3-Step+  charge  system  is  also  safe  for  all  the  connected 
equipment. 
 

3.2.2 

Temperature compensated charging 

The  Mass  Combi  Pro  is  delivered  with  a  battery 
temperature  sensor.  By  installing  this  battery  temperature 
sensor  (for  Lead  Acid  batteries  only)  the  charge  voltages 
are  automatically  adapted  for  deviating  temperatures. 
When  the  battery  temperature  is  low,  the  charge  voltage 
increases.  On  the  other  hand,  when  the  battery 
temperature  is  high,  the  charge  voltage  is  decreased. 
Overcharge  and  gassing  are  prevented  this  way.  This  will 
extend the life of your batteries. 
 

Temperature  compensated  charging  cannot 
prevent 

the 

batteries 

from 

overcharging 

situations. 

 

3.2.3 

Silent mode 

When the Mass Combi Pro is in operation, the cooling fans 
produce  audible  noise.  In  silent  mode  the  noise  level  is 
reduced. As a result: 

 

the charge current may be limited; 

 

the charging time may increase. 

 

3.3 

Inverter 

3.3.1 

General 

The  inverter  provides  voltage  and  frequency  regulated  AC 
power  from  a  battery  bank.  Fast  acting  electronic  circuits 
protect  the  inverter  against  extreme  overloads,  low  and 
high battery voltage and overheating of the inverter. 
A  large  momentary  surge  power  is  available  for  inductive 
loads, such as electric motors. 
 

3.3.2 

Energy saving mode (selectable) 

In  the  inverter  mode  the  Mass  Combi  Pro  has  a  built-in 
automatic  energy  saving  feature  that  reduces  battery 
power  consumption  when  no  load  is  present  on  the 
outputs.  Response  from  idle  is  instant.  In  most  cases  the 
operation  is  not  noticeable.  The  energy  saving  mode  can 
be  set  by  means  of  MasterBus  or  dipswitch  A4,  refer  to 
chapter 6, Configuration. 

The  Mass Combi Pro scans the AC outputs with pulses of 
230  V  every  2½  seconds.  When  it  detects  a  load  that  is 
larger  than  50  W  (adjustable),  it  switches  On  the  inverter 
automatically.  
 

Small  loads  such  as  clocks  in  VCR’s  or  micro 
waves are most likely not to work in this mode. 

3.4 

Operation modes 

The  Mass  Combi  Pro  is  not  just  a  combination  of  an 
inverter  and  a  battery  charger.  Many  additional  features 
help  to  increase  the  total  available  AC  power.  In  the  next 
sections,  nine  different  main  operation  modes  are 
described. Most of these modes can be combined, refer to 
section  3.4.10.  You  can  enable  these  modes  by  means  of 
front switch, DIP switches or the MasterBus user interface. 
All modes are enabled by default except for the Gen/Mains 
supporting  mode  as  there  are  regulations  in  some 
countries that do not allow this. After enabling by the user, 
becoming  “active“  of  a  mode  is  determined  by  the  Mass 
Combi  Pro  itself  based  on  AC  and  DC  power  availability, 
battery  state  of  charge  and  configuration  (Chapter  6,  
Configuration). 
 

3.4.1 

Inverting mode 

See  figure  3-3.  When  there  is  no  external  AC  power 
available, the inverter of the Mass Combi Ultra provides AC 
power on the AC outputs. 
 

 

Figure 3-3: Inverting mode 

 

3.4.2 

Charging mode 

See  figure  3-4  and  3-5.  When  external  AC  power  comes 
available on the Mains- or Gen input, the main battery will 
be  charged  and  the  AC  outputs  are  supplied  by  the 
external power. 
 

Содержание MASS COMBI PRO 12/3000-150

Страница 1: ...MASS COMBI PRO 12 3000 150 24 3500 100 MULTI PURPOSE CHARGER INVERTER USER AND INSTALLATION MANUAL 10000010915 02 ...

Страница 2: ...Pro 1 Display with front switch 6 AC output 1 OUT 1 11 Sync connector 2x 2 Main battery negative 7 AC output 2 OUT 2 switched 12 Temperature sensor connector 3 Main battery positive 8 DIP switch units 2x8 13 MasterBus connector 2x 4 Mains AC input terminal MAINS 9 Fan 3x 5 Generator AC input terminal GEN 10 Ground stud 1 2 3 4 5 6 7 ...

Страница 3: ...2 7 Warning regarding the use of batteries 6 3 HOW IT WORKS 7 3 1 Principle 7 3 2 Battery charger 7 3 3 Inverter 8 3 4 Operation modes 8 4 OPERATION 11 4 1 LED indicators 11 4 2 Protections 12 4 3 Operation policies 12 4 4 Maintenance 13 4 5 Daily use MasterBus monitoring 13 5 INSTALLATION 14 5 1 Unpacking 14 5 2 Environment 14 5 3 Wiring 14 5 4 Things you need 15 5 5 Removal of the front lid 15 5...

Страница 4: ... purchase on the condition that the product is installed and used according to the instructions in this manual Installation or use not according to these instructions may result in under performance damage or failure of the product and may void this warranty The warranty is limited to the cost of repair and or replacement of the product Costs of labor or shipping are not covered by this warranty 1...

Страница 5: ...le products 3 Use of the Mass Combi Pro other than mentioned in point 2 is considered to be inconsistent with the intended purpose Mastervolt does not hold itself liable for any damage resulting from the above 2 3 Organizational measures The user must always have access to the user s manual be familiar with the contents of this manual This applies in particular to Chapter 2 Safety Guidelines and M...

Страница 6: ...re not sold for applications in any medical equipment intended for use as a component of any life support system unless a specific written agreement pertaining to such intended use is executed between the manufacturer and Mastervolt Such agreement will require the equipment manufacturer either to contract additional reliability testing of the Mass Combi Pro parts and or to commit to undertake such...

Страница 7: ...system See figure 3 2 The first step of the 3 Step charge system is the BULK phase in which the output current of the charger is 100 and the greater part of the battery capacity is charged rapidly The current charges the batteries and gradually the voltage rises to the absorption voltage refer to the specifications The duration of this phase depends on the ratio of battery capacity to charger curr...

Страница 8: ...ower consumption when no load is present on the outputs Response from idle is instant In most cases the operation is not noticeable The energy saving mode can be set by means of MasterBus or dipswitch A4 refer to chapter 6 Configuration The Mass Combi Pro scans the AC outputs with pulses of 230 V every 2 seconds When it detects a load that is larger than 50 W adjustable it switches On the inverter...

Страница 9: ...uit breaker may trip if nothing is done To avoid this the Mass Combi Ultra can automatically reduce the battery charger output and thus the AC power consumption This Power sharing feature constantly senses the incoming AC current which is used to supply both the battery charger and the appliances connected to the AC outputs The Power Sharing level should be set to match the value of the external c...

Страница 10: ...arallel with the external AC power source This means that energy from the batteries is added to the AC output only Under no circumstances AC power from the inverter can be fed back into the AC grid Please mind that several countries maintain different regulations with regard to AC sources operating in parallel with the AC grid This may mean that in some situations the use of the Generator Mains su...

Страница 11: ...uring charging the blinking LED s indicate the charge phase of the 3 Step charge algorithm During inverting the LEDs give a rough estimation of the battery voltage the more LED s are illuminated the higher the battery voltage 4 1 7 Main switch See figure 4 1 item 7 The only control on the Mass Combi Pro itself is the main switch on the front of the unit This switch controls on off and Inverter off...

Страница 12: ...ected against over and under voltage See specifications If the AC input voltage is out of operating range the Mass Combi Pro will switch to inverter mode disconnecting both AC inputs and it will switch back if the AC input voltage is within range again The DC input of the Mass Combi is also protected against over and under voltage See specifications The Mass Combi Pro switches off if the DC input ...

Страница 13: ...Generator Mains Poor quality 1 5 4 AC out state State of the AC output No AC output AC out1 only AC out1 2 1 6 5 Main charger Main charger state On Off 1 7 58 Battery DC Main charger Main battery state of charger Bulk Absorption Float Standby Const volt Error 2 1 18 Main battery Main battery voltage 0 16 V 0 32 V 0 64 V 2 2 6 Main battery Main battery current minus is discharging 500 500 A 2 3 7 B...

Страница 14: ...cts must be located within a distance of 10 cm 4 inch around the Mass Combi Pro Keep at least 15 cm 6 inch free space below the Mass Combi Pro Do not locate the Mass Combi Pro in the same compartment as the batteries Do not install the Mass Combi Pro straight above the batteries because of possible corrosive fumes 5 3 Wiring The wiring is connected inside the connection compartment If necessary th...

Страница 15: ...en the neutral conductor N and earth PE GND is not required or acceptable Therefore the automatic connection between the neutral conductor N and earth PE GND is disabled by default For safe installation it is necessary to insert a Residual Current Device earth leakage switch of 30 mA in the AC in and outputs of the Mass Combi Pro Refer to local regulations on these issues 5 4 Things you need Make ...

Страница 16: ...olts finger tight so shifting is still possible 4 Place the two lowermost bolts 5 Fasten all bolts securely 5 7 Wiring instructions WARNING Have installation work done by a licensed electrician only Before connecting the wiring make the AC distribution as well as the DC distribution voltage free Move the main switch to the Off position CAUTION Short circuiting or reversing polarity may lead to ser...

Страница 17: ...on Manual 17 5 8 Installation overview Figure 5 4 Installation overview for one Mass Combi stand alone operation CAUTION Ensure correct polarities cross sections and fuses for all wiring An RCD according to local regulations must be connected to output 1 and 2 ...

Страница 18: ... MasterBus network is highly flexible for extended system configuration Mastervolt also offers several interfaces like the Modbus interface making even non MasterBus devices suitable to operate in the MasterBus network For central monitoring and control of the connected devices Mastervolt offers different panels like the full colour MasterView System panel All monitoring panels can be used for mon...

Страница 19: ...d PE GND when the Mass Combi Pro is working as an inverter The ground relay function allows you to connect the Neutral conductor N of the inverter output circuit to the Safety Ground PE GND automatically when the Mass Combi is working as an inverter Refer to local standards on this issue Figure 6 1 DIP switches and cover print DIP switch Function A1 A2 Parallel mode 0 0 Stand alone 1 0 Master 0 0 ...

Страница 20: ...f which must be used by the Mass Combi Pro No shunt Shunt devices in the list Main charger Maximum current Maximum charging current adjustable 100 A 1 150 A 1 100 A 1 50 A Method Charging method selectable 3 Step refer to chapter 3 3 Step constant voltage Battery type Select the main battery type Flooded Lead acid wet cell User defined Flooded Gel AGM Spiral MLi Flooded traction Nickel Cadmium Bul...

Страница 21: ...w off 100 Low battery inverter switch off voltage batt current 100 12 24 48V user def 9 50 19 00 38 00V 9 50 13 00 19 00 26 00 38 00 52 00V DC low on Low battery inverter switch on voltage at DC Low off alarm 12 24 48V user def 12 00 24 00 48 00V 10 00 13 00 20 00 26 00 40 00 52 00V DC low off delay Delay time before inverter switches off on low battery voltage 30 s 0 30 s AC transfer AC input pol...

Страница 22: ...can initiate an event at another MasterBus connected device Event source Description Disabled no event programmed Inverting The Mass Combi Pro is in Inverter mode Charging The Mass Combi Pro is in Charge mode Supporting The Mass Combi Pro is in Supporting mode Overload The inverter current is too large Low bat The main battery voltage has dropped below the Low bat value Alarm A Mass Combi Pro alar...

Страница 23: ...sary to put the Mass Combi Pro out of operation follow the instructions in order of succession as described below 1 Move the Main switch of the Mass Combi Pro to Off 2 Remove DC distribution fuses and or disconnect the batteries 3 Remove AC input fuses and or switch off the AC sources 4 Open the connection compartment of the Mass Combi Pro 5 Check with a suitable voltage meter whether the inputs a...

Страница 24: ...refer to generator input specifications in chapter 8 3 red MB monitoring Overload Inverter in overload inverted power exceeds 3500 W Check the load connected and disconnect 9 red Battery low Battery voltage low Stop inverting start charging 9 blinking red Charging a low battery Errors Mass Combi Pro shuts down 3 and 9 red 4 yellow Overtemperature Combi too hot Restart when alarm is over Check vent...

Страница 25: ...ttery 14 5 V 2 29 0 V 2 Max ripple on DC full load 5 RMS 5 RMS Nominal DC current at full load 300 A 175 A Recommended batteries 300 900 Ah 200 600 Ah No load DC drain Off mode hard switched 0 W 0 W Inverter off mode remote 4 W 4 W Energy saving mode 7 W 7 W Normal operation mode 16 W 16 W Battery charger specifications Input voltage range 184 275 V 184 275 V Max AC input current 12 A 16 A Max cha...

Страница 26: ...y conformal coating max 95 relative humidity none condensing Standards approvals listings CE ABYC Options features Front panel display Yes shows charge state inverter power input output state and includes on off inverter off switch Battery temperature sensor Yes Cooling Maintenance free vario fans MasterBus functionality MasterBus powering Standard on selectable Overload protection Gen Mains input...

Страница 27: ...Mass Combi Pro 12 3000 150 24 3500 100 User and Installation Manual 27 8 2 Dimensions Figure 8 1 Dimensions in mm ...

Страница 28: ...CONSIN 53051 USA 1 800 307 6702 Option 1 technical marinco com ASIA PACIFIC 42 Apollo Drive Rosedale AUCKLAND 0632 New Zealand 64 9 415 7261 enquiries bepmarine com Copyright 2019 Mastervolt All rights reserved Reproduction transfer distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited ...

Отзывы: