25
Controllo per i-32V5 MIDI
Air/water inverter chillers and heat pumps with axial fans
Parame-
ter
Description
Unit Default
Range
Visibility
Allowed configurations:
Description
Notes
Coo
First cooling setpoint
°C
7.0
25÷Coo2
U
Hea
First heating setpoint
°C
45.0
Hea2÷H01
U
San
Sanitary setpoint
°C
48.0
25÷H01
U
If sanitary function
active
Coo2
Second cooling setpoint
°C
18.0
Coo÷25
U
Hea2
Second heating setpoint
°C
35.0
25÷Hea
U
H01
Maximum value in heating
setpoint
°C
60.0
-50÷80
I
H04
Minimum value in cooling
setpoint
°C
5.0
-50÷80
I
H10
Sanitary function enabling
/
0
0÷6
I
See par. 12.
H17
Analogue input configura
-
tion ST6
/
0
0÷49
I
0 = Input disabled
6 = Domestic hot water probe/DS
H18
Analogue input configura
-
tion ST7
/
0
0÷49
I
0 = Input disabled
41 = Remote water temperature
probe
H22
Voltage input configuration
0-10V DC
Analogue ST11
/
0
0÷30
I
0 = Input disabled
40 = System setpoint decalibration
H46
Digital input configuration
ID2
/
0
0÷30
I
0 = Input disabled
3 = Summer/winter change mode
H47
Digital input configuration
ID3
/
0
0÷30
I
0 = Input disabled
2 = Remote On / Off
H51
Digital input configuration
ID7
/
0
0÷30
I
0 = Input disabled
28 = DHW thermostat call
H53
Digital input configuration
ID9
/
0
0÷30
I
0 = Input disabled
25= silenced ventilation
26 = double set-point call
H75
Digital inputs polarity
/
0
0÷255
I
0 = Digital inputs N.A.
1 = ID1 polarity inverted
2 = ID2 polarity inverted
4 = ID3 polarity inverted
8 = ID4 polarity inverted
16 = ID5 polarity inverted
32 = ID6 polarity inverted
64 = ID7 polarity inverted
128 = ID8 polarity inverted
H76
Digital inputs polarity
/
0
0÷255
I
0 = Digital inputs N.A.
1 = ID9 polarity inverted
2 = ID10 polarity inverted
4 = ID1E1 polarity inverted
8 = ID2E1 polarity inverted
16 = ID3E1 polarity inverted
32 = ID4E1 polarity inverted
64 = ID5E1 polarity inverted
128 = ID6E1 polarity inverted
H77
Digital inputs polarity
/
0
0÷255
I
0 = Digital inputs N.A.
1 = ID7E1 polarity inverted
2 = ID8E1 polarity inverted
4 = ID9E1 polarity inverted
8 = ID10E1 polarity inverted
H83
Output configuration
In voltage DO5
/
22
0÷47
I
0 = Output disabled
25 = Double set-point valve
29 = Boiling enabling
H84
Output configuration
In voltage DO6
/
6
0÷47
I
0 = Output disabled
6 = Sanitary valve
H126
Serial address
/
1
1÷200
I
In the cascade configuration, assign
a different address to each control.
H129
Enable second setpoint
/
0
0÷4
I
See par.15.
H130
Heating with DHW storage
tank
/
0
0÷1
I
0 = Normal operation
1 = In Heat, machine always turned
towards DHW
A08
Antifreeze alarm activation
setting
°C
3
-127÷127
I
Different values can
compromise the cor-
rect operation of the
machine
b04
Radiant panels valve switch
-
ing time
sec
30
0÷600
I
Different values may
compromise the cor-
rect operation of the
machine.
b05
Compressor cut-off hyster
-
esis
°C
0.2
0÷255
I
b06
Transient hot sanitary out
-
put
sec
45
0÷255
I
b07
PI regulator integral time
sec
150
0÷255
I