9

 

                Figure #5

 

 
If locking arm fails to hook locking pin, turn cam-lock counter-clockwise one completes turn and repeat the 
procedure like 

Figure #3

 

 
 
 

LEVEL FLOOR

 

 
It is very important that the existing floor be level If it is not level the insulated floor panels must be leveled by 
shimming between the existing floor and the floor panels.  Assembling a walk-in of any type on an uneven or 
unleveled floor without some sort of shimming of grouting is not practical, not advisable and will never result in 
a satisfactory installation. 
 
Leveling of floor type walk-in floor panels should be accomplished by the use of a sand leveling bed or the use 
of shim stock.  Shim stock can be rot resistant wood, strips of galvanized sheet metal, etc.  Shims under floor 
panels must be no further than 18” on center in both length and width so as to property support the floor 
panels when the walk-in is assembled and the product load is in place.  Shimming just the outer edges of just 
the corners of the floor panels will result in broken panels and/or separation of the metal liners from the foam. 
 

 
CAULKING 

 
Caulking is recommended in all panel joints as shown in 

Figure #6, #7, 

and

 #8

.  Caulk should be of high-

grade outdoor type odorless compound.  Approximately one tube of caulk is repaired for every 60 square feet 
of panel surface. 
 
It should be noted that on walk-ins subject to external weather conditions, the caulking of roof joints does not 
seal the roof against water penetration.  Therefore, a weather protective roof must be installed atop the 
insulated roof panels.   

Caulking

Roof 
panel

wall 

panel

Caulking

Joining 
seam 
of 

like 
panels

Caulking

Wall Panel

Floor Panel

 

              Figure # 6                                          Figure # 7                                                Figure # 8 

      

Roof to Wall Caulking Detail                    Like Panel To Like Panels Caulking Details                      Floor to Wall Caulking Detail

 

Содержание CL-156

Страница 1: ...Installation Operations Manual Master Bilt Products 908 Highway 15 North New Albany MS 38652 Phone 800 684 8988 PN 090 90000 Rev 05 20 03 LocN...

Страница 2: ...2...

Страница 3: ...ns 6 Notice to store owners managers 6 Electrical 7 Panel Storage 7 Cam Fasteners 8 Level Floor 9 Caulking 9 Floor Assembly 10 Celing and Wall Penal Assembly 10 Door and Frame installation 10 Refriger...

Страница 4: ...ys of sun or near a direct source of radiant heat or airflow This will adversely affect the case and will result in poor performance NOTICE Read this manual before installing your cabinet Keep the man...

Страница 5: ...ing signal words are used in the warnings and safety messages DANGER Severe injury or death will occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUT...

Страница 6: ...the equipment clean and sanitary so it will meet your local sanitation codes 3 Rotate your stock so that older stock does not accumulate A First In First Out rotation practice will keep the products...

Страница 7: ...spacer Groove edge of panel down 2 X 4 wood frame Figure 2 Whenever possible panels should be stored indoors panels stored indoors may be stored in their original factory crates If it is necessary to...

Страница 8: ...will be as shown Cam Wrench Hook in Open Position Figure 3 NOTE All cam lock locking arms must be in the open position before attempting to lack panels together Push panels together and turn cam wret...

Страница 9: ...er in both length and width so as to property support the floor panels when the walk in is assembled and the product load is in place Shimming just the outer edges of just the corners of the floor pan...

Страница 10: ...should be completely aligned and cam fasteners completely tightened If wall panels appear to have a stair step effect on the top horizontal egde as thy are being assembled the foor is not level At thi...

Страница 11: ...drain pan of evaporator coil seal around drain line with silicone or butyl caulking to prevent moist air entering box from outside Start compressor and allow running at least 24 hours before committin...

Страница 12: ...ply to door frame TEMPERATURE CONTROLS On the CM models the Temperature Control is on the end penel of the blower housing These controls have an off position at full counter clockwise position and sho...

Страница 13: ...oting Guide 1 High head pressure and high back pressure A Condenser coil clogged or restricted B Condenser fan motor defective 2 Low back pressure and low head pressure A Restriction in system B Refri...

Страница 14: ...E 070UU 1 SK 3 3A R35XZ070UU 1 SK 1 C12X 070UU 4 SK 1 W46X 070UU 3 28X63 RH NSF 1092 DGT SK 2 2P D28RX070UU 1 F35E 07 UU 1 F35S 070UU 1 TOTALS 12 Vapor Proof Light Globe for door panel 23 00594 1 1 Di...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: