This controller can perform control functions for most Dual Pump pumping applications. It is more than likely that the 

control parameters have already been set up for your particular application, however, hereunder you will find details 

of the setup and configuration options.

DIP 

Switch

Position Function

1/2

Off/Off

Mode A: 

Standard typical float switch configuration (Start,Stop and High Level). No Low Level

Off/On

Mode B: 

Standard configuration plus low level (Start,Stop and High Level).

On/Off

Mode C: 

Standard configuration plus Prime Loss enabled, on Low Level (Input 1)

On/On

Mode D: 

Pressure Pumping configuration (Lead, Lag and Low Pressure)

3

Off

Operating Pump alternates each time a 

pu

mp start is triggered, or after 30 minutes continuous running.

On

Operating Pump alternates after 6 hours continuous running.

4

Off

Anti-seize Timer disabled

On

Anti-seize Timer 6 seconds every 7 days enabled

5

Off

When placed in Manual Mode, pump remains in Manual Mode

On

When placed in Manual Mode after 5 minutes the pump will revert to Auto

6

Off

High Level Alarm automatically resets upon open circuit of high level input. High Level alarm

has 15 minute delay.

On

High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay.

Mode A: Standard Configuration

Start/Stop/High  Level  operation.  When  the  Pump  Start  input  is  closed  contact  (triggered),  the  Duty  Pump 

will  be  turned  on.  The  pump  will  remain  on  until  both  the  Pump  Start  and  Pump  Stop  Inputs  have  turned  off

(Open Circuited). Upon High Level, both pumps will run until the Pump Stop Input turns off.

Input

Function

Input 1

Low Level

Input 2

Pump Stop

Input 3

Pump Start

Input 4

High Level

Mode B: Standard Configuration plus Low Level Alarm

As per Mode A, except it has an active Low Level input. The Low Level input must be closed, for Pump Start and 

Pump Stop inputs to function. The High Level input however, will still override the Low Level and run both pumps. 

Input functions are as follows:

OPERATION

In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if either pump has not run 

for 4 hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. 

Input functions are as follows:

There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and

“feature”options, as per the following table:

Input

Function

Input 1

Standby Start

Input 2

Pump Stop

Input 3

Pump Start

Input 4

High Level

Содержание FPC-30040-CON

Страница 1: ...PUMP ON FAULT PUMP ON FAULT MAIN ISOLATOR P U M P C O N T R O L OWNER S OPERATION MANUAL Dual Pump Controller Installation and Operating Instructions MODEL FPC 30040 CON DOC FPC 30040 CON VER 1 0...

Страница 2: ...st be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 A...

Страница 3: ...r enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to main isolator is not restricted 4 Ensure cables condui...

Страница 4: ...minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed conta...

Страница 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Страница 6: ...Mode Timeout With DIP Switch 5 set to On the pump will only remain in Manual Mode for 5 minutes after which time it automatically reverts to Auto High Level Alarm Reset The controller will also use th...

Страница 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100k Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separa...

Страница 8: ...tance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts C...

Страница 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case...