Controllo per i-HPV5 

Chillers and Inverter Air/Water heat pumps with axial fan

Parame-

ter

Description

Unit Default

Range

Visibility

Allowed configurations:

Description

Notes

Coo

First cooling setpoint

°C

7.0

25÷Coo2

U

Hea

First heating setpoint

°C

45.0

Hea2÷H01

U

San

Sanitary setpoint

°C

48.0

25÷H01

U

If  sanitary  function 

active

Coo2

Second colling setpoint

°C

18.0

Coo÷25

U

Hea2

Second heating setpoint

°C

35.0

25÷Hea

U

San2

Second sanitary setpoint

°C

48.0

25÷H01

U

H01

Maximum  value  in  heating 

setpoint

°C

60.0

-50÷80

I

H04

Minimum  valeu  in  cooling 

setpoint

°C

5.0

-50÷80

I

H10

Sanitary function enabling

/

0

0÷6

I

See par. 12.

H19

Input configuration

Analogue ST6

/

0

0÷49

I

0 = Input disabled

6 = Domestic hot water probe/DS

H22

0-10V  DC  live  input  config

-

uration

Analogue ST11

/

0

0÷30

I

0 = Input disabled

40 = Plant setpoint decalibration

H46

Input configuration

Digital ID2

/

0

0÷30

I

0 = Input diasbled

3 = Summer / winter mode change

H47

Input configuration

Digital ID3

/

0

0÷30

I

0 = Input disabled

2 = Remote On / Off

H51

Input configuration

Digital ID7

/

0

0÷30

I

0 = Input disables

28 = DHW thermostat call

H53

Input configuration

Digital ID9

/

0

0÷30

I

0 = Input disabled

28 = DHW thermosta call

*

H60

Input configuration

Digital ID6E

/

0

0÷30

I

0 = Input disabled

26 = chiamata doppio set-point

*

H63

Input configuration

Digital ID9E

/

0

0÷30

I

0 = Input disabled

25 = Silenced version

H76

Digital inputs polarity

/

0

0÷255

I

0 = Digital inputs N.A.

1 = Polarità invertita di ID9

H77

Digital inputs polarity

/

0

0÷255

I

0 = Digital inputs N.A.

1 = ID7E1 polarity inverted

2 = ID8E1 polarity inverted

4 = ID9E1 polarity inverted

8 = ID10E1 polarity inverted

H85

Output configuration

In DO7 power

/

6

0÷47

I

0 = Output disabled

6 = DHW valve

*H86

Output  configuration  in 

D01E power

/

48

0÷47

I

0 = Output disabled

48  =  Compressor  operation  indica

-

tion

*H87

Output  configuration  in 

D02E power

24 

0÷47

I

0 = Output disabled

24=Alarm signaling

*H88

Output configuration

In D03E power

21

0÷47

I

0 = Output disabled

21=*Defrost signal in progrss

*H89

Output configuration

In D04E power

31

0÷47

I

0 = Output disabled

31=*Reporting season

*H90

Output configuration

In D05E power

/

25

0÷47

I

0 = Output disabled

25=Double  set  point  /  3-way  valve 

for radiant panels

H126

Serial address

/

1

1÷200

I

In the cascade configuration, assign 

a different address to each control

-

ler.

H129

Enable second setpoint

/

0

0÷4

I

See par. 15.

H130

Heating  with  DHW  storage 

tank

/

0

0÷1

I

0 = Normal operation

1 = In Heat, machine always turned 

towards DHW

A08

Antifreeze  alarm  activation 

setting

°C

3

-127÷127

I

Different  values  can 

jeopardise 

proper 

operation of the unit

b04

Radiant panels valve switch

-

ing time

sec

30

0÷600

I

Different  values  can 

jeopardise 

proper 

operation of the unit

b05

Compressor  cut-off  hyster

-

esis

°C

0.2

0÷255

I

b06

DHW  to  heating  output 

transient

sec

45

0÷255

I

b07

PI regulator integral time

sec

150

0÷255

I

b08

Enable dynamic setting

/

0

0÷1

I

See par. 9

b09

Maximum cooling offset

°C

3.0

-50.0÷80.0

I

See par. 9

b10

Maximm heating offset

°C

-3.0

-50.0÷80.0

I

See par. 9

Содержание i-HPV5H 0140

Страница 1: ...er any form of the texts and of the figures contained in this manual This manual is a translation from the official italian language version For reasons of environmental respect the Company will not p...

Страница 2: ...B First emission Rev Date Compiled Approved Note Code Serie MCO01080100001 Chillers and inverter Air Water heat pumps with axial fans Controllo per i HPV5 Chillers and Inverter Air Water heat pumps w...

Страница 3: ...NU PAR 10 4 9 OPERATING HOURS MENU OHR 10 4 10 LOG MENU HIST 10 4 11 FIRWARE VERSION MENU FIR 10 4 12 USB MENU USB 10 4 12 1 FIRMWARE UPDATE UPdF 10 4 12 2 PARAMETERS UPDATE UPPA 10 5 SYSTEM RESOURCES...

Страница 4: ...YSTEM HEALTH INTEGRATION RESISTENCE 19 21 4 INTEGRATION RESISTANCE SELECTION MODE 19 21 5 CIRCULATOR MANAGEMENT WITH ACTIVE RESISTANCE 19 21 6 BOILER ENABLING 19 21 7 LOGIC OF INTEGRATION HEATERS AND...

Страница 5: ...5 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 24 13 LACK OF VOLTAGE 28 24 14 UTILITIES BLOCK ALARM TABLE 28 25 MODBUS VARIABLES 29...

Страница 6: ...on due to dangerous electrical voltage Indicates important information that the operator has to follow in order to guarantee the correct operation of the unit in complete safety Also indicates some ge...

Страница 7: ...tivated and or modified at the same time Different values from the default values can compromise the correct operation of the unit in case of doubt on the value to set contact the company Only authori...

Страница 8: ...e to a higher menu or to increase the parameter value DOWN key allows to move to a lower menu or to decrease the parameter value 4 1 2 LED Cooling mode LED is on if COOL or COOL SAN mode is selected H...

Страница 9: ...0 C San2 Second sanitary setpoin 48 0 25 60 C Coo2 Second Summer setpoint 18 0 Coo 25 C Hea2 Second Winter setpoint 35 0 25 Hea C If sanitary function is enabled see par 12 4 4 PASSWORD MENU PSS Enter...

Страница 10: ...can read firmware version uEr revision rEu and sub revision SUb 4 12 USB MENU USB This menu appears after entering the installer password only if a USB key containing the relevant update files is con...

Страница 11: ...ion by default par 13 1 DO7 H85 XP 10 1 N XP 10 2 fase 6 HDW valve control Voltage output 230Vac 50Hz 2A AC1 see paragraph 12 Modbus RTU RS485 XC 1 1 GND XC 2 1 R XC 2 2 R Factory enabled with CM acce...

Страница 12: ...nt set point will be set Coo Hea b15 2 With input at 50 the set point will be that set Coo Hea With input at 100 the current set point will be adjusted set Coo Hea b15 2 NOTE In cooling mode consideri...

Страница 13: ...val of time P16 the circulator is turned on for a time equal to P17 seconds The function is disabled with P17 0 default The periodic function is suspended in the case of antifreeze mode intervention 8...

Страница 14: ...during this function the flow switch alarm is disabled the maintenance technician must guarantee that there is water inside the system 9 COMPRESSOR ON OFF LOGIC The restart of compressors is in operat...

Страница 15: ...see Chapter 5 and the relative control must also be enabled with parameter H85 6 default The domestic hot water DHW function is controlled through parameter H10 Parameter VALUE Function H19 6 DHW temp...

Страница 16: ...ctrical bridge must be removed from the terminal block With the contact open the unit will be in stand by mode in this state the message E00 will appear on the display on the machine When the contact...

Страница 17: ...2 0 Function not active 1 Enable Hz minimum L03 0 Function not active 1 Function active only in cooling mode 2 Function active only in heating mode 3 Function active only in sanitary mode 4 Function a...

Страница 18: ...ed mode With the function active the noise output and power of the unit are limited for additional information see the installer user manual 20 PARTIAL RECOVERY WITH DESUPERHEATER IF DS ACCESSORY IS P...

Страница 19: ...o lockout due to the intervention of an alarm It switches off when the machine finishes DHW production also taking into account any offset on the set point set with parameter r31 Parameter VALUE Funct...

Страница 20: ...f boiler use r32 1 3 Boiler equipment 21 7 LOGIC OF INTEGRATION HEATERS AND OR BOILER IN JOINT OPERATION OR IN SUB STITUTION OF THE HEAT PUMP COMPRESSOR The auxiliary parts that can be used for joint...

Страница 21: ...o thermoregulated by the system water remote probe as described above If the remote system water probe is not active the boiler is controlled by the flow probe of the heat pump 21 8 3 OPERATION IN SUB...

Страница 22: ...r12 minutes plant inte gration heater HEAT HEAT SAN HEAT 1 0 1 2 Set the minutes 4 6 1 3 1 Heat pump 2 After r16 minutes DHW integration heater HEAT SAN SANITARY 0 1 1 Set the minutes 0 1 4 2 3 1 Hea...

Страница 23: ...s 6 3 1 Plant DHW integration heater 2 After r12 minutes heat pump HEAT HEAT SAN HEAT SANITARY 1 1 Set the minutes Set the minutes 0 3 TABLE 4 OPERATION IN SUBSTITUTION INTERVENTION ORDER STATUS OPERA...

Страница 24: ...unt are interrupted With remote on off contact open the Plant inte gration heater is deactivated Works as indicated in TABLES 1 2 3 and 4 COOL SAN DHW Cannot be actived Works as indicated in TABLE 5 C...

Страница 25: ...I 0 Digital inputs N A 1 Polarit invertita di ID9 H77 Digital inputs polarity 0 0 255 I 0 Digital inputs N A 1 ID7E1 polarity inverted 2 ID8E1 polarity inverted 4 ID9E1 polarity inverted 8 ID10E1 pola...

Страница 26: ...ter is present Contat company r03 Antifreeze heaters setpoint in cooling mode C 4 3 6 I Only change if gly col water is present Contact company r06 Antifreeze heaters delta C 2 0 0 0 25 5 I Only chang...

Страница 27: ...a period of 10 seconds from the start of the machine after the bypass time the status of the digital input is considered if it is active the presence of flow is considered If a lack of flow is diagno...

Страница 28: ...ber of alarm interventions in one hour is 3 the alarm becomes manual reset 24 12 E041 4 WAY VALVE This alarm identifies a malfunction of the 4 way valve for reversing and is manual reset The alarm is...

Страница 29: ...g to your requirements you must modify the following parameters Parameter VALUE Function H124 0 Baud rate 4800 bit s 1 Baud rate 9600 bit s 2 Baud rate 19200 bit s 3 Baud rate 38400 bit s H125 0 Parit...

Страница 30: ...nlet 401 C 10 R Water outlet 405 C 10 R ACS If active 428 C 10 R External 433 C 10 R Compressor 1 discharge 440 C 10 R Remote system If active 7000 10 R Analogue output Condensaton fan 7001 10 R Circu...

Страница 31: ...module Gi Probe 11 If active 954 BOOL 1 R ALARM E801 Inverter link 1 2 ALARM E802 Inverter link 2 4 ALARM E851 Hardware fault inverter 1 5 ALARM E852 Hardware fault inverter 2 7 ALARM E861 Overcurrent...

Страница 32: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 32...

Страница 33: ...33 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...

Страница 34: ...Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan 34...

Страница 35: ...35 Controllo per i HPV5 Chillers and Inverter Air Water heat pumps with axial fan...

Страница 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: