Jumpers and Jacks:
JUMPER
SET AT
DESCRIPTION
J1
N/A
Ethernet Connection with PoE/POE+ support
J2
N/A
Factory Use Only
J3
N/A
Tamper Switch (normally open contact) See section
14.
J4
N/A
RS-485 Termination, install only if the MR62e is at the
end of the communication bus
J5
PoE
MR62e powered from the Ethernet connection
VIN
MR62e powered from an external 12 Vdc power
source connected to TB4-3 (VIN), TB4-4 (GND)
J6
– J13
N/A
Factory Use Only
DIP Switches:
The four switches on S1 DIP switch configure the operating mode of the eMAX-MR62e Module. DIP
switches are read on power-up except where noted.
1
2
3
4
Definitions
OFF OFF OFF OFF Normal operating mode.
ON
X
OFF OFF
After initialization, enable default User Name (admin) and Password
(password). The switch is read on the fly, no need to re-boot. See IT
Security section for additional information.
OFF
ON
OFF OFF Use factory default communication parameters.
ON
ON
OFF OFF
Use OEM default communication parameters. Contact system
manufacture for details. See Bulk Erase section below.
ON
ON
OFF OFF Bulk Erase prompt mode at power up. See Bulk Erase below.
All other switch settings are unassigned and reserved for future use. (X = don
’t care)
Factory Default Communication Parameters:
Network: static IP address: 192.168.0.251
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.0.1
4. Bulk Erase Configuration Memory:
The bulk erase function can be used for the following purposes:
➢
Erase all configuration, sets MR62e to OEM setting (sanitize board).
➢
Restore to OEM default parameters.
Bulk Erase Steps:
Do not remove power during steps 4-6.
1. Set S1 DIP switches to: 1 & 2 "ON", 3 & 4 "OFF".
2. Apply power to the MR62e.
3. Watch for LEDs 1 & 2 and 3 & 4 to alternately flash at a 0.5 second rate.
4. Within 10 seconds from applying power, change switches 1 or 2 to "OFF". If these switches are
not changed, the MR62e will power up using the OEM default communication parameters.
5. LEDs 1 and 2 alternately flash at a 0.5 second rate while the memory is being erased.
6. Once the memory is eased, LED 1 will be on for about 3 seconds, then the eMAX-MR62e will
reboot.