INTRODUCTION

1  INTRODUCTION

1.1   GENERAL

The Whisper  6/ 12 Mobile Diesel Generating set is ma-

nufactured and marketed by Mastervolt.

It is important to read this manual before installing and

operating the generating set. Both safety and durability

rely very much on the correct identification, installation

and a well understanding of  ratings, features, design,

maintenance and operation procedures.

The information, specifications, illustrations & statements

contained within this publication are given with our best

intentions and are believed to be correct at the time of

going to press. 

Our policy is one of continued development and we re-

serve the right to amend any technical information with-

out prior notice.

Whilst every effort is made to ensure the accuracy of the

particulars contained within this publication neither the

manufacturer, distributor, or dealer in any circumstances

shall be held liable for any inaccuracy or the consequen-

ces thereof.

WARNING: 

A warning symbol  draws attention to spe-

cial warnings, instructions or procedures

which, if not strictly observed, may result in

damage or destruction of equipment, seve-

re personal injury or loss of life.

DANGER: 

This danger symbol refers to electric dan-

ger and draws attention to special war-

nings, instructions or procedures which, if

not strictly observed, may result in electri-

cal shock which will result in severe per-

sonal injury or loss of life.

Realise that people are not used to have

230V available on a vehicle. Put warning

signs on wall sockets and on junction

boxes. Instruct non-regular users of the

vehicle. Warn maintenance personal of

garages that do service on the vehicle. 

1.2   SERVICE AND MAINTENANCE

Regular service and maintenance should be executed

according the directions in this manual. For service and

maintenance one can appeal to the manufacturer or the

dealers.

1.3   GUARANTEE

Mastervolt guarantees that this generating set has been

built according to good workmanship, according to the

specifications in this manual and according to European

Community safety regulations.

During production and prior to delivery, all of our genera-

ting sets are tested and inspected.

The well functioning of this generating set is subject to

guarantee. The period and conditions of this guarantee

are laid down in the general conditions of delivery as

registered with the Chamber of Commerce and Industries

in Amsterdam number 33279951 and are available on

request. The guarantee period is two years, limited to

1000 running hours. Some aspects of the warranty

scheme are given here in more detail:

Guarantee period 1000 running hours or 24 months

whichever occurs first. Warrantee does not cover failures

that are caused by misuse or a faulty installation.

Example 1. Faulty installation:

Overheating of the engine is the most common cause of

problems with mobile generating sets. These problems are

caused by poor circulation of the cooling liquid due to wrong

routing of the pipes to the radiators: bents will capture air

bubbles causing “air-lockes” blocking the circulation of the

liquid. Other examples of installation problems are hot air

circulation into the radiators and the radiator fans sucking

exhaust gasses into the radiators.

The generator and other parts should be protected against

the influences of the weather and splashing water (with dirt

and salt) below the vehicle. Refer the installation manual.

Example 2: Misuse:

Long term running with no load or too little load can

cause the exhaust to get choked with soot or carbon.

Cleaning the exhaust is not covered by warrantee.

Example 3: Neglect

Whisper generators have an option for an auto start/stop

mode or interval mode. 

Mastervolt cannot be held responsible for damage

caused by the unattended running generator.

Warranty means that faulty parts are repaired or replaced

free of charge. If necessary the whole generator unit will

be exchanged. Labour necessary to complete repairs on

board a vehicle executed by an authorised service

engineer is covered, but is limited to a reasonable

Содержание Whisper 6

Страница 1: ...g 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www mastervolt com USERS MANUAL FOR MOBILE APPLICATIONS V1 November 2004 WHISPER 6 12 3000 RPM Mobile diesel generating set 2...

Страница 2: ...lures 6 2 1 4 Installation 7 2 1 5 Operation 7 2 1 6 Fire and explosion 7 2 1 7 Chemicals 7 2 2 Transport lifting and storage 8 2 3 The Whisper 6 12 generating set 8 2 3 1 Features 8 2 3 2 Remote cont...

Страница 3: ...4 3 Regular maintenance 25 4 3 1 Maintenance schedule 26 4 3 2 Putting out of service 26 5 TROUBLE SHOOTING 27 5 1 Alternator malfucntions AC trouble 27 5 1 1 General 27 5 1 2 Trouble shooting check l...

Страница 4: ...this generating set has been built according to good workmanship according to the specifications in this manual and according to European Community safety regulations During production and prior to d...

Страница 5: ...n manual then damage may occur and the generating set may not fulfil its specifica tions In all these cases the guarantee may become invalid Use original parts only 1 4 LIABILITY Mastervolt does not a...

Страница 6: ...When working on the electrical system the 3 Amp fuse must be removed from the control panel and the battery plus cable must be removed from the battery Connection and protection must be done in accor...

Страница 7: ...y is closed Never the less take note of the signs on the generating set which shows symbols in a triangle indicating danger When service has to be executed while the engine is running be aware of movi...

Страница 8: ...removing the generating set from long term storage perform an insulation check Refer to the alternator maintenance paragraph for procedures While the battery is stored it should be recharge every 12 w...

Страница 9: ...d water cooled 13 Thermo switch alternator 14 Injector 2x W6000 3x W12000 15 Glowplug 2x W6000 3x W12000 16 Valve cover 17 Circulation pump engine cooling 18 Filling cap oil 2x 19 Solenoid 20 Electric...

Страница 10: ...t is based on the Mitsubishi L2E 2 cylinder W6 or L3E 3 cylinder W12 diesel engine The engine is indirectly injected The engine is water cooled and the cooling liquid is cooled by a radiator The engin...

Страница 11: ...n diesel en gines Fuel free from water and contaminants is of the ut most importance 2 5 11 Oil information 1 Specification The oil must be suitable for oil changes as specified in the maintenance cha...

Страница 12: ...ltage 230V 50 Hz alternating current AC single phase Output rating 50Hz 5 kW 6 10 kW 12 Power factor 1 Voltage tolerance 5 optional voltage regulator 2 Frequency tolerance 5 Optional electronical Gove...

Страница 13: ...water temperature switch 7 blue 1 mm2 LCP water temperature switch 7 blue black 1 mm2 DDC exhaust temperature switch 8 blue green 1 mm2 LCP exhaust temperature switch 8 blue rose 1 mm2 DDC fuel soleno...

Страница 14: ...M R E T R A T S G N I R U S E M T N E R R U C R E M R O F S N A R T BLUE 1 7 BLUE GREEN 1 8 0 1 J 7 1 K C A L B E U L B 8 J 2 1 5 1 K C A L B 2 1 J 8 1 K N I P E U L B PURPLE 1 6 4 1 J 6 1 K C A L B...

Страница 15: ...G N I R U S E M T N E R R U C R E M R O F S N A R T BLUE 1 7 BLUE GREEN 1 8 0 1 J 7 1 K C A L B E U L B 8 J 2 1 5 1 K C A L B 2 1 J 8 1 K N I P E U L B PURPLE 1 6 4 1 J 6 1 K C A L B E L P R U P 6 1...

Страница 16: ...O T O M R E T R A T S G N I R U S E M T N E R R U C R E M R O F S N A R T BLUE 1 7 BLUE GREEN 1 8 0 1 J 7 1 K C A L B E U L B 8 J 2 1 5 1 K C A L B 2 1 J 8 1 K N I P E U L B PURPLE 1 6 4 1 J 6 1 K C A...

Страница 17: ...EUTRAL NOT CONNECTED MAIN WINDING BLACK 4 BLACK 4 RED 3 MAIN WINDING GREEN 2 RED 3 EXCITATION GREEN 1 WINDING YELLOW GREEN DDC AC 1 YELLOW GREEN BLUE 33 BROWN 33 BLUE DDC ct 1 11 RED CURRENT TRANSFORM...

Страница 18: ...IATORCOOLER RADIATORCOOLER ENGINE FUSE 5A FUSE 5A POWER SUPPLY 230 VAC ENGINE GENERATOR 12VDC 12VDC M M 230VAC 230VAC M M 12VDC 12VDC K1 K1 K2 K2 230VAC 230VAC 230 115VAC 230 115VAC 200VA 200VA TRAFO...

Страница 19: ...NAL BLOCK THERMOSTAT COOLER ALTERNATOR BAT FUSE JUCTION BOX AIR FANS FUSE CONTROL PANEL RADIATOR COOLER ALTERNATOR PUMP 2 BAT ENGINE ENGINE M M M M M M M M CU0 75 80 70 C CU4 CU0 75 45 35 C CU0 75 4 1...

Страница 20: ...has been running under full load for a longer period do not shut it down abruptly Reduce the electrical load to about 30 of the rated load and let it run for approx 5 minutes 2 Press the STOP button...

Страница 21: ...n switching on your electrical devices Nevertheless the Whisper is designed so as not to overheat even under extreme conditions Do not run the generator for very long periods at no load or at very low...

Страница 22: ...linder glazing and high oil consump tion For the same reason it is of the greatest importance to use the right oil specifica tion The first time starting up or after running out of fuel it could be ne...

Страница 23: ...5 4 2 Observe the exhaust at the normal full load The exhaust must be free from soot Do not allow the engine to run with a dirty exhaust without investi gating the cause as this may result in an expen...

Страница 24: ...n and put them in a can with preservation diesel fuel Start the engine and run the engine warm 3 Drain the hot engine oil and refill with preservation oil 4 The coolant can stay in the engine and radi...

Страница 25: ...excitation if the problem is in the capacitors or in the windings Rotor diodes broken Check the diode in the rotor refer to special procedures The Whisper 6 ULTRA has one diode in the rotor Generator...

Страница 26: ...RT BAT Starter battery voltage too low ALTERNATOR No output battery charging voltage AC ALTERN TEMP Alternator temperature is too high WATER TEMP Coolant temperature is too high OIL PRESSURE Oil press...

Страница 27: ...ction Blocked injector Have the injector tested and cleaned if necessary Wrong valve clearance Adjust valve clearance Temporarily hunting this will disappear when engine has run in Engine speed drops...

Страница 28: ...eplace V belt Thermostat faulty Check thermostat and replace Sooty black exhaust Generator is being overloaded Check electrical load and switch off some Display will indicate Overload consumers Insuff...

Страница 29: ...tery is used for flashing one must take care A short circuit can cause heavy sparking fire and injuries When flashing does not bring back voltage the capaci tor s should be renewed When this does not...

Страница 30: ...screw is to be locked in position with the lock nut 5 4 2 Adjusting valve clearance and retightening the cylinder head bolts Both procedures has to be executed with a cold engine When both procedures...

Страница 31: ...When the 6 nuts in total are removed the generating set can be lifted out the canopy 5 nuts are well accesible The sixth nut has to be removed by taking out the bold from the bottom of the canopy 2 T...

Страница 32: ...g of Shaft 13 Bearings 2 pcs 10 O ring 9 Seals 2 pcs 8 Clips 1 set 11 12 O ring 14 50209010 Waterpump repair kit B same as repair kit A excluding the shaft 13 and O ring 14 50201060 Capacitor xx micro...

Страница 33: ...r to impeller 4 Impeller 1x including screw 3 50209013 5 Gasket 1x 50209012 6 Pump housing 1x 50201813 8 Seal 2x 50209015 9 O ring 1x 50209017 10 Bearing 2x 50209014 11 Clip 2x 50209019 12 Clip 1x 502...

Страница 34: ...34 November 2004 WHISPER 6 12 Mobile EN INFORMATION LOG first service after 50 hours hour counter remarks next service every 150 hours hour counter remarks...

Страница 35: ...EN WHISPER 6 12 Mobile November 2004 35 NOTES...

Страница 36: ...November 2004 WHISPER 6 12 Mobile EN MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www mastervolt com info mastervolt com...

Отзывы: