background image

13

14

Fault localization and trouble shooting for voltage 
problems

Measurement 

Item

Normal 

measurement 

result

Fault 

measurement 

result

Possible 

cause

Trouble

shooting

Phase voltage

108-132V

(120V)

198-242V

(220V)

The voltage 

is 

too high 

or 

too low.

The circuit is 

overloaded. 

Redistribute 

the circuit load.

High 

impedance 

points are

 found in 

switchboard 

or circuit. 

Locate the 

high impedance 

and repair 
or replace 

relevant parts.

The supply 

voltage 

is 

too high 

or 

too low. 

Consult the 

power supply 

department

Voltage to 

earth 

of zero line

<2V

>2V

Leakage 

current

Find the 

current source: 

Is there any 

multipoint 

ground? 

Does the 

equipment 

or 

device 

leak current? 

Three-phase 

imbalance

Check and 

redistribute 

the load

>2V

<2V

Voltage to 

earth 

of zero line

Harmonic 

interference

Increase neutral 

line conductor, 

install electrical 

filter or use 

other methods 

to reduce the 

harmonic 

interference 

The supply 

voltage 

is 

too high 

or 

too low

Consult the 

power supply 

department

The electron 

device in 

the circuit 

results in the 

electric wave 

distortion 

Revaluate 

and 

relocate 

(if necessary) 
the electronic 

device 

in the circuit

The voltage 

is 

too high 

or 

too low.

153-185V

(120V) 

280-342V

(220V)

Peak voltage

The supply 

frequency 

is 

too high 

or 

too low. 

Consult 

the electricity 

department

The frequency 

is 

too high 

or 

too low.

60Hz

(50Hz)

Frequency

Содержание ms5908

Страница 1: ...TEST mA VA ms Hz VA ms AC L N L E N E Peak Z L Z N Z E ASCC 12 A 15 A 20 A HOLD N E L V Vd Z RCD GFCI MS5908 Circuit Analyzer Operation Manual...

Страница 2: ...ility of residual current device RCD and response action time Test the reliability of GFCI action and response action time Backlight function and data hold function Warning Do not use this instrument...

Страница 3: ...em selection key 5 Data hold key 6 Backlight function key 7 Sub test item up selection key 8 Sub test item down selection key 9 Test key TEST mA VA ms Hz VA ms AC L N L E N E Peak Z L Z N Z E ASCC 12...

Страница 4: ...voltage drop of 12A 15A and 20A load separately Under the appropriate test function press the test key to test d Menu Operation The main test items of the analyser are located on the bottom of display...

Страница 5: ...tween live line and earth line to test the performance of GFCI Press the test key to test 12 A 15 A 20 A Impedance Z real time display of line connection status and frequency and display of the impeda...

Страница 6: ...off is automatically cancelled When auto power off function is enabled if there is no other key operation for 30 minutes the analyser will automatically turn off Data hold function press the key to en...

Страница 7: ...between two live lines 2 Combined fault 3 Reverse connection of earth line and neutral line Voltage measurement The normal measured value of phase voltage is 120V 10 60Hz The peak voltage of sine wave...

Страница 8: ...the current source Is there any multipoint ground Does the equipment or device leak current Three phase imbalance Check and redistribute the load 2V 2V Voltage to earth of zero line Harmonic interfere...

Страница 9: ...nnection point equipment and switchboard and the connection of breaker air break switch Usually a high impedance point generates heat To locate this problem infrared radiation thermometer can be used...

Страница 10: ...ter is too small for the power transmission length or the quality of equipment parts or connector is poor Usually the earth line impedance is less than 1 to provide a free discharge route for failure...

Страница 11: ...3 m Residual current device RCD test During the RCD test the analyzer will generate a low current between live line and earth line by means of a fixed resistance which will affect the current balance...

Страница 12: ...ch will affect the current balance between live line and zero line The GFCI shall response to the current imbalance by cutting off the power The analyzer will display the value of the current triggere...

Страница 13: ...ative humidity Physical dimension 193mm L 78mm W 38mm D Power source Six AAA batteries Weight 295g including batteries Accuracy index Accuracy reading words one year guarantee Reference conditions Amb...

Страница 14: ...partment and open the cover 4 Replace the batteries 5 Ensure the batteries are installed properly Do not mismatch polarity 6 Put back the cover and tighten the screws Maintenance Battery installation...

Отзывы: