background image

 

      

               

 

Single Phase EV Charger Protection unit 

 

 

 

                                                                

12 | 

P a g e

 

 

Connect the supply cable from the distribution board (or meter tails) directly to the RCBO ‘Incoming Supply’ 

terminals.  

Connect the outgoing cable to the contactor L, E & N terminals.  

 

If required, connect the CT to the 3 pin connector on the PCB 

 

Check ALL power and earth connections before switching on. 

 

THIS PRODUCT IS DESIGNED FOR AN ISOLATED EARTHING ARRANGEMENT.  CHECK 

BEFORE USING SWA CABLE

 

Содержание IP-EVCP-M

Страница 1: ...Single Phase Electric Vehicle Charger Protection Units SP EVCP T C SP EVCP R C SP EVCP M C SP EVCP B C IP EVCP T C IP EVCP R C IP EVCP M C Installation Manual V1 5 Aug 2020...

Страница 2: ...erating Instructions 14 Status Indicator 15 Specifications 16 Warranty 16 Declaration of Conformity 17 PRODUCT ADVISORY NOTICE This product must be installed by a competent person in accordance with t...

Страница 3: ...ter April 2020 The units are not intended for any purpose other than that defined within this document WARNINGS Please read and observe the following notices carefully These warnings must be observed...

Страница 4: ...e supplied with a split core CT for installing on the main incoming supply cable to the property See page 9 for connection details On detection of fault conditions the electronic circuit disconnects t...

Страница 5: ...Single Phase EV Charger Protection unit 5 P a g e...

Страница 6: ...Single Phase EV Charger Protection unit 6 P a g e...

Страница 7: ...Single Phase EV Charger Protection unit 7 P a g e...

Страница 8: ...pply cable from the distribution board directly to the Incoming Supply terminals Connect the outgoing cable to the contactor L E N terminals If required connect the CT to the 3 pin connector on the PC...

Страница 9: ...ly to the MCB Incoming Supply terminals Connect the outgoing cable to the contactor L E N terminals If required connect the CT to the 3 pin connector on the PCB Check ALL power and earth connections b...

Страница 10: ...directly to the RCBO Incoming Supply terminals Connect the outgoing cable to the contactor L E N terminals If required connect the CT to the 3 pin connector on the PCB Check ALL power and earth conne...

Страница 11: ...irectly to the MCB RCCD Incoming Supply terminals Connect the outgoing cable to the contactor L E N terminals If required connect the CT to the 3 pin connector on the PCB Check ALL power and earth con...

Страница 12: ...directly to the RCBO Incoming Supply terminals Connect the outgoing cable to the contactor L E N terminals If required connect the CT to the 3 pin connector on the PCB Check ALL power and earth conne...

Страница 13: ...Single Phase EV Charger Protection unit 13 P a g e Connection details for CT versions...

Страница 14: ...ith a split core CT to allow the unit to monitor whole house load The CT should be clamped around the incoming supply cable directly after the service providers meter It is designed to measure the FUL...

Страница 15: ...red flashes 1Hz recovers when current in range Tripped Under voltage 1 red flash over 4 sec period recovers when voltage in range Tripped Over voltage 2 red flashes over 4 sec period recovers when vo...

Страница 16: ...Document Revision V1 5 Aug 2020 Terminal Capacities Min Max Torque Incoming Terminals cable size tightening torque 0 5 mm2 6 0mm2 1 3Nm Incoming RCBO cable size tightening torque 2 5 mm2 25 0mm2 2Nm O...

Страница 17: ...J Charlton Director Emissions EN60255 1 2010 Emissions standard for Measuring Relays and Protection Equipment EN60255 26 2013 EN55011 2016 A1 2017 Emissions Standard for ISM Equipment EN55032 2012 Em...

Отзывы: