Controllo per i-32V5 MIDI

 Air/water inverter chillers and heat pumps with axial fans

18

Parameter

VALUE

Function

L02

0

Function not active

1

Enable Hz minimum

L03

0

Function not active

1

Function active only in cooling mode

2

Function active only in heating mode

3

Function active only in sanitary mode

4

Function active in cooling and sanitary mode

5

Function active in heating and sanitary mode

6

Function in cooling and heating mode

7

Function always active

With the function active, the output and power of the unit are limited, for additional information see the installer user manual.

17.  MINIMUM HZ FUNCTIONS

When the function is activated, the power of the unit is increased, for information contact the company.

18.  AUXILIARY RESISTANCES

In some system solutions it may be necessary to use an integration heater for the system and/or for the sanitary area. This is an additional re-

source for heating in case the compressor cannot meet the set in a reasonable time. The resistor controller only operates in heating mode and 

if 

r10 = 1

.

To define how the integration resistors are to operate, parameter 

r24 

must be se:

• 

r24 = 0

 for integration resisitors not used;

• 

r24 = 1

 for use of system integration resisitor;

• 

r24 = 2

 for use of sanitary integration resisitance;

• 

r24 = 3

 for use of both the system integration resistor and the sanitary integration resistor.

18.1 

SYSTEM RESISTANCE

The system resistance must be connected to the digital output DO3 and can be configured by setting parameter 

H81 = 22

.

If the regulation temperature remains lower than the hot water set-point 

Hea – r11

 (°C) for a time equal to 

r12

 the integration resistor is activat-

ed according to the operation of the machine in the combined or replacement bands.

The resistor is also activated if the control temperature remains below the water set-point 

Hea – r11

 (°C) and the machine is in lockout due to 

the intervention of an alarm. It switches off when the machine exits the alarm block.

Setting 

r21 = 1

, during the defrost cycle, if required (temperature lower than 

Hea - r11

), the system resistor is activated without waiting for the 

time defined by 

r12

.

The resistor switches off when the set-point is reached (also taking into account any offset set with parameters 

r29

 or 

r30

).

Parameter

VALUE

Function

H81

22

System integration resistance

r10

1

Enabling of system resistors

r11

5 (default)

Delta resistances in system integration (in tenths of °C)

r12

10 (default)

System integration activation delay (in minutes)

r21

1

Enabling resistors during defrosting

r24

1/3

Type of use resistors

18.2 

SANITARY RESISTANCE

This function can be activated as an alternative to the system integration resistance. The DHW resistance must be connected to digital output 

DO3 and can be configured by setting parameter 

H81 = 26

, in addition the DHW function must be active.

The resistance is activated if the production of domestic hot water lasts longer than 

r16

 (minutes) or if the machine goes into lockout due to 

the intervention of an alarm. It switches off when the machine finishes DHW production (also taking into account any offset on the set-point set 

with parameter 

r31

).

Parameter

VALUE

Function

H81

26

DHW integration resistor

r15

1

Enabling of DHW resistors

r16

10 (default)

Sanitary integration activation delay (in minutes)

r24

2/3

Type of use of resistance

18.3 

INDIVIDUAL SYSTEM/HEALTH INTEGRATION RESISTENCE

Configuring the DHW resistance it is also possible to use it as a system resistor, by setting the parameter 

r15 = 2

 and 

r24 = 3

.

In this way, in the event of a request for system integration, the resistance declared as DHW integration is activated, thus making it possible to 

have a single integration resistance for the system, DHW and defrosting.

Содержание i-32V5C MIDI 0121

Страница 1: ...the explanations and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts of the figures contained in this manual This manual...

Страница 2: ...V5 MIDIAir water inverter chillers and heat pumps with axial fans 2 00 01 2021 EM AR First emission Rev Date Compiled Approved Note Code Serie MCO01040101001 00 Chillers and Inverter Air Water heat pu...

Страница 3: ...9 OPERATING HOURS MENU oHr 10 4 10 LOG MENU HiSt 10 4 11 FIRWARE VERSION MENU Fir 10 4 12 USB MENU USB 10 4 12 1 FIRMWARE UPDATE UPdF 10 4 12 2 PARAMETERS UPDATE UPPA 10 5 SYSTEM RESOURCES 11 6 EDITIN...

Страница 4: ...ON OR IN SUB STITUTION OF THE HEAT PUMP COMPRESSOR 19 18 8 OPERATION HEAT PUMP MODE 20 18 9 JOINT OPERATION I BRACKET 20 18 10 JOINT OPERATION II BRACKET 20 18 11 OPERATION IN SUBSTITUTION 20 18 12 OP...

Страница 5: ...5 Controllo per i 32V5 MIDIAir water inverter chillers and heat pumps with axial fans 23 14 LACK OF VOLTAGE 28 23 15 UTILITIES BLOCK ALARM TABLE 28 24 MODBUS VARIABLES 29...

Страница 6: ...cution due to dangerous electrical voltage Indicates important information that the operator has to follow in order to guarantee the correct operation of the unit in complete safety Also indicates som...

Страница 7: ...activated and or modified at the same time Different values from the default values can compromise the correct operation of the unit in case of doubt on the value to set contact the company Only auth...

Страница 8: ...u or to increase the parameter value DOWN key allows to move to a lower menu or to decrease the parameter value 4 1 2 LED Cooling mode LED is on if COOL or COOL SAN mode is selected Heating mode LED i...

Страница 9: ...itary setpoint 48 0 25 60 C Coo2 Second Summer setpoint 18 0 Coo 25 C Hea2 Second Winter setpoint 35 0 25 Hea C If sanitary function is enabled see par 12 4 4 PASSWORD MENU PSS Enter the password for...

Страница 10: ...you can read firmware version uEr revision rEu and sub revision SUb 4 12 USB MENU USB This menu appears after entering the installer password only if a USB key containing the relevant update files is...

Страница 11: ...3 2 2 Remote on off Voltage free digital input Active function by default par 13 1 DI9 H53 XC 7 1 XC 7 2 0 Not set Voltage free digital input DO3 H81 XP 1 1 N XP 1 2 phase 22 System integration heate...

Страница 12: ...put type 0 10 V default b20 1 for ratiometric input Correction calculation with input 0 10 V b20 0 With input at 0 Volt the current set point will be set Coo Hea b15 2 With 5 Volt input the set point...

Страница 13: ...TING ON CALL BY TEMPERATURE CONTROLLER WITH PERIODIC ACTIVATION With P03 1 you can also configure the circulator to run periodically according to the following parameters P16 Periodic activation time...

Страница 14: ...s with maintenance privilege PRG PSS PRG enter installer password PRG Press UP and DOWN simultaneously for 3 seconds It is possible to exit the system venting cycle manually by pressing the MODE ESC b...

Страница 15: ...y time the compressor is switched on and off 10 1 SILENCED VENTILATION Configuring a digital input DI9 with parameter H53 25 it is possible to manage the function of silent ventilation management Para...

Страница 16: ...er the display returns to show the water outlet temperature In heating mode before entering DHW mode the last value read by the flow probe of the heat pump is memorised Once the DHW temperature contro...

Страница 17: ...ing the compressor start up phase the switch off is managed by the probe on the heat pump delivery In heating mode the call is active if the following conditions are verified Flow probe temperature He...

Страница 18: ...tivated if the control temperature remains below the water set point Hea r11 C and the machine is in lockout due to the intervention of an alarm It switches off when the machine exits the alarm block...

Страница 19: ...r r23 r23 0 default for boiler not used priority of resistor intervention r23 1 for boiler use on system only priority of resistor intervention r23 2 for boiler use only in DHW mode priority intervent...

Страница 20: ...ntrolled by the flow probe of the heat pump 18 10 JOINT OPERATION II BRACKET If the outside temperature is between r28 and r08 the auxiliary heaters are enabled in combination with the heat pump in he...

Страница 21: ...ter r16 minutes DHW integration resistence HEAT SAN SANITARY 0 1 1 Set the minutes 5 6 2 3 1 System DHW integration resistence HEAT HEAT SAN HEAT SANITARY 1 1 0 3 1 Boiler HEAT HEAT SAN HEAT SANITARY...

Страница 22: ...m integration resistence 2 After r12 minutes heat pump HEAT HEAT SAN HEAT 1 0 1 2 Set the minutes 0 2 5 1 3 1 Boiler 2 After r16 minutes heat pump HEAT SAN SANITARY 0 1 0 1 2 Set the minutes 2 3 5 6 0...

Страница 23: ...egration resistance COOL SAN SANITARY 0 1 1 Set the minutes 0 1 2 3 4 5 6 2 3 Table 6 shows the behaviour of the plant and DHW integration heaters in all the operating modes of the unit TABLE 6 INTEGR...

Страница 24: ...all the following conditions are met Compressor in operation Defrosting is not in progress and is not counting to enter defrost mode There are no safety controls or restrictions active The recovery ca...

Страница 25: ...tal inputs N A 1 ID1 polarity inverted 2 ID2 polarity inverted 4 ID3 polarity inverted 8 ID4 polarity inverted 16 ID5 polarity inverted 32 ID6 polarity inverted 64 ID7 polarity inverted 128 ID8 polari...

Страница 26: ...l between 2 periodi cal activations of the pump min 0 0 600 I See par 8 P17 Operating time of the pump in periodical mode sec 0 0 255 I See par 8 r02 Antifreeze heaters setpoint in heating mode C 4 3...

Страница 27: ...inside the unit and must not be tampered with or bypassed in any way The flow switch is bypassed by the control for a period of 10 seconds from the start of the machine after the bypass time the stat...

Страница 28: ...sing and is manual reset The alarm is not active for a bypass time of approximately 180 seconds from the start of the compressor In heating or DHW mode after the bypass time has expired the alarm is a...

Страница 29: ...E911 Overload protection Compressor E921 PFC POE overcurrent Compressor E931 Internal communication error Compressor E941 PFC fault Compressor E951 Heatsink and or ambient temperature sensor fault Com...

Страница 30: ...l 1 heat 4 Sanitary 0 off If active 1 running 5 7 Defrost status 0 inactive 1 starting 2 active 3 dripping 4 finished 253 C 10 R Transducer tempera tures evaporazione 254 C 10 R evaporation 305 ora R...

Страница 31: ...2 module Gi Probe 8 If active 3 ALARM E692 module Gi Probe 9 If active 4 ALARM E702 module Gi Probe 10 If active 5 ALARM E712 module Gi Probe 11 If active 954 BOOL 1 R ALARM E801 Inverter link 1 2 ALA...

Страница 32: ...Controllo per i 32V5 MIDIAir water inverter chillers and heat pumps with axial fans 32...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...ADVANTIX SpA Via S Giuseppe Lavoratore 24 37040 Arcole VR Italy Tel 39 045 76 36 585 E mail info advantixspa it www maxa it...

Отзывы: