INSTALLATION INSTRUCTIONS
1.5m~2m
VP30
Fig.37
Fig.38
Fig.39
Fig.40
Fig.41
C AUTIO N
Refer to the figures on the right for the installation
of pipes.
The drain pipe as well as the connection part of
indoor unit must be heat insulated, or condensate
will occur.
Please connect the pipe with horny PVC bond
and make sure there is no leakage.
Do not impose the pressure on connecting
part of drainpipe.
The gradient downwards of drain pipe should be
over 1/100, and do not bend the drain pipe.
Pull the drain pipe transversely within 20m. Please
install a supporter in case the drainpipe is very
long to prevent it from bending.
Lean Downward over 1/100
Supporting Unit
Fold
Bend
Lean Downward
over 1/100
As long as possible (10cm)
Name
Qty.
Outline/specification
Function
Duct installation
board
8
Connecting duct
Fixation bolt (fixing
installation board)
8
ST3.9
×
10-F-H
Fixing duct
installation board
Instructions for duct installation accessories
Duct design
Fix installation board
Make the du ct as short a s pos sible due to the
low static pr essur e (nea rly 0 p a) of this un it.
Fix the insta llation boar d on d uct ou tlet w ith
the bo lts in a ccessories. If the bolt i s
self-provide d, the length of bo lt sho uld be
appro priate and m ake sure no t to da mage the
inside of unit. See Fig.3 0
Duct i nstallation
Fix the duct on installati on bo ard wi th rivet.
See F ig.41.
NOTE :
1.Do n ot let the in door u nit be ar the weigh t of du ct.
2.For conve nient maintenanc e, install the duct
at th e plac e whe re it is easy to do removing.
3.In ca se do ing in stallation in meeti ng roo m or
such place s, ple ase equip th e inte rior w ith
liner and m uffler.
4.The se acc essor ies ar e optio nal. Please conta ct
the servic e for o ther r equire ment .