CALIBRATION
www.maxcessintl.com
DLCA NET-IP65-ECAT
MI 850A366 1
Page 36 of 44
Weightless calibration procedure continued
When performing a calibration both the zero and WEIGHTLESS
calibrate steps must be done in sequence before a calibration
is valid.
If only zeroing the tension is required use the 0x1E or 0x1F
command.
1.
Unload the load cell(s) for Tension Zone 1.
2.
Enter the command 0x01 (Zero Calibrate Zone 1) in the
Command Request.
The DLCA NET-IP65-ECAT
immediately responds with 0x8000 0001 (Busy) in the
Command Response
.
If the calibrate zero is successful, the DLCA NET-IP65-
ECAT will respond after ten to twenty seconds with
0x1000 0001. Otherwise, error message 0x20XX 0001
will be returned.
3.
Clear the
Command Request
by entering the command
0x00.
4.
Enter the command 0x03 (Weightless Calibrate Zone 1) in
the
Command Request
. The DLCA NET-IP65-ECAT will
immediately respond with success message 0x1000
0003
or
error message 0x20XX 0003 in the
Command
Response
.
5.
Clear the Command Request register by entering the
command 0x00.
Clearing the command request is necessary to prevent
starting multiple calibrations, such as zero and precision,
before the first entered request is finished.
Weightless Calibration is complete.