Controllo per i-32V5 MIDI
Air/water inverter chillers and heat pumps with axial fans
26
Parame-
ter
Description
Unit Default
Range
Visibility
Allowed configurations:
Description
Notes
b08
Enable dinamic setting
/
0
0÷1
I
See par. 9
b09
Maximum cooling offset
°C
3.0
-50.0÷80.0
I
See par. 9
b10
Maximum heating offset
°C
-3.0
-50.0÷80.0
I
See par. 9
b11
Cooling outdoor tempera
-
ture setting
°C
25
-127÷127
I
See par. 9
b12
Heating outdoor tempera
-
ture setting
°C
15
-127÷127
I
See par. 9
b13
Cooling temperature delta
°C
-10.0
-50.0÷80.0
I
See par. 9
b14
Heating temperature delta
°C
10.0
-50.0÷80.0
I
See par. 9
b15
0-10V analogue input set
-
ting decalibration band
°C
5.0
0.0÷10.0
I
See par. 7
b20
Input enabling 0-10V / rati
-
ometric
/
0
0÷1
I
0 = Input 0-10V
1 = Ratiometric inut
b22
Plant probe temperature
control cut-off hysteresis
°C
5.0
0.0÷25.5
I
See par. 13.4
b25
Compressor cut-on hyster
-
isis
°C
2.0
0.0÷25.5
C
P01
Pump ON compressor OFF
delay
sec
30
0÷255
I
P02
Pump OFF compressor OFF
delay
min
2.0
0÷25.5
I
P03
Pump operating mode
/
0
0÷1
I
See par. 8
The pump is always
on if the antifreeze
resistances are ac-
tive.
P04
Pump setting in antifreeze
°C
5
-15÷15
I
See par. 8
P05
Pump hysteresis in anti
-
freeze
°C
2.0
0.0÷15.0
I
See par. 8
P09
Modulating pump inlet/out
-
let water delta T setting
°C
2.0
0÷15
I
See par. 8
P16
Interval between 2 periodi-
cal activations of the pump
min
0
0÷600
I
See par. 8
P17
Operating time of the pump
in periodical mode
sec
0
0÷255
I
See par. 8
r02
Antifreeze heaters setpoint
in heating mode
°C
4
3÷6
I
Only change if gly
-
col water is present.
Contact company.
r03
Antifreeze heaters setpoint
in cooling mode
°C
4
3÷6
I
Only change if gly
-
col water is present.
Contact company.
r06
Antifreeze heaters delta
°C
2.0
0.0÷25.5
I
Only change if gly
-
col water is present.
Contact company.
r08
Operation in substitution
upper limit
°C
-20
-20÷50
I
Respect r22 ≥ r28 ≥ r08
r10
System integration enabling
/
0
0÷1
I
0 = Function disabled
1 = Function enabled
See par. 18
r11
System integration heater
delta
°C
0.5
0,0÷25.5
I
See par. 18.1
r12
System/heat pump integra
-
tion heater activation
min
10
0÷255
I
See par. 18.1
r14
Exclusive resistor operation
/
0
0÷1
I
0 = Resistors that can be activated
simultaneously
1 = Resistors that can be activated
exclusively
r15
Enabling sanitary integra
-
tion
/
0
0÷2
I
0 = Fuction disabled
1 = Function enabled
See par. 18.2
r16
Heater activation delay
DHW/heat pump integra
-
tion
min
15
0÷255
I
r19
Duration of activation of
basin resistances from last
defrost
min
10
0÷255
I
0= attivazione resistenza indipen
-
dente da sbrinamento.
r20
Priority use of resistors
/
1
0÷1
I
0 = Priorità lato impianto
1 = Priorità lato sanitario
Il settaggio di questo
parametro si rende
necessario solo se
r14=1
r21
Enable system side mitiga
-
tion with defrosting resis
-
tors
/
0
0÷1
I
0=Funzione disabilitata
1=Funzione abilitata