February 2005 / Mass Sine 5000 / EN
15
4.5
Connecting the remote control panel
The remote control panel C4-RI for the MASS inverter comprises an
off/on switch and two LED’s. The LED 'inverter on' indicates proper
functioning of the inverter and the availability of 230/117V AC output
voltage. The LED 'failure' indicates overload, over temperature or too
low voltage. Connect the remote control panel by means of a telephone
cable (not supplied with the panel).
4.6
Commissioning after installation
Carefully check the polarity of the connections.
CAUTION!
Only insert the inverter fuse if the polarity is correct.
Switching on with incorrect polarity will damage the inverter irreparably.
The inverter fuse cannot prevent this.
If the connections are correct:
•
check whether the on/off switch is in the OFF position;
•
when inserting the inverter fuse, a spark will occur, caused by the
capacitor used in the inverter. This is normal.
The inverter is now ready for use.
4.7
Automatic switching between Mass inverter, the AC
generator and / or shore power
Please contact your Mastervolt supplier if you intend to use the inverter
with a generator or shore power connection. Hand switched or simple
relay switching systems could damage your inverter, because of the
lack off time delay. This kind of damage is not covered by the warranty.