MANUAL                                              PCUWS10   

 

 

Programming IP and Internal Clock 

To enter the programming mode the internal clock synchronization useful to the historian of 
the web page and set the IP address of the Web Server follow these steps: 
 
1. Disconnect the user from PCUWS10 ( even just the positive terminal ) 
2 . Set the main switch (1 ) to OFF . 
3 . Disconnect the positive terminal of the battery to bring the PCUWS10 mode off. 
4 . Connect the positive terminal of the battery while holding down the UP and ENTER (6) 

and release them immediately after the appearance of the display (5) the words " DD / MM 
/ YY HH : MM" . 

5 . Through the UP and DOWN buttons (6) to enter the Day, Month , Year , and finally the 

Hour Minutes proceeding to advance with the ENTER button ( 6) 

6 . Minutes After inserting , pressing the ENTER button (6) will appear on the display (5) all 

information entered for a time of 5 seconds and then switch to programming the Web 
Server . 

7 . Upon the appearance on the display (5) the words " Enter IP " , using the UP and DOWN 

buttons (6) Enter the IP address to assign to the Web Server advancing through the 
ENTER button ( 6). 

8 . After entering the last digit of the IP , pressing the ENTER button ( 6 ) to enter the 

programming mode seen previously in step 5. 

All data entered during programming are stored in the same PCUWS10 without power for 
long periods (50 years) , so the programming will be resumed automatically each time the 
PCUWS10 and activates after 2 minutes of no manual intervention on the buttons. 
Periodically ( once a year ) or when the historian does not match the current time , it is useful 
to set the internal clock of PCUWS10 again and check the status of the batteries. 
 
(* optional)  
Optionally comes with the PCUWS10 relay interface for input and output optocouplers for 
input at the sole request of the customer at a cost slightly higher.  
The PCUWS10 comes standard with a TTL interface for the remote control section with the 
connections shown below: 

 

Содержание PCUWS10

Страница 1: ...1 PCUWS10 Power Charge Unit Web Server ...

Страница 2: ...nd independently for long periods of time with the possibility of control and vision on the internet Battery test the unique program allows you to evaluate the PCUWS10 through a careful measurement buffer in times of Use and refilling the efficiency of the backup battery is connected indicating the state in the form of percentage yield Protection and separation in its unique capabilities the PCUWS...

Страница 3: ...RATIONS Fully automatic with desulfation and measurement parameters continuously BATTERY TYPE lead acid batteries or gel BATT AMPS From 10 to 110 Ah Charging 10C From 10 to 220 Ah Charging 20C INPUT OUTPUT LAN temperature sensor and battery 8 in out at the customer s request Presence LAN Presence Mains Battery operational presence USERS Max 50 A 24 Volt 1200 Watt INSULATION IP65 ...

Страница 4: ...oth batteries at PCUWS10 Do not cover the air vents of the PCUWS10 A battery being charged could emit explosive gases Avoid sparks in the vicinity of batteries At the end of its useful life the batteries tend to form internal sparks With the passage of time all batteries may present defects In general the defects during charging are compensated by the advanced control PCUWS10 but they do occur une...

Страница 5: ...d by the manufacturer usually one tenth of the Ampere battery If the value exceeds 10 amperes for which the PCUWS10 was designed or is below 50mA one can not advance in the programming 10 Press the ENTER button 6 to start the PCUWS10 that the display will indicate the detected voltage from the battery the power that you are taking the percentage yield of the batteries since reliable after a full c...

Страница 6: ...emperature also two windows show the presence of mains and free batteries The first graph below marked on the right with V volts shows the evolution of the charge in green above 24V and low in red below 24V in the 24 hours of the day starting from 00 00 to 23 59 in steps of 5 minutes The second graph is marked to the right with A Amps shows the trend of the charging current in green from 0 to 10A ...

Страница 7: ...on the web interface on the first refresh of the page indicating the status of the off 0V 5V ON Both the outputs and inputs are useful for managing utilities and machinery on the site remotely manageable via a web interface on any device PC laptop tablet smartphone etc that has a browser and Internet interfaces LIMITED WARRANTY MASTER DIGIT issues this limited warranty to the purchaser the origina...

Страница 8: ...d then switch to programming the Web Server 7 Upon the appearance on the display 5 the words Enter IP using the UP and DOWN buttons 6 Enter the IP address to assign to the Web Server advancing through the ENTER button 6 8 After entering the last digit of the IP pressing the ENTER button 6 to enter the programming mode seen previously in step 5 All data entered during programming are stored in the ...

Страница 9: ...anche per lunghissimi periodi con possibilità di controllo e visione su internet Test di batteria il programma esclusivo del PCUWS10 permette di valutare attraverso una scrupolosa misurazione nei momenti di utilizzo tampone e successiva ricarica l efficienza della batteria tampone collegata indicandone lo stato in forma di resa percentuale Protezione e distacco nelle sue esclusive funzionalità il ...

Страница 10: ...E Completamente automatica con desolfatazione e misurazione continua dei parametri TIPO DI BATTERIA Batterie al piombo acido o gel AMPERAGGIO BATT Da 10 a 110 Ah ricarica 10C Da 10 a 220 Ah ricarica 20C INPUT OUTPUT LAN Sensore temperatura batterie 8 in out a richiesta del cliente Presenza rete LAN Presenza rete elettrica Presenza Batteria operativa UTENZA Max 50 A 24 Volt 1200 Watt ISOLAMENTO IP6...

Страница 11: ...a del PCUWS10 Una batteria in carica può generare gas esplosivi Evitare la formazione di scintille in prossimità delle batterie Al termine della vita utile le batterie tendono a formare scintille interne Con il passare del tempo tutte le batterie possono presentare dei difetti In genere i difetti durante la ricarica vengono compensati dal controllo avanzato del PCUWS10 ma si possono comunque verif...

Страница 12: ...degli Ampere delle batterie Se il valore supera i 10 Ampere per il quale il PCUWS10 è stato progettato o è sotto i 50mA non si può avanzare nella programmazione 10 Premere il pulsante ENTER 6 per avviare il PCUWS10 che indicherà sul display la tensione rilevata dalle batterie la corrente che si sta prelevando la percentuale di resa delle batterie dato attendibile dopo un completo ciclo di scarica ...

Страница 13: ...trano la presenza della rete elettrica e della connessione batterie Il primo grafico sottostante contrassegnato alla destra con V Volt mostra l andamento della carica in verde sopra i 24V e della scarica in rosso sotto i 24V nelle 24h della giornata partendo dalle ore 00 00 alle ore 23 59 con step di 5 minuti Il secondo grafico contrassegnato alla destra con A Ampere mostra l andamento della corre...

Страница 14: ...imo refresh della pagina segnalando lo stato dell ingresso 0V spento 5V acceso Sia le uscite che gli ingressi sono utili per gestire utenze e macchinari presenti nel sito tramite interfaccia web gestibile da remoto su qualunque dispositivo PC portatile Tablet Smartphone ecc che dispone di un browser ed interfaccia internet GARANZIA LIMITATA MASTER DIGIT conferisce la presente garanzia limitata all...

Страница 15: ...mmazione dell IP del Web Server 7 Alla comparsa sul Display 5 della scritta Inserire IP tramite i pulsanti UP e DOWN 6 inserire l IP da assegnare al Web Server avanzando tramite il pulsante ENTER 6 8 Dopo l inserimento dell ultima cifra dell IP premendo il pulsante ENTER 6 si entra nella modalità di programmazione vista in precedenza al punto 5 Tutti i dati inseriti in fase di programmazione riman...

Отзывы: