Control unit SG-RSV 206/X

1002565 

SG-RSV 206/1 

12 / 24 V=

 

 

Output: pnp non-inverted

1003181 

SG-RSV 206/2 

12 / 24 V=

 

 

Output: pnp inverted

Version 2

Содержание SG-RSV 206 Series

Страница 1: ...GmbH Co KG rlinger Strasse 1 3 89073 Ulm GERMANY Tel 49 731 2061 0 Fax 49 731 2061 222 E mail info ulm mayser com Website www mayser com Control unit SG RSV 206 X 1002565 SG RSV 206 1 12 24 V Output...

Страница 2: ...ity model or design Mayser Ulm 2012 Table of contents About these operating instructions 3 Intended use 4 Safety instructions 4 Parts supplied 5 Transport and storage 5 Packaging and transport 5 Stora...

Страница 3: ...eceived from the manufacturer to the operating instruc tions These operating instructions are only valid for the products specified on the title page Validity The target group of these operating instr...

Страница 4: ...ction in the safety classification the downstream control must be of the same cat egory or higher The control unit is designed for processing the signals of a pressure sensitive protec tion device PSP...

Страница 5: ...for use in these zones In the event of a fault put out of operation In the event of malfunctions and visible damage put the control unit out of oper ation by decommissioning it Do not overload control...

Страница 6: ...current The control unit is operated with a voltage of 12 or 24 V DC If the supply voltage is connected the control unit is ready for operation SG RSV 206 1 Control unit SG RSV 206 1 has a non inverte...

Страница 7: ...n of the protection device may be impaired When installing the product in a switch cabinet ensure sufficient clearance from heat sources at least 2 cm 1 Fix the control unit in any position with 4 mm...

Страница 8: ...ween the protection device and the machine Take particular care when setting up the interface In the case of screw terminals only use non tin plated conductor cores with wire end ferrules Operation wi...

Страница 9: ...set to LOW 5 Repeat step 1 6 Disconnect sensor 1 Output is set to LOW 7 Repeat step 1 8 Disconnect sensor 2 Output is set to LOW 9 Repeat step 1 Control unit RSV 206 2 2 Activate sensor 1 Output is s...

Страница 10: ...unit works without a reset If the sensor is released after activation the output returns to HIGH after a delay tw The control unit works without a reset If the sensor is released after activation the...

Страница 11: ...ause Remedy Output remains set to LOW when the state changes No or incorrect supply voltage 1 Check supply voltage compare with type plate 2 Check terminal assignment Output is set to HIGH Incorrect m...

Страница 12: ...r 1 or 2 1 Check non activated sensor resistance 1k2 5 2 Measured resistance deviates signifi cantly Replace sensor Cable break 1 Check activated sensor resistance 400 ohms 2 Measured resistance devia...

Страница 13: ...Mayser CAUTION Disposal The control units produced by Mayser are professional electronic tools exclusively in tended for commercial use known as B2B devices Unlike the B2C business to con sumer device...

Страница 14: ...unit inputs Sensors 1 and 2 Monitoring resistor Short circuit resistance Line resistance Line length max Switching thresholds Sensor activated Cable break Y1 Y2 and Y3 Y4 1k2 ohms 400 ohms 100 ohms 10...