Disinfecting the Piping System with Chlorine:
1.
Shut off the water to the inlet and outlet of the cartridge filter.
2.
Remove the cartridge sump and empty all water. Fill with household chlorine (Clorox, non-
scented), 5.25% sodium hypochlorite.
3.
Re-install the sump to the filter assembly and open the inlet and outlet valves.
4.
Open the cold water faucet at the farthest point in the piping until you detect chlorine odor.
Once the odor is detected, close that faucet. Continue this procedure until the chlorine odor
has been detected at every faucet. If chlorine odor is not detected at all faucets, repeat
steps 1 through 4.
5.
Close ball valve on outlet of cartridge filter.
6.
Allow the water to stand for at least (4) hours to kill the bacteria residual in the piping
system.
**
No water should be used during disinfection. **
Before consumption of water, an EPA Lab Test is suggested.
MWC-EM SERIES
TROUBLESHOOTING
Symptom: No flow of water no Alarm and Gland Nut not glowing
Cause
Solution
Electric Supply
Check electrical outlet and breaker box for power.
Replace fuse in Meter Power Supply
Symptom: No flow of water no Alarm and
Gland Nut
is
glowing blue
and meter is reading 100%
Cause
Solution
Solenoid
Turn off water and release pressure to the MWC-EM unit.
Remove solenoid coil and clean port and plunger.
Defective solenoid replace
Symptom: Alarm is on and no flow of water and Meter is reading less than 50% and Lamp is on
and
Gland Nut
is
glowing
blue.
Cause
Solution
Lamp is over a year old
Replace lamp
See Germicidal Lamp Replacement.
Quartz Sleeve is dirty
Remove quartz sleeve and
UV quartz eye dirty
Remove Quartz Eye and clean
Symptom: Alarm is on and no flow of water and Lamp is out and Meter is reading 0%
Cause
Solution
Lamp
Replace lamp
See Germicidal Lamp Replacement.
Remove quartz sleeve and clean
Remove Quartz Eye and clean