HRH-5

8595188136396

Indication of supply voltage
Choice of function

Function PUMP UP                                                                     Function PUMP DOWN

Relay is designed for monitoring levels in wells, basins, reservoirs, tanks...
In one device you can choose the following confi gurations:
- one-level switch of conductive liquids (by connecting H and D)
- two-level switch of conductive liquids
One-state device monitors one level, two-state device monitors two levels (switches on one level 
and switches off  on another level)
Choice of function PUMP UP, PUMP DOWN
Adjustable time delay on the output (0.5 - 10s)
Sensitivity adjustable by a potentiometer (5-100kΩ)
Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes
Galvanically separated supply voltage UNI 24.. 240 VAC/DC
Output contact 1xchangeover/SPDT  8A/250V AC1
1-MODULE, mounting onto a  DIN rail

Level switch 

HRH-5

Monitoring of two levels    

2

A1 - A2

24... 240 V AC/ DC (AC 50 - 60 Hz)

max. 2 VA

-15 %; +10 %

adjustable in range 5 kΩ -100 kΩ

max. AC 3.5 V

AC <0.1 mA

max. 400 ms

800 nF (sensitivity 5kΩ), 100 nF (sensitivity 100 kΩ)

adjustable, 0.5 -10 sec

1.5 sec

± 5 %

1x changeover/ SPDT (AgNi / Silver Alloy )

8 A / AC1

2500 VA , 240 W 

250 V AC1 / 24 V DC

500 mW

1x10

7

1x10

5

-20 °C to +55 °C (-4 °F to 131 °F)

-30 °C to +70 °C (-22 °F to 158 °F)

3.75 kV (supply - sensors)

any

DIN rail EN 60715

IP 40 from font panel / IP 10 terminals

III.

2

AWG 10 (2.5 mm2)

90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)

72 g (2.5 oz.)                       

 EN 60255-6,  EN 61010-1

 see pg. 90-91

Functions:
Supply terminals:
Voltage range:
Input:
Toleration of voltage range:
Measuring circuit
Sensitivity ( input resistance):
Voltage n electrodes:
Current in probes:
Time response:
Max. capacity of probe cable:
Time delay (t):
Time delay after switching on (t1):
Accuracy
Accuracy in setting (mechanical):
Output
Number of contacts:
Current rating:
Switching voltage:
Switched voltage:
Min. switched output DC:
Mechanical life (AC1):
Electrical life:
Other information
Operational temperature:
Storing temperature:
Electrical strenght:
Operational position:
Mounting:
Protection degree:
Overvltage category:
Pollution degree:
Profi le of connecting wires (mm

2

):

Dimensions:
Weight:
Standards:
Recommended measuring probes:

Connection

Function

Device description

Technical parameters

Tank with

 monitored level

Relay is designated for monitoring of levels of conductive liquids with possibility of functions: PUMP UP 

or PUMP DOWN. To prevent polarization and liquid electrolysis of liquid, and undesirable oxidation of 

measuring probes, alternating current is used. For measuring use three measuring probes: H- upper level, 

D-  lower level, C - common probe. In case you use a tank made of a conductive material, you can use 

it as probe C. In case you require monitoring of one level only, it is neccessary to connect inputs H and 

D and connect them to one probe - in this case sensitivity is lowered by half  (2.5... 50kΩ). Probe C can 

be connected with a protective wire of supply  system (PE). To prevent undesirable switching out output 

contacts by various infl uences (sediment on probes, humidity...) it is possible to set sensitivity of the device 

according to conductivity of monitored liguid (corresponding to “resistance” of liquid) range 5 up to 100kΩ. 

To reduce infuences of undesirable switching of output contacts by liquid gorgle in tanks, it is possible to set 

delay of output reaction 0.5 - 10s.

Symbol

!

!

!

!

!

!

!

!

!

!

Monioring of one level   

Un

max

level

min

15-18

red LED

Un

max

level

min

15-18

red LED

Tank with 

monitored level

     Supply voltage terminals

Terminals for conection of 

probes H, D

Output indication

Choice of function

Adjustment of 

delay on output

  Terminal for connection of 

probe C

Output contacts

EAN code

HRH-5 /UNI

Содержание FPC-30040-CON

Страница 1: ...PUMP ON FAULT PUMP ON FAULT MAIN ISOLATOR P U M P C O N T R O L OWNER S OPERATION MANUAL Dual Pump Controller Installation and Operating Instructions MODEL FPC 30040 CON DOC FPC 30040 CON VER 1 0...

Страница 2: ...st be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 A...

Страница 3: ...r enclosure must be mounted in a vertical position 2 Ensure mounting method does not compromise enclosure weather proof rating 3 Ensure access to main isolator is not restricted 4 Ensure cables condui...

Страница 4: ...minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed conta...

Страница 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Страница 6: ...Mode Timeout With DIP Switch 5 set to On the pump will only remain in Manual Mode for 5 minutes after which time it automatically reverts to Auto High Level Alarm Reset The controller will also use th...

Страница 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100k Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separa...

Страница 8: ...tance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts C...

Страница 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case...

Страница 10: ...hermal Overload TOL2 415VAC Pump P2 95 96 NC Contact TOL2 A1 A2 Contactor 18A 240Vac C2 Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 Inline Relay 12Vdc R1 Common Fault R1 1 BMS Volt Fr...

Страница 11: ...11 NOTES...

Страница 12: ...level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears...

Отзывы: