Voltage drop (V  ) measurement

    Dummy load shall be used in the circuit to 
measure the load phase voltage and then calculate 
the voltage drop. The voltage drop and load phase 
voltage will be displayed when the load reaches 
12A, 15A and 20A.
    In terms of qualified circuit, when measurement 
is made in the most remote socket from the 
switchboard, the voltage drop shall be less than 5%. 
During the measurement of the remaining sockets 
of the same area, the farthest socket from the 
switchboard shall be measured first and then other 
measurements shall be made from the distant to 
the near. The reading of the voltage drop shall be 
shown on the downward trend.
    If the voltage drop exceeds 5% and no obvious 
drop of reading is found during the measurement 
made near the switchboard, it indicates that the 
first connection point goes wrong. In this case, 
perform a visual inspection of the wire connection 
among the first connection point, equipment and 
switchboard and the connection of breaker 
(air-break switch). Usually, a high impedance point 
generates heat. To locate this problem, infrared 
radiation thermometer can be used. In addition, we 
can directly measure the voltage on both sides of 
the breaker (air-break switch) to locate the point of 
failure.  

d

    If the voltage drop exceeds 5%, and during the 
measurement made near the switchboard, the 
reading drops constantly and no obvious change 
is found between the two sockets, it indicates that 
the lead wire diameter is too small compared with 
the transmission distance, the transmission 
distance is too long or the circuit is overloaded. 
Under such circumstances, check the cable to see 
if the lead wire diameter complies with the required 
standard, and measure the lead wire current to see 
if it is overloaded. 
    If the voltage drop exceeds 5% and there is an 
obvious change of voltage drop reading between 
the two sockets, it indicates that a high impedance 
point exists between the two sockets. Usually, 
problems are found at the contact, such as poor 
connection, loose connector, or socket problem. 

Содержание ms5908

Страница 1: ...TEST mA VA ms Hz VA ms AC L N L E N E Peak Z L Z N Z E ASCC 12 A 15 A 20 A HOLD N E L V Vd Z RCD GFCI MS5908 Circuit Analyzer Operation Manual...

Страница 2: ...ility of residual current device RCD and response action time Test the reliability of GFCI action and response action time Backlight function and data hold function Warning Do not use this instrument...

Страница 3: ...em selection key 5 Data hold key 6 Backlight function key 7 Sub test item up selection key 8 Sub test item down selection key 9 Test key TEST mA VA ms Hz VA ms AC L N L E N E Peak Z L Z N Z E ASCC 12...

Страница 4: ...voltage drop of 12A 15A and 20A load separately Under the appropriate test function press the test key to test d Menu Operation The main test items of the analyser are located on the bottom of display...

Страница 5: ...tween live line and earth line to test the performance of GFCI Press the test key to test 12 A 15 A 20 A Impedance Z real time display of line connection status and frequency and display of the impeda...

Страница 6: ...off is automatically cancelled When auto power off function is enabled if there is no other key operation for 30 minutes the analyser will automatically turn off Data hold function press the key to en...

Страница 7: ...between two live lines 2 Combined fault 3 Reverse connection of earth line and neutral line Voltage measurement The normal measured value of phase voltage is 120V 10 60Hz The peak voltage of sine wave...

Страница 8: ...the current source Is there any multipoint ground Does the equipment or device leak current Three phase imbalance Check and redistribute the load 2V 2V Voltage to earth of zero line Harmonic interfere...

Страница 9: ...nnection point equipment and switchboard and the connection of breaker air break switch Usually a high impedance point generates heat To locate this problem infrared radiation thermometer can be used...

Страница 10: ...ter is too small for the power transmission length or the quality of equipment parts or connector is poor Usually the earth line impedance is less than 1 to provide a free discharge route for failure...

Страница 11: ...3 m Residual current device RCD test During the RCD test the analyzer will generate a low current between live line and earth line by means of a fixed resistance which will affect the current balance...

Страница 12: ...ch will affect the current balance between live line and zero line The GFCI shall response to the current imbalance by cutting off the power The analyzer will display the value of the current triggere...

Страница 13: ...ative humidity Physical dimension 193mm L 78mm W 38mm D Power source Six AAA batteries Weight 295g including batteries Accuracy index Accuracy reading words one year guarantee Reference conditions Amb...

Страница 14: ...partment and open the cover 4 Replace the batteries 5 Ensure the batteries are installed properly Do not mismatch polarity 6 Put back the cover and tighten the screws Maintenance Battery installation...

Отзывы: