TROUBLE SHOOTING 

 

 

 

14

 

November 07 / Solar ChargeMaster 20, 40 / EN 

 

7 TROUBLE 

SHOOTING 

 
Error Description 

Error 
condition 

Display Reason 

Remedy 

Battery is low 

Load will reconnect as soon as battery is recharged. 

Overcurrent / Short 
circuit of loads 

Switch off all loads. Remove short circuit. Controller 
will switch on load automatically after max 1 minute. 

Controller is thermally 
overloaded and has 
disconnected the loads. 

Check proper ventilation of controller. 
After cooling down the loads are reconnected 
automatically. 

 

Battery voltage too high 
(>15.5 / 31.0 V) 

Check if other sources overcharge the battery. If not, 
controller is damaged. 

Loads are not 
supplied 
(flashing 
symbols). 

Battery wires or battery 
fuse damaged, battery 
has high resistance 

Check battery wires, fuses and battery. 

Battery is flat 
after short 
time 

 

Battery has low capacity  Change battery 

Battery is not 
being charged 
during 
daytime 

No up-moving 
bars 

Solar array faulty or 
wrong polarity 

Check Solar array and wiring 

Battery wrong 
polarity 

Permanent 
sound 

Battery is connected with 
reverse polarity 

Change polarity 

Controller is thermally 
overloaded 

Mount controller at a location with better ventilation 

Controller 
limits solar 
current 
(flashing 
symbols). 

 

Solar array exceeds 
nominal current of 
controller. 

Check solar array current. 

Содержание Solar ChargeMaster SCM-N 20

Страница 1: ...Solar ChargeMaster SCM N 20 SCM N 40 INTELLIGENT CHARGE CONTROLLER MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www Mastervolt com ENGLISH PAGE 1...

Страница 2: ...ement of the product Costs for installation labor or shipping of the defective parts are not covered by this guarantee 1 3 Validity of this manual All of the specifications provisions and instructions...

Страница 3: ...arly applies to chapter 2 Safety Guidelines and Measures 2 4 Maintenance repair In case of maintenance and repair activities disconnect batteries and PV modules to prevent unintentional damage to the...

Страница 4: ...stem For example street lights and road signs are often solar powered Overnight the battery is discharged during a preset time using the nightlight function Dusk to Dawn At day the battery is recharge...

Страница 5: ...4V 24V 72 44V 36V With a 12V system the Solar ChargeMaster 40 can supply a maximum power of 480W To connect higher power devices you will need more than one Solar ChargeMaster or change the system vol...

Страница 6: ...screws have to carry also the force applied by the wiring Mind the minimum required distance of 10 cm 4 to floor and ceiling this is necessary for ventilation reasons Installation step by step 1 Open...

Страница 7: ...ricted Normal operation Unrestricted Battery connected with wrong polarity to Unrestricted Unrestricted Unrestricted Reverse polarity at 24V system no 12V system yes Yes if only the battery is connect...

Страница 8: ...conditions are shown in the LCD screen if the Low Voltage Disconnect function shuts off the load output or in case of various other error conditions See chapter 7 for details Figure 9 Load control 5 3...

Страница 9: ...n dusk and dawn no real time setting is required It may take some days until the controller has learnt midnight This method can cause some inaccuracy but avoids any clock readjustment The controller s...

Страница 10: ...olyte In this menu you can select the proper battery type liquid electrolyte or GEL VRLA AGM according to your PV system to get better charge of your battery The default battery type is liquid electro...

Страница 11: ...his menu See section 5 4 2 for details The default nightlight function EVENING is OFF Mid of night 6 1 5 Nightlight function morning settings Description Displays Settings MORNING OFF Morning From to...

Страница 12: ...ge Day Night threshold 5 5 11 0 V Solar Voltage Day Night threshold 6 0 12 1 V Solar Voltage Day Night threshold 6 6 13 2 V Solar Voltage Day Night threshold 7 2 14 3 V Solar Voltage In this menu you...

Страница 13: ...section 4 4 1 Default Read in of current data Read in of current data Read back of data logger PC link bidirectional communication 6 1 9 Individual factory settings Description Displays Settings You c...

Страница 14: ...1 0 V Check if other sources overcharge the battery If not controller is damaged Loads are not supplied flashing symbols Battery wires or battery fuse damaged battery has high resistance Check battery...

Страница 15: ...e 13 7 27 4 V 25 C 13 7 27 4 V 25 C Load disconnect voltage 11 0 12 2 22 0 24 4 V depending on setting 11 0 12 2 22 0 24 4 V depending on setting Load reconnect voltage 12 8 25 6 V 12 8 25 6 V Tempera...

Страница 16: ...N 40 Is in conformity with the directives and standards 2006 95 EC Electrical Apparatus Low Voltage Directive 89 336 EEC Electromagnetic compatibility directive 93 68 EEC CE marking EN 60730 1 Electr...

Отзывы: