8.1.2
Weightless calibration from web pages
Enter these parameters:
Load Cell Excitation voltage (on Hardware web page)
Which Sensor Inputs Used (on Hardware web page)
Load Cell Sensitivity
Load Cell Rating
Maximum Tension
Web Wrap Angle
Angle from Force Direction
Procedure
1.
Unload the load cells.
2.
Click on the link to "Zero Calibrate Tension Zone x".
Wait for the calibration to complete.
3.
Click on the link to "Weightless Calibrate Tension Zone x".
4.
The DCLA NET-IP65-ECAT will return that the calibration is
complete or return an error message.
8.2
Zero tension from web pages
To zero the tension in a tension zone, unload the load cells, and
then click on the link "Zero Tension Zone x". This is the same as
pressing the [
] button on the front panel.