3- MOUNTING

4- INPUTS

5.1 SOUNDER OUTPUT

The panel has two supervised sounder output rated 0.5А 24V DC. Overloading the output will cause a sounder output fault and fuse 

activation. A 2x1.5 mm2 cable must be used as a sounder circuit. 10кΩ resistor, located on sounder output from factory default is 

used as end-of-line element.

5.2 AUXILIARY POWER SUPPLY OUTPUT

The panel is equipped with an auxiliary 0.5А 24V DC power supply output. The output is used for energising external devices such 

as telephone dialler or gas detector. Connecting an external device with improper voltage requirement or overloading the output 

will cause device malfunction or output fault. The output provides continuous power supply. In case of mains power supply failure, 

the batteries provide power supply to the output.

5.3 RELAY OUTPUTS

The panel has two relay outputs with volt free changeover contacts rated 1A 30V DC, NC and NO. If a relay output would be used 

in an application requiring continuous high current - even below the rated values - an appropriate terminal should be used between 

the device and the relay output.

5- OUTPUTS

Page 4/16

KK-642.042 Rev.No:0 01.11.12 ML-221XX User Manual                                                                                                                   

The chosen site for the mounting of the panel must be clean, dry and not subject to shock or vibration. The panel must not be 

mounted near to sources of excessive heat or cold (see the specifications). Mark the position of the fixing holes according to the 

respective Annex, ensuring that the wall is flat at the chosen location. Screws or bolts of a minimum of 4mm diameter must be used 

to mount the cabinet in all mounting positions. Panel cable entries from back and top of the panel are available for easy mounting. 

Drill and plug the wall then fix the cabinet using all fixing points. Open the panel front cover using the key provided.

4.1 MAINS POWER SUPPLY

The system is designed to operate with 220V AC 50Hz. Earth connections must be made to earth terminal and earth resistor must 

be less than 10Ω. The mains supply of the panel must be via an independent self-resetting fuse rated 6A 220V AC. This fuse must 

be separate from the other fuses and a caution note should be written such as “ATTENTION! FIRE ALARM CONTROL PANEL’S FUSE. 

DO NOT REMOVE” to ensure safe operation of the panel. Recommended cable types for mains power supply are 3x2.5 NYM or 3x2.5 

NYA. Do not connect or disconnect detection circuits, mains supply input and PCB connections while the panel is energised to avoid 

an electric shock.

4.2 BATTERIES

Batteries provide continuity of operation during a failure of the mains power supply. The power supply has an automatic battery 

charger circuit, so there is no need for an external charging unit. The panel uses two units of 12V DC 7Ah dry type batteries.

4.3 ZONES

Zone circuits provide supply to detectors and manual call points, and conduct fire, short circuit and open circuit signals. Please refer 

to the respective Annex for connection scheme. Each zone is capable of hosting up to 20 fire detectors and infinite number of 

manual call points. The characteristics of the cable is dependant on the length of the circuit: for a circuit of 0-500 meter long, use 

1x2x0.8+0.8J-Y(st)Y cable, for a circuit of 500-1500 meter long - 1x2x1.5+1.5J-Y(st)Y. A 6.8kΩ resistor must be connected to 

unused circuits and after the last device on the circuit as an end-of-line element.

5.3.1 FIRE RELAY: 

The fire relay activates on fire condition. The output is returned to its initial position by pressing Reset button provided no fire 

condition is available. The fire relay is normally not energised.

5.3.2 FAULT RELAY: 

The fault relay activates on fault condition. The output returns to its initial position automatically as soon as fault condition ends. 

Fault relay is normally energised; this enables conveying a fault signal to a remote control unit when the panel goes out of power 

supply.

Содержание ML-221XX series

Страница 1: ...COMMISSIONING OPERATING AND MAINTENANCE MANUAL MODEL MAXLOGIC SERIES SUB MODEL CONVENTIONAL SYSTEM FIRE ALARM CONTROL PANEL...

Страница 2: ...tions Santral Models Accessories and Options Annex A Panel Wiring Diagram Annex B Panel Dimensions Annex C1 Panel Serigraphy Annex C2 Panel Serigraphy Annex C3 Panel Serigraphy Annex C4 Panel Serigrap...

Страница 3: ...nt Do not use the panel before reading this manual The subjects that should be noticed during handling and transportation This product should be stored as packed on indoor areas Storing ambient temper...

Страница 4: ...in all mounting positions Panel cable entries from back and top of the panel are available for easy mounting Drill and plug the wall then fix the cabinet using all fixing points Open the panel front c...

Страница 5: ...Illumination indicates any fault condition This would typically be Mains power supply or battery voltage is low Leak from or wire to earth Open or short circuit on the sounder circuit Open or short c...

Страница 6: ...load a short circuit or exceeding 230V AC on mains supply input On activation of the mains fuse the batteries energise the panel 9 1 NORMAL In normal condition only the Power On LED should illuminate...

Страница 7: ...are as follows Set the Button Control key to Enable position The buzzer will sound once Press the Silence Buzzer button then keeping the button pressed press the Reset button till Alarm Buzzer Silence...

Страница 8: ...etwork card Memory card Network Memory card 4 way relay card 4 way sounder card 2 way relay card 2 way sounder card 2 4 8 16 Zone Capacity Product Code Product Name Page 8 16 KK 642 042 Rev No 0 01 11...

Страница 9: ...Y 2213 Memory card provides to save event logs for ML 221XX series panels Up to 1000 event log memory It provides to monitor log events in the PC program Providing panel configuration via PC program 1...

Страница 10: ...Page 10 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Network Card MLY 2212 Mermory Card MLY 2213 Network and Memory Card MLY 2214 Wiring Diagram...

Страница 11: ...Page 11 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex A Panel Wiring Diagram...

Страница 12: ...Page 12 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex B Panel Dimensions 400mm 300mm 100mm...

Страница 13: ...Page 13 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C1 Panel Serigraphy...

Страница 14: ...Page 14 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C2 Panel Serigraphy...

Страница 15: ...Page 15 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C3 Panel Serigraphy...

Страница 16: ...Page 16 16 KK 642 042 Rev No 0 01 11 12 ML 221XX User Manual Annex C4 Panel Serigraphy...

Отзывы: