Mass Combi Pro 12/3000-150, 24/3500-100
– User and Installation Manual
21
Value
Meaning
Default
Adjustable range
Float settings
Float voltage
Float voltage (adjustable if User Defined).
13.25/26.50/53.0 V
8-16.00/16-32.00/32-64.00 V
Inverter
Voltage
AC voltage
230 V
180-260 V
Frequency
AC frequency
50 Hz
50 Hz, 60 Hz
Enable GND rel.
Option to enable ground relay
Not checked
Not checked, checked
Energy save mode
Option to enable Energy save mode
Not checked
Not checked, checked
Scanning below
The Combi starts scanning below this
inverted power level in Energy save
mode.
10 W
10-250 W
Dynamic window
Select to base the input window upon
battery type default values or upon your
own preset values. Refer to section 4.2.4
Use battery type
Use battery type, user defined (Use
battery type: dynamic input window
still present, but not configurable)
DC high off
High battery voltage for inverter switch off
(12/24/48V, user defined only).
16.00/32.00/64.00V
13.00-16.00/26.00-32.00/52.00-
64.00V
DC high on
High battery voltage for inverter switch to
DC High Off alarm (12/24/48V, user def.)
15.50/31.00/62.00V
13.00-16.00/26.00-32.00/52.00-
64.00V
DC low off I=0%
Low battery voltage at which the inverter
switches off when the battery current is
0-2% of nominal (12/24/48V, user def.)
10.00/20.00/40.00V
9.50-13.00/19.00-26.00/38.00-
52.00V
DC low off I=2%
Low battery voltage at which the inverter
switches off when the battery current is
2% of nominal (12/24/48V, user def.)
9.75/19.50/39.00V
9.50-13.00/19.00-26.00/38.00-
52.00V
DC low off 100%
Low battery inverter switch off voltage,
batt. current 100% (12/24/48V, user def.)
9.50/19.00/38.00V
9.50-13.00/19.00-26.00/38.00-
52.00V
DC low on
Low battery inverter switch on voltage at
DC Low off alarm (12/24/48V, user def.)
12.00/24.00/48.00V
10.00-13.00/20.00-26.00/40.00-
52.00V
DC low off delay
Delay time before inverter switches off on
low battery voltage.
30 s
0-30 s
AC transfer
AC input policy
Define which AC input to be used under
which conditions, refer to section 4.3
Gen preferent
Mains preferent, Gen preferent, Max
fuse prefer
AC out 2 policy
Define under which conditions to use AC
output-2, refer to section 4.3
Gen/Mains input
Events only, Generator input, Mains
input, Gen/Mains input, Always on
Generator fuse
Generator fuse value
25 A
1-50 A
Mains fuse max.
Mains fuse maximum value that can be
set in the monitoring tab
30 A
1-30 A
Mains limit A
Mains fuse value setting
6 A
1-30 A
Mains limit B
Mains fuse value 10A
10 A
1-30 A
Mains limit C
Mains fuse value 16A
16 A
1-30 A
Power sharing
Power sharing mode option, chapter 3.
Checked
Not checked, checked
Allow AC support
AC support mode option, chapter 3.
Not checked
Not checked, checked
Gen. high volt.
Generator AC input window
275 V
184-275 V
Gen. low volt.
Generator AC input window
180 V
184-275 V
Gen. high freq.
Generator AC input window
58 Hz
36-68 Hz
Gen. low freq.
Generator AC input window
40 Hz
36-67 Hz
Generator delay
Time to trigger a Generator alarm
10 s
5
– 300 s
Mains high volt.
Mains AC input window
275 V
184-275 V
Mains low volt.
Mains AC input window
180 V
184-275 V
Mains high freq.
Mains AC input window
65 Hz
35-68 Hz
Mains low freq.
Mains AC input window
40 Hz
35-68 Hz
Mains delay
Time to trigger a Mains alarm
10 s
5-20 s