16
(when BLU is selected in point 5) or program
20(when LBU is selected in point 5). If solar
power is available, but the battery voltage is lower
than the setting in point 20, the AC will charge the
battery until the battery voltage reaches the setting
point in program 20.
Solar energy provides power to the loads as first
priority.
If battery voltage has been higher than the setting
point in program 21 for 5 minutes, and the solar
energy has been available for 5 minutes too, the
inverter will turn to battery mode, solar and
battery will provide power to the loads at the
same time.
When the battery voltage drops to the setting in
point 20, the inverter will turn to bypass mode,
AC will provides power to the load only, and
solar power will charge only the battery.
AC will provide power to the loads as first
priority. Solar and battery energy will provide
power to the loads only when AC power is not
available.
02
AC input voltage
range
Appliances (default)
If selected, acceptable AC input voltage range
will be within 90-280VAC.
UPS
If selected, acceptable AC input voltage range
will be within 170-280VAC.
GEN
When the user uses the device to connect the
generator, select the generator mode.
VDE
If selected, acceptable AC input voltage range
will conform to VDE4105 (184VAC-253VAC)
03
Output voltage
Set the output voltage, (220VAC-240VAC)
04
Output frequency
50HZ (default)
60HZ
05
Solar
supply
priority
(default)
Solar energy provides power to charge battery as
first priority.
When AC is available, if the battery voltage is
lower than the setting in point 21, solar energy
will not supply to the load it will only charge the