Mastervolt Solar ChargeMaster SCM-N 20 Скачать руководство пользователя страница 6

 
 
 
 
 
INSTALLATION  

 

 

6

 

November 07 / Solar ChargeMaster 20, 40 / EN 

 

4 INSTALLATION 

 

WARNING 
During installation and commissioning of 
the Solar ChargeMaster, the Safety 
Guidelines and Measures are applicable 
at all times. See chapter 2 of this manual. 

 

CAREFUL! 
Wrong connections may cause damage to 
the Solar ChargeMaster and other 
equipment as well, which is not covered 
by warranty! 

 
4.1 

Grounding the Solar System 

Be aware that the Solar ChargeMaster has negative 
grounding. See also figure 7. The negative terminals 
of the Solar ChargeMaster controller are connected 
internally and therefore have the same electrical 
potential. If any grounding is required, always 
connect this to the negative wires. 
 

4.2 

Things you need for installation 

4.2.1 Tools: 

A cross-head screw driver is all you need for the 
strain relieves, the screw terminals and the fastening 
screws for the housing. See also figure 5. 
 

WARNING! 
Use isolated tools! 

 
 

4.2.2 Materials: 

Part  

Part nr. 

Incl. 

Solar Chargemaster SCM-N 20 

131802000 

 

Solar Chargemaster SCM-N 40 

131804000 

 

Temperature sensor 

41500900 

yes 

PC Link USB (option)  

21730400 

no 

4 screws 4,5 mm for wall 
mounting 

 no 

DC wiring 

 

no 

 
For advanced use you need the Solar ChargeMaster 
data control software (downloadable from www. 
Mastervolt.com) 
 
Mind the recommended wire size, see this table.  
Model 

Length < 1m

Length 1-3

SCM20-N 

4 mm²

6 mm²

SCM40-N 

10 mm²

16 mm²

Place positive and negative wire close to each other 
to minimize electromagnetic effects. 
 

Mind that the screws have to carry also 
the force applied by the wiring. 
Mind the minimum required distance of 10 
cm/ 4" to floor and ceiling, this is 
necessary for ventilation reasons. 

Installation step by step 
1.  Open the terminal lid. See figure 6. 
2.  Remove the screws from the strain relief and 

take off the strain relief bridges. See figure 5 too. 

3.  Mount the controller to the wall. Use appropriate 

screws for the wall material. Use screws with 4 
to 5 mm shaft and max. 10 mm head diameter, 
no counter sunk. See figure 5 for locating the 
mounting holes. 

 

Figure 6 

 

4.  Connect the wires leading to the battery with 

correct polarity. See figure 7. To avoid any 
voltage on the wires, first connect the controller, 
then the battery. 
 

Wrong polarity will cause a permanent warning 
sound. 
The controller has a built-in voltage drop 
compensation which automatically compensates 
battery wire voltage drops of up to 250 mV. 
 

 
WARNINGS!  
 

  If the battery is connected with reverse polarity, 

the load terminals will also have the wrong 
polarity. Never connect loads during this 
condition! 

  A fuse must be integrated in the positive lead to 

the battery to protect any short circuit at the 
battery wiring. Mind the recommendations of 
your battery manufacturer. 

  The fuse must take the charge controller 

maximum current: Solar ChargeMaster20: 30A, 
Solar ChargeMaster40: 50A. 

  Solar panels provide voltage as soon as 

exposed to sun light. Mind the solar panel 
manufacturer’s recommendations in any case. 

 
5.  To avoid voltage at the load terminal, push the 

button (see figure 5) shortly to shut off the load 
output. 

6.  Connect the wires leading to the loads with 

correct polarity. See figure 7. 

7.  Fasten the strain relieves. 

Содержание Solar ChargeMaster SCM-N 20

Страница 1: ...Solar ChargeMaster SCM N 20 SCM N 40 INTELLIGENT CHARGE CONTROLLER MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www Mastervolt com ENGLISH PAGE 1...

Страница 2: ...ement of the product Costs for installation labor or shipping of the defective parts are not covered by this guarantee 1 3 Validity of this manual All of the specifications provisions and instructions...

Страница 3: ...arly applies to chapter 2 Safety Guidelines and Measures 2 4 Maintenance repair In case of maintenance and repair activities disconnect batteries and PV modules to prevent unintentional damage to the...

Страница 4: ...stem For example street lights and road signs are often solar powered Overnight the battery is discharged during a preset time using the nightlight function Dusk to Dawn At day the battery is recharge...

Страница 5: ...4V 24V 72 44V 36V With a 12V system the Solar ChargeMaster 40 can supply a maximum power of 480W To connect higher power devices you will need more than one Solar ChargeMaster or change the system vol...

Страница 6: ...screws have to carry also the force applied by the wiring Mind the minimum required distance of 10 cm 4 to floor and ceiling this is necessary for ventilation reasons Installation step by step 1 Open...

Страница 7: ...ricted Normal operation Unrestricted Battery connected with wrong polarity to Unrestricted Unrestricted Unrestricted Reverse polarity at 24V system no 12V system yes Yes if only the battery is connect...

Страница 8: ...conditions are shown in the LCD screen if the Low Voltage Disconnect function shuts off the load output or in case of various other error conditions See chapter 7 for details Figure 9 Load control 5 3...

Страница 9: ...n dusk and dawn no real time setting is required It may take some days until the controller has learnt midnight This method can cause some inaccuracy but avoids any clock readjustment The controller s...

Страница 10: ...olyte In this menu you can select the proper battery type liquid electrolyte or GEL VRLA AGM according to your PV system to get better charge of your battery The default battery type is liquid electro...

Страница 11: ...his menu See section 5 4 2 for details The default nightlight function EVENING is OFF Mid of night 6 1 5 Nightlight function morning settings Description Displays Settings MORNING OFF Morning From to...

Страница 12: ...ge Day Night threshold 5 5 11 0 V Solar Voltage Day Night threshold 6 0 12 1 V Solar Voltage Day Night threshold 6 6 13 2 V Solar Voltage Day Night threshold 7 2 14 3 V Solar Voltage In this menu you...

Страница 13: ...section 4 4 1 Default Read in of current data Read in of current data Read back of data logger PC link bidirectional communication 6 1 9 Individual factory settings Description Displays Settings You c...

Страница 14: ...1 0 V Check if other sources overcharge the battery If not controller is damaged Loads are not supplied flashing symbols Battery wires or battery fuse damaged battery has high resistance Check battery...

Страница 15: ...e 13 7 27 4 V 25 C 13 7 27 4 V 25 C Load disconnect voltage 11 0 12 2 22 0 24 4 V depending on setting 11 0 12 2 22 0 24 4 V depending on setting Load reconnect voltage 12 8 25 6 V 12 8 25 6 V Tempera...

Страница 16: ...N 40 Is in conformity with the directives and standards 2006 95 EC Electrical Apparatus Low Voltage Directive 89 336 EEC Electromagnetic compatibility directive 93 68 EEC CE marking EN 60730 1 Electr...

Отзывы: