Quick Install Guide

 

1. Operator Placement

 

2. Arm Position

 

3. Release Handle Clamp

 

4. AC Input Power

 

5. Ground Operator

 

6. Set Opening Direction and ID Plug

 

7. Limit Switch Adjustment

 

8. Entrapment Protection Wiring

 

9. Learn Gate Positions

 

10. Adjust ERD Reverse Sensor

 

11. Loops & Loop Detectors

 

12. Matrix 1 Settings

 

13. Wiring Opening Device Options

 

Dual Gate Operators Wiring

1
2
3
4
5
5
6

7-8

8
9
9

10
10
11

Table of Contents

Megatron specifications

Troubleshooting

 

USB Black Box Port

 

Test Edge 1 Entrapment sensor

 

Gate Cycling Troubleshooting

 

Matrix 1 LED Troubleshooting

 

MC-200 LED Troubleshooting

 

BC-7 Module LED Troubleshooting

Commonly Used Safety Sensor Wiring

12
12
13

14-15

16
17

18-21

UL 325 Class of Operation

 - Class I, II, III, IV

Gate Type

 - Vehicular Swing Gate

Input AC Power/Amps

 - Switchable: 115VAC / 6 Amp, 1 phase

 

     

          or 230VAC / 2 Amp, 1 phase

Motor

 - 24VDC Brushless (equivalent to 1 HP AC motor)

Operating Temperature:

 -4°F to 158°F (-20°C to 70°C)

Cycles per Hour AC Input Power

 - Continuous

Battery Back-Up Cycles

 

(BC-7 Battery Module-7 Amp/Hr

 

Batteries fully charged)

- Approximately 450 cycles

Max Gate Weight / Length:

 - 

MAX Megatron 1400 and 1400HP -

 1400lbs @ 15 ft or 1200 lbs @ 20 ft 

 - 

MAX Megatron 2200 and 2200HP -

 2200lbs @ 15 ft  or 1500 lbs @ 20 ft

 - 

MAX Megatron 2200 PLUS and 2200HP PLUS -

 2500lbs @ 15 ft or 1800 lbs @ 20 ft

 - 

MAX Megatron FAST -

 1200lbs @ 12 ft gate per operator 

 - 

MAX Megatron FAST PLUS -

 1600lbs @ 12 ft gate per operator

90° Opening Time:

 - 

MAX Megatron 1400/1400HP/2200/2200HP/2200 PLUS/2200HP PLUS -

 16 selectable speeds

 

  from approximately 11.5 sec to 20 sec depending on the weight and length of the gate.

 - 

MAX Megatron FAST and FAST PLUS -

 16 selectable speeds from approximately

 

  6 sec to 14 sec depending on the weight and length of the dual gates.

Entrapment Protection:

 

-  UL 325 Type A Inherent (ERD sensor)

 - 

Inputs 

for 

NORMALLY CLOSED (N.C.) 

UL 325

 

  Type B1 (photo cell) and Type B2 (sensing edge)

24.5”

24.5”

21.3”

29.9”

17”

25.2”

18.5”

26.6”

18.3”

16.8”

NOTE:

 The number of gate cycles using 

ONLY

 battery back-up power will vary depending on the 

weight of the gate, the gate length, the operating condition of the gate hardware, temperature and 
the amount of charge the batteries have at the beginning of the battery power only operation.

NOTE:

 The MAX Megatron FAST and FAST PLUS are 

ONLY

 available for installation on bi-parting gates 

(dual operators). A single gate operator 

CANNOT

 be used.

High Profile

1400

2200

2200 Plus

FAST

FAST PLUS

1400HP

2200HP

2200HP PLUS

2

UL 325 2016 Standard-Megatron Quick Install Rev 10

Содержание Megatron 1400

Страница 1: ...l Commercial Brushless DC Swing Gate Operators Made in USA 14 0 0 H P 2 2 0 0 H P 2 2 0 0 H P P L U S H ig h P r o f ile 14 0 0 2 2 0 0 2 2 0 0 P LU S FA S T FA S T P LU S CONFORMS TO UL STD 325 UL CLASS I II III IV CERTIFIED TO CAN CSA STD C22 2 NO 247 SAFETY SENSORS REQUIRED Version 10 ...

Страница 2: ...00lbs 15 ft or 1200 lbs 20 ft MAX Megatron 2200 and 2200HP 2200lbs 15 ft or 1500 lbs 20 ft MAX Megatron 2200 PLUS and 2200HP PLUS 2500lbs 15 ft or 1800 lbs 20 ft MAX Megatron FAST 1200lbs 12 ft gate per operator MAX Megatron FAST PLUS 1600lbs 12 ft gate per operator 90 Opening Time MAX Megatron 1400 1400HP 2200 2200HP 2200 PLUS 2200HP PLUS 16 selectable speeds from approximately 11 5 sec to 20 sec...

Страница 3: ... anchors 1 2 MOTOR Power In PWR 24V GND RS 485 RS 485 MATRIX BOARD ALARM BATTERY PACK LIMIT SWITCH MOTOR INPUTS 24V GND UL ALARM 12V ALARM RET RESET GND GATE TAMPER MAG LOCK OPEN RIGHT OPEN LEFT MAGLOCK DELAY PRIMARY GATE SAFETY CENTER EXIT OPEN MAX GATE SPEED STOP CLOSE ANTI TAILGATE CLOSE TIMER POSITION RECORDER ID PLUG AUTOMATIC OPEN CLOSE CONTROLS BATTERY BACK UP MODE MATRIX 1 PHOTOCELL EDGE 1...

Страница 4: ...T PARTIAL OPEN OBD PORT BLACK BOX MOTOR MOTION CENTER REVERSE SENSITIVITY MOTOR OVERLOAD NO LIMIT SWITCH CLAMP SLIPPING MIN MAX 12VDC GND 24VDC GND MAX MIN OFF SAFETY LEAVE OPEN LEAVE CLOSED MADE in USA OPEN 1 TIME 2Sec 1 5Sec COM NC BA TTERY IN USE POWER GA TE ST A TUS MOTOR ON LINE LIMIT SWITCH ON LINE GND PRIMARY GA TE GND SEC GA TE UL ENTRAP PHOT O CE L L GND ST R I K E GND KE Y PAD RDR GND F ...

Страница 5: ...olt POWER IN POWER SOLAR IN BATTERY IN www max us com Made in USA BATTERY PACK TO MOTOR CONTROLLER PhotoCell Edge UL Entrap 1 2 Limit SW ON LINE MATRIX JOG LEFT JOG RIGHT Jog LT Jog RT GND Edge 1 Edge 2 Photo Cell ERD Motor OverLoad POWER MC 200 Motor Controller 16 15 14 13 12 3 4 5 MAX LED ON Edge Sensitivity ERD CLOSED LIMIT OPEN LIMIT 2 4 V GND UL ALARM 12V ALARM RET RESET GND GA TE T AMPER MAG...

Страница 6: ... tec tion aga inst fire rep lace onl y with the sam e typ e and rati ng of fus e AV ER TIS SE ME NT pou r ne pas com pro me ttre la pro tec tion con tre les risq ues d in cen die utili ser un fus ible de mê me s typ e et car act éris tiqu es nom ina les ON OF F Bat tery E F 1 2 Ba tte ry Vo ltag e Rep lace Bat tery TES T Bat tery Bat tery IN Erro r MA X BC 7 Bat tery Mod ule Ph oto Ce ll Ed ge UL ...

Страница 7: ... 15 14 13 12 3 4 5 M A X LE D ON Ed ge Se ns itiv ity ER D MO TO R Po we r In PWR 24V GND RS 485 RS 485 MA TRI X BO AR D ALA RM BATT ERY PAC K LIMI T SWIT CH MOT OR INPU TS ON OFF Batt ery E F 1 2 Bat tery Vol tag e Rep lace Batt ery TES T Batt ery Batt ery IN Erro r MA X BC 7 Batt ery Mod ule BA TT ER Y IN 24V GND UL ALA RM 12V ALA RM RET RES ET GND GAT E TAM PER MA G LOC K OPE N RIG HT OPE N LEF...

Страница 8: ...limit rings need to be set BEFORE the gate can be cycled or DAMAGE could occur Push and HOLD the JOG LEFT or JOG RIGHT buttons accordingly on the MAX MC 200 motor controller to move the gate release the button to stop gate Re adjust limit ring postions as desired R o t a t e C L O S E D r i n g u n t i l L E D l i g h ts CLOSED LIMIT OPEN LIMIT Arm in CLOSED position Adjust Limit Switches OSED LI ...

Страница 9: ...ON for BOTH MC 200 s whe n du al op erators are us ed 5 Press STO P bu tto n ag ain with in 5 min to learn se ns ors an d en d learn mod e be ep ing stop s Inpu ts are no w MONITORED 2 3 2 3 2 3 A sensor MUST be wired to EDGE 1 or operator WILL NOT function Wire NORMALLY CLOSED N C MONITORED sensors ONLY to each operator s MC 200 when dual operators are used Reversing Edge and or Photo Cell can be...

Страница 10: ...nstall along entire edge of gate Conduit The hinge area may need protection against entrapment MAX 10K mini sensing edge works well in this area OPEN CLOSE direction MC 200 Edge 2 or Photo Cell input Gate Closed Normally CLOSED N C OPENING direction Photocell OPEN CLOSE Sensing Edge on Bottom of Gate If the bottom of gate is 6 or higher above the ground then a 10K sensing edge should be installed ...

Страница 11: ...on Matrix 1 to shut off alarm loops loop detectors 11 ON 1 2 3 4 5 6 7 8 5 Op tim um Se ns Inc rease Se ns De cre ase Se ns DE FL EC TO MET ER PO WER ON No rm al Po we r OF F No Po we r LED INDICA TO RS DE TECT ON De tec t OF F No De tec t 2 Hz Fla sh Dela y Tim ing SW 1 SW 2 Freq ue ncy ON ON Lo w ON OF F Me diu m Lo w OF F ON Me diu m High OF F OF F High SW 4 SW 5 Ou tput B ON ON Pu lse on En tr...

Страница 12: ...ce Dry Contact N O N O NOTE See manual for more info Stop Com External Alarm Reset Button Security Device PRESS to RESET Telephone Entry Dry Contact N O Normal Opening Devices 24V GND UL ALARM 12V ALARM RET RESET GND GATE TAMPER MAG LOCK OPEN RIGHT OPEN LEFT MAGLOCK DELAY PRIMARY GATE SAFETY CENTER EXIT OPEN MAX GATE SPEED STOP CLOSE ANTI TAILGATE CLOSE TIMER POSITION RECORDER ID PLUG AUTOMATIC OP...

Страница 13: ...SA OPEN 1 TIME 2Sec 1 5Sec COM NC BATTERY IN USE POWER GATE STATUS MOTOR ON LINE LIMIT SWITCH ON LINE GND PRIMARY GATE GND SEC GATE UL ENTRAP PHOTOCELL GND STRIKE GND KEYPAD RDR GND FIRE DEPT GND MAX OPEN GND RADIO SIG RADIO GND OPEN STOP CLOSE COM GATE DISABLE P h o t o C e l l E d g e U L E n t r a p 1 2 L i m i t S W O N L I N E M A T R I X J O G L E F T J O G R I G H T J o g L T J o g R T G N ...

Страница 14: ...FO PRI_CIO Communica on Established Fri 07 11 2014 10 57 38 ENTRAP PRI_MC Photo Cell Deac vated Fri 07 11 2014 10 57 34 ENTRAP PRI_MC Photo Cell Ac vated Fri 07 11 2014 10 57 21 INFO Radio Input Deac vated Fri 07 11 2014 10 57 21 INFO Radio Input Ac vated Fri 07 11 2014 10 56 46 WARNING PRI_MC Tamper Reported Fri 07 11 2014 10 56 36 INFO SEC_MC Fully Open Posi on Unknown Fri 07 11 2014 10 56 36 IN...

Страница 15: ...properly If EDGE 2 LED or PHOTOCELL LED is ON on MC 200 If so check entrapment sensor wiring or missing jumper If BATTERY IN USE LED is ON and BATTERY BACK UP MODE switch leave Open then battery may be too low and gate is kept OPEN If BATTERY IN USE LED is ON and BATTERY BACK UP MODE switch is set to OPEN 1 TIME then if AC power is lost gate will automatically open 1 time If CLOSE TIMER is OFF the...

Страница 16: ...o to and GND to GND Check wiring between Matrix 1 RS485 gnd and SECONDARY MC 200 RS485 gnd terminals connect to to and GND to GND Check if limit switch box is plugged into PRIMARY MC 200 LIMIT SWITCH input on back and MC 200 is powered ON Check if limit switch box is plugged into SECONDARY MC 200 LIMIT SWITCH input on back and MC 200 is powered ON An entrapment event has occurred check if an entra...

Страница 17: ...is tight on output shaft of operator Loop fault condition Check if EXIT loop wires are connected into to loop input connector properly Check if loop detector is inserted properly in Matrix 1 slot Set unique loop detector frequency for each loop detector used Loop Detector might be defective Replace defective loop detector NOTE RENO loop detector LED s flash as default but function normally ignore ...

Страница 18: ...ate Photocell on EDGE 2 input is misaligned with reflector Sensor is NOT a N C monitored sensor that is UL325 2016 compliant Sensor on EDGE 2 input photocell or edge may not be wired properly see Sensor on EDGE 2 is damaged or malfunctioning Sensor is NOT a N C monitored sensor that is UL325 2016 compliant Jumper between PHOTOCELL and GND is missing or broken jumper is required if a sensor is not ...

Страница 19: ...attery Button Press to show amount of battery power available when using battery power ONLY Battery voltage LEDs will light respectively Replace Battery LED Replace battery when lit BATTERY Plug MUST be plugged into BATTERY IN port Before use POWER SOLAR IN Port MAX Megatron Toroid box connection POWER IN Battery Pack Ports Back of MAX MC 200 motor controller connections ON O FF Battery E F 1 2 Ba...

Страница 20: ... meet the UL 325 2016 standard Type B1 Non Contact sensor entrapment protection device MUST be MONITORED by the gate operator NOTE DO NOT use 10K Resisitor included with photocell NOTE To meet the UL 325 2016 standard Type B1 Non Contact sensor entrapment protection device MUST be MONITORED by the gate operator Installation Steps 1 Set switch to LIGHT ON 2 Wire 12V power to photocell 3 Wire MC 200...

Страница 21: ...N See installation instructions ATTENTION Voir la notice d installation Edge 2 Photo Cell MC 200 PWR 12V MUST be used ONLY power entrapment protection sensors with MC 200 PWR 12V 2 3 A sensor MUST be wired to EDGE 1 or operator WILL NOT function Wire NORMALLY CLOSED N C MONITORED sensors ONLY to each operator s MC 200 when dual operators are used Reversing Edge and or Photo Cell can be wired to AN...

Страница 22: ...he 3 Inputs MC 200 PWR 12V MUST be used to power MONITORED sensors UNUSED inputs MUST remain JUMPERED or fault will occur GN D 1 2 3 GN D 1 2 3 Inputs MUST be LEARNED to MONITOR sensors To LEARN inputs 1 MONITORED Sensors MUST be wired to inputs BEFORE they can be learned Any unused inputs MUST be jumpered 2 Reversing Edge and or Photo Cell can be wired to either input 2 or 3 3 Press and HOLD the ...

Страница 23: ...n receiver 2 Wire 12V power to receiver polarity does not matter 3 Wire MC 200 EDGE 1 to receiver CH 1 P N C Wire MC 200 GND to receiver CH 1 COM 4 Wire MC 200 EDGE 2 to receiver CH 2 P N C Wire MC 200 GND to receiver CH 2 COM 5 Install antenna on receiver 6 Install batteries in transmitters 7 Wire Channel 1 Transmitter to CLOSING Edge ONLY 8 Wire Channel 2 Transmitter to OPENING Edge 9 Program Ch...

Страница 24: ...on River Ave Fountain Valley Ca 92708 Tel 949 699 0220 4009963 CONFORMS TO UL STD 325 UL CLASS I II III IV CERTIFIED TO CAN CSA STD C22 2 NO 247 SAFETY SENSORS REQUIRED Residential Commercial Brushless DC Swing Gate Operators Made in USA Version 10 ...

Отзывы: