Note:
Never use any solvents, abrasives or corrosive materials to clean the inverter.

CAUTION:
Do not touch the surface when the inverter is operating. Some parts may be hot 
and cause burns. Turn OFF the inverter (refer to Section 6.2) and let it cool down 
before you do any maintenance or cleaning of inverter.

The LCD and the LED status indicator lights can be cleaned with cloth if  they are too dirty 
to be read.

The inverter has been designed in accordance with international grid tied standards for 
safety, and electromagnetic compatibility requirements. Before delivering to the customer 
the inverter has been subjected to several tests to ensure it’s optimal operation and reliability.

Solis three phase string inverter does not require any regular maintenance. However, cleaning the 
heat-sink will help in dissipating heat and increase the life time of inverter. The dirt on the
inverter can be cleaned with a soft brush.

9. Troubleshooting

In case of a failure the LCD screen will display an alarm message. In this case the inverter 
may stop feeding energy into the grid. The alarm descriptions and their corresponding alarm 
messages are listed in Table 9.1: 

8. Maintenance

9. Troubleshooting

.44.

.45.

Alarms

Cause

Solution

 Input voltage low/missing

 Polarity reversed

 Main board damaged

No Information 

(Blank Screen)

 Test – DC switch OFF

 Check PV connections

 Check polarity

 Check voltage >120V Single, >350V three

  Test – DC Switch ON

 Check voltage >120V Single, >350V three

 If DC voltage is “0” replace inverter

Initializing 

(Inverter stuck 

in this mode)

 Inverter is waiting for 

  driving signal

 Test – DC switch OFF

 Check PV connections

 Check polarity

 Check voltage >120V Single, >350V three

  Test – DC Switch ON

 Check voltage >120V Single, >350V three

 A cable may have been damaged or loosened 

  in shipping replace inverter

OV-G-V: Over 

Grid Voltage

 Inverter detects grid 

  voltage as too high

 228VAC for 208V mode

 264VAC for 240V mode

  Test – DC switch OFF

 Check AC at the inverter 

 If AC measures high, adjust upper limit with 

  permission from utility

  Test – DC Switch ON, full power

 Check AC at inverter test points

 Compare with LCD

 If AC measures high, cables between inverter 

  and interconnect are too small

 Check ampacity and voltage drop calculations

UN-G-V: Under 

Grid Voltage 

 Inverter detects grid 

  voltage as too low

 183VAC for 208V mode

 211VAC for 240V mode

 Test – DC switch OFF

 Check AC at the inverter test points

 If AC measures low, adjust lower limit with 

  permission from utility

 Check LCD voltage reading, may be a bad 

  measurement circuit

  Test – DC Switch ON

 Check grid standard

 Replace inverter

Содержание Beta-20K

Страница 1: ...34 917 750 542 Email info masterbattery es Web www masterbattery es If you encounter any problem on the inverter please find out the inverter S N and contact us we will try to respond to your question...

Страница 2: ...equipment has supplied The customer is fully liable for any modifications made to the system therefore any hardware or software modification manipulation or alteration not expressly agreed with the ma...

Страница 3: ...afety Symbols 2 2 General Safety Instruction 4 1 2 Packaging List 3 1 1 Product Description 5 Installation 5 1 Select a Location for the Inverter 5 2 Mounting the Inverter 5 3 Electrical Connections 6...

Страница 4: ...4 Screen Brightness Control 30 31 7 3 5 System Update 32 7 4 7 Yearly Energy Detail 7 4 8 Total Energy Detail 7 4 9 Work Log 36 37 37 7 4 6 Monthly Energy Detail 36 7 5 5 Calibrate Energy 42 42 7 5 6...

Страница 5: ...his manual contains important instructions that should be followed during installation and maintenance Please read these instructions carefully before use and keep them for future reference 2 2 Genera...

Страница 6: ...f OCPD Beta 20K should be 40A Beta 25K Beta 30K Beta 25K HV Beta 30K HV Beta 36K HV and Beta 40K HV should be 63A CAUTION Risk of electric shock Do not remove cover Refer maintenance servicing to qual...

Страница 7: ...ings the ESC and the ENTER keys 3 Overview Table 3 1 Status indicator 2 Two people are required to remove the inverter from the carton Handles are formed into the heatsink for ease of handling the i n...

Страница 8: ...stallation position 4 Installation Use the original box to repackage the inverter seal with adhesive tape with the desiccant inside the box 5 Installation 11 10 4 2 Product storage 5 1 Select a Locati...

Страница 9: ...vertical position The steps of mounting are as follows 3 Using the expansion bolts to fix the bracket to the wall Install on a vertical surface or structure capable of bearing the weight Must install...

Страница 10: ...1 All electrical installations must be in accordance with all local and national standards Table 5 1 Electrical connection symbols GRID COM1 Connecting terminal of the Grid DC 1 DC4 _ Positive DC inp...

Страница 11: ...the external heat sink connection If the AC terminal is used to connect the ground please refer to the contents of 5 3 3 If the heat sink is used to connect the ground please follow the steps below F...

Страница 12: ...pin as shown in Figure 5 13 Figure 5 12 Disassemble the Connector Cap nut Figure 5 13 Insert the Wire into the Connector Cap nut and contact pin 5 Installation 5 Installation 18 19 Cable type Outside...

Страница 13: ...ire is longer than 100m it s recommended to use 16 35mm2 cable Refer to local electrical codes for wire sizing 5 3 3 AC side connection The length after winding AC cable diameter 30K model AC cable di...

Страница 14: ...se refer to related instructions of Ginlong communication products Figure 5 20 Connect cable to AC terminal Figure 5 21 Tighten the AC terminal RS485 communication connection of RJ45 network port 1 In...

Страница 15: ...itch AC OFF 2 Wait 30 seconds Switch the DC switch OFF or directly disconnect the DC output connector The LEDs and LCD of the inverter will be off within one minute 6 1 Start the inverter 1 Switch the...

Страница 16: ...3 6MWh Status NO Grid 2015 02 23 19 35 MENU ENT MONTHLY ENERGY ESC ESC UP DOWN ENT 0 00 3 00 6 00 9 00 12 0 15 0 18 0 21 0 0 00 00 10 20 30 40 50 60 Po wer kW 7 General Operation There are four submen...

Страница 17: ...uency Carbon Offset Efficiency Generating 0003687kWh 0000014kWh 0000001kWh 0508kWh 2081kWh 0071 6kWh 000204kWh 50 01Hz 0003 67ton 99 99 ESC UP DOWN ENT 7 General Operation 7 General Operation 7 3 Sett...

Страница 18: ...the previous menu Set Address 2015 02 23 19 35 YES ENT NO ESC Slave Address 01 ESC UP DOWN ENT Press the ESC key to cancel the change and return to the previous menu 7 General Operation 7 General Ope...

Страница 19: ...by pressing the UP DOWN keys Pressing the ENTER key gives access to a submenu 7 4 1 Alarm Message The display shows the 100 latest alarm messages see Figure 7 14 Screens can be scrolled manually by p...

Страница 20: ...of the inverter see Figure 7 17 which is for service technicians only Figure 7 17 Communication data 7 4 5 Daily Energy Information The screen shows the daily energy detail of the inverter see Figure...

Страница 21: ...or press the UP DOWN keys to select energy power detail of different date Yearly Energy 2015 02 23 19 35 2015 0 0 0 5 1 0 1 5 2 0 2 5 3 0 Yea rly Ene rgy MW h 01 02 03 04 05 06 07 08 09 10 11 12 00 51...

Страница 22: ...e 7 23 Advanced settings Advanced Set 2015 02 23 19 35 Select Standard Grid ON OFF Power Control Clear Energy Restore Settings Calibrate Reset Password 7 General Operation 7 General Operation Press th...

Страница 23: ...inverter see Figure 7 27 Press the DOWN key to move the cursor Press the UP key to revise the value Press the ENTER key to execute the setting Press the ESC key to return to the previous menu Figure 7...

Страница 24: ...om working properly This function is applicable by maintenance personnel only wrong operation will prevent the inverter from reaching maximum power Press the DOWN key to move the cursor Press the UP k...

Страница 25: ...ooting 44 45 Alarms Cause Solution Input voltage low missing Polarity reversed Main board damaged No Information Blank Screen Test DC switch OFF Check PV connections Check polarity Check voltage 120V...

Страница 26: ...cts low DCV on internal bus Test Measure DC and AC voltages Compare with LCD Replace Inverter Internal damage Wire came loose during shipping 9 Troubleshooting 9 Troubleshooting Alarms Cause Solution...

Страница 27: ...wer Factor at rated output power Operating frequency range Hertz Max efficiency EU efficiency MPPT efficiency Max DC input power Watts Grid voltage range Volts Model Dimensions Weight Topology Operati...

Страница 28: ...ted DC voltage Volts Rated grid frequency Hertz 3 N PE 400 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid vol...

Страница 29: ...ency Hertz 3 PE 480 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage Volts Rated output current Amps Po...

Страница 30: ...y Hertz 99 9 10 Specification 54 3 PE 480 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Max input strings number Rated grid voltage Volts Rated...

Страница 31: ...dity 530W 700H 356 5D mm 1000 18 18 18 18 23 4 23 4 23 4 23 4 4 8 384 576 0 8leading 0 8lagging 50 60 98 8 98 4 58 2kg Transformerless IP65 30 dBA Natural convection 4000m 20 years 25 60 Display Monit...

Отзывы: