 V Output...

Страница 2: ...ity model or design Mayser Ulm 2012 Table of contents About these operating instructions 3 Intended use 4 Safety instructions 4 Parts supplied 5 Transport and storage 5 Packaging and transport 5 Stora...

Страница 3: ...eceived from the manufacturer to the operating instruc tions These operating instructions are only valid for the products specified on the title page Validity The target group of these operating instr...

Страница 4: ...ction in the safety classification the downstream control must be of the same cat egory or higher The control unit is designed for processing the signals of a pressure sensitive protec tion device PSP...

Страница 5: ...for use in these zones In the event of a fault put out of operation In the event of malfunctions and visible damage put the control unit out of oper ation by decommissioning it Do not overload control...

Страница 6: ...current The control unit is operated with a voltage of 12 or 24 V DC If the supply voltage is connected the control unit is ready for operation SG RSV 206 1 Control unit SG RSV 206 1 has a non inverte...

Страница 7: ...n of the protection device may be impaired When installing the product in a switch cabinet ensure sufficient clearance from heat sources at least 2 cm 1 Fix the control unit in any position with 4 mm...

Страница 8: ...ween the protection device and the machine Take particular care when setting up the interface In the case of screw terminals only use non tin plated conductor cores with wire end ferrules Operation wi...

Страница 9: ...set to LOW 5 Repeat step 1 6 Disconnect sensor 1 Output is set to LOW 7 Repeat step 1 8 Disconnect sensor 2 Output is set to LOW 9 Repeat step 1 Control unit RSV 206 2 2 Activate sensor 1 Output is s...

Страница 10: ...unit works without a reset If the sensor is released after activation the output returns to HIGH after a delay tw The control unit works without a reset If the sensor is released after activation the...

Страница 11: ...ause Remedy Output remains set to LOW when the state changes No or incorrect supply voltage 1 Check supply voltage compare with type plate 2 Check terminal assignment Output is set to HIGH Incorrect m...

Страница 12: ...r 1 or 2 1 Check non activated sensor resistance 1k2 5 2 Measured resistance deviates signifi cantly Replace sensor Cable break 1 Check activated sensor resistance 400 ohms 2 Measured resistance devia...

Страница 13: ...Mayser CAUTION Disposal The control units produced by Mayser are professional electronic tools exclusively in tended for commercial use known as B2B devices Unlike the B2C business to con sumer device...

Страница 14: ...unit inputs Sensors 1 and 2 Monitoring resistor Short circuit resistance Line resistance Line length max Switching thresholds Sensor activated Cable break Y1 Y2 and Y3 Y4 1k2 ohms 400 ohms 100 ohms 10...

Отзывы: