PV voltage and power
PV charger output voltage and MPPT charging current
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL
4048/60A
4048/80A
5048/60A
5048/80A
Input Voltage Waveform
Sinusoidal
Nominal Input Voltage
230Vac
Low Loss Voltage
90Vac
±
7V(APL
、
GEN);170Vac
±
7V(UPS)
186Vac
±
7V(VDE)
Low Loss Return Voltage
100Vac
±
7V(APL
、
GEN);180Vac
±
7V(UPS)
196Vac
±
7V(VDE)
High Loss Voltage
280Vac
±
7V(UPS
、
APL
、
GEN)253Vac
±
7V(VDE)
High Loss Return Voltage
270Vac
±
7V(UPS
、
APL
、
GEN)250Vac
±
7V(VDE)
Max AC Input Voltage
300Vac
Nominal Input Frequency
50HZ/60HZ (Auto detection)
Low Loss Frequency
40HZ
±
1HZ(UPS
、
APL
、
GEN)
47.5HZ
±
0.05HZ(VDE)
Low Loss Return Frequency
42HZ
±
1HZ(UPS
、
APL
、
GEN)
47.5HZ
±
0.05HZ(VDE)
High Loss Frequency
65HZ
±
1HZ(UPS
、
APL
、
GEN)
51.5HZ
±
0.05HZ(VDE)
High Loss Return
Frequency
63HZ
±
1HZ(APL
、
GEN
、
UPS)
50.05HZ
±
0.05HZ(VDE)
Output Short Circuit
Protection
Line mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)
>95%(Rated R load, battery full charged)
Transfer Time
10ms typical (UPS
、
VDE)
20ms typical (APL)
Output power derating:
When AC input voltage drops
230Vac model: