background image

Masport P36-3 Gas Inbuilt

16

Diagram 3

HORIZONTAL

INSTALLATIONS

Install the flue system according to the
manufacturer's instructions included
with the components.

1) Set the unit in its desired location. Check to

determine if wall studs or roof rafters are in
the way when the flueing system is at-
tached. If this is the case, you may want to
adjust the location of the unit. Rough in the
gas preferably on the right side of the unit
and the electrical (junction block is on the left
side) on the left.

2) Put a bead of silicone inside the outer section

of the adapter and a bead of Mill-Pac on the
inner collar. Slip the adapter over the exist-
ing inner and outer flue collar and fasten to
the outer collar only with the 3 supplied
screws (drilling pilot holes will make this
easier). Level the fireplace and fasten it to
the framing using nails or screws through
the nailing strips.

3) Assemble the desired combination of pipe

and elbows to the appliance adaptor and
twist-lock for a solid connection.

Note: Apply sealant "Mill-Pac" to inner

pipe and high temperature silicone
sealant to outer pipe.

a) Horizontal runs of flue must be support-

ed every three feet. Wall straps are
available for this  purpose.

4) Mark the wall for a 10" x 10"  square hole.

The center of the square hole should line up
with the centerline of the horizontal pipe. Cut
and frame the 10 inch square hole in the
exterior wall where the flue will be terminat-
ed. If the wall being penetrated is construct-
ed of non-combustible material, i.e. mason-
ry block or concrete, a 7"(178mm) diameter
(7-1/2"(191mm) diameter for flex) hole is
acceptable.

Note:

a)

The horizontal run of flue must be
level, or have a 1/4 inch rise for
every 1 foot of run towards the
termination. Never allow the flue
to run downward. This could
cause high temperatures and
may present the possibility of a
fire.

b) The location of the horizontal flue termi-

nation on an exterior wall must meet all
local and national building codes, and
must not be blocked or obstructed.  For
External Flue Terminal Locations, see
diagram on page 10.

5) The arrow on the flue cap should be

pointing up. Insure that the 1-1/2" clear-
ances to combustible materials are main-
tained. Install the termination cap, see dia-
gram 3.

The four wood screws provided should be
replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.

Note: If installing termination on a siding

covered wall, a vinyl siding stand-
off or furring strips must be used
to ensure that the termination is
not recessed into the siding.

6) Before connecting the horizontal run of flue

pipe to the flue termination, slide the Wall
Thimble over the flue pipe.

Diagram 1

INSTALLATION

7) Slide the appliance and flue assembly to-

wards the wall carefully inserting the flue
pipe into the flue cap assembly. It is impor-
tant that the flue pipe extends into the flue
cap sufficient distance so as to result in a
minimum pipe overlap of 1-1/4 inches. Se-
cure the connection between the flue pipe
and the flue cap by attaching the two sheet
metal strips extending from the flue cap
assembly into the outer wall of the flue pipe.
Use the two sheet metal screws provided
to connect the strips to the pipe section. See
Diagram 2.

8) Install wall thimble in the center of the 10"

square and attach with wood screws. See
Diagram 3.

Diagram 2

Содержание Calais

Страница 1: ... informationconsultanauthorisedinstaller service agency or the gas supplier FORYOURSAFETY Do not store or use gasoline or other flammablevapoursandliquidsinthevicinity of this or any other appliance Installation and service must be performed by an authorised installer service agency or the gas supplier P36 Gas Inbuilt Head Office Australia 54 Boundary Rd Braeside P O Box 553 Mordialloc 3195 Head O...

Страница 2: ...he warmth and charm of a wood fireplace at the flick of a switch The model P36 has been approved by the Australian Gas Association for both safety and efficiency It promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Masport Fireplace ...

Страница 3: ... Gas Fire 6 ManufacturedHomeAdditionalRequirements 6 Clearances 6 MantelClearances 7 MantelLegClearances 8 FramingandFinishing 8 Unit Assembly Prior to Installation TopStandoffAssembly 9 Top Facing Support Side Nailing Strip Assembly 9 FlueingIntroduction 9 ExteriorFlueTerminationLocations 10 Direct Flue System Flex 11 Flueing HorizontalTerminations 12 Co Axial Flue System 13 VerticalTerminations ...

Страница 4: ...ace We have printed a copy of the contents here for your review The label is AustraliaOnly located on the front inside base of the unit visible when the bottom louvre is open DATA BADGE NOTE Masport units are con stantly being improved Check the label on the unit and if there is a difference the label on the unit is the correct one ...

Страница 5: ...ed person 3 THISAPPLIANCEISNOTINTENDEDASA FIREPLACEINSERT DONOTCONNECT TO MASONARY FLUE 4 This appliance must be connected to the specified flue and termination cap to the outside of the building enve lope Never flue to another room or inside a building Make sure that the flue is fitted as per Flueing instruc tions 5 Inspect the flueing system annually for blockage and any signs of deterioration 6...

Страница 6: ...e e g wood met al concrete This may be the floor or raised up on a platform to enhance its visual impact If the appliance is going to be in stalled on carpeting combustible linoleum tile or other combustible material other than wood flooring the appliance must be in stalled on a metal or wood panel extending the full width and depth of the appliance 4 TheP36CoAxialFlueGasFireplacecanbe installed i...

Страница 7: ... 2 COMBUSTIBLE MANTELS These drawings are to scale at 1 6 one inch 6 inches Mantel can be installed anywhere in shaded area or higher using the above scale Note Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolour Also the material from which the mantel is made from must be heat resistamt to 85 o C Diagram 1 Diagram 2 INSTALLATION ...

Страница 8: ... the finished surface to be flush with the front of the unit Total facing thickness can vary from 1 2 13mm to 1 1 4 32mm thick Maximum38mmprojectionat51mmminimum clearance 3 For exterior walls insulate the enclosure to the same degree as the rest of the house apply vapour barrier and drywall as per local installation codes Do not insulate the fireplace itself 4 The top of the unit must not be clos...

Страница 9: ...e mounted in 3 different positions depend ing on the thickness of the facing material For C screw position the top facing support is reversed 1 Mount Top Facing Support using the 3 suppliedscrewsintothethreepre punched screw holes on the top front of the unit Use hole positions A B or C depending on your facing depth 2 Use the same screw hole position for the Side Nailing Strips as was used for th...

Страница 10: ...dow door or non mechanical air inlet or any other opening into a building with the exception of sub floor ventilation see also Note I Appliances up to 150 MJ h input 500 Appliances over 150 MJ h input 1500 k Vertically below an openable window door or non mechanical air inlet or any other opening into a building with the exception of sub floor ventilation see also Note I see table below Clearance ...

Страница 11: ...f Mill Pac 1 8 plated screws 8 9 screws 8 x 1 1 2 Drill Point Stainless Steel 4 If longer runs are needed the Direct Flue system Flex 946 516 includes all the parts needed to install the P36 with a maximum 3 0m run 1 175mm dia flexible liner 3 0m length 2 100mm dia flexible liner 3 0m length 3 spring spacers 7 4 thimble 2 5 AstroCap termination cap 1 6 screws 12 7 tube of Mill Pac 1 8 plated screw...

Страница 12: ...ed on pages 6 to 8 Horizontal flue must be supported every 3 feet 0 9 meters NOTE If you are installing the P36 into a Masport Mantel Kit use the minimum horizontal flue height centre line of 40 1 2 1029mm Remember to include the mantel base in your calculations and to maintain the 3 76mm clearance to the underside of the mantel top A flue guard should be used when ever the termination is lower th...

Страница 13: ...if two 90o elbows are used 3 Minimum distance between elbows is 2 ft 0 6m 4 Determine the permitted range of horizontal termination arrangements by using chart on page 12 and deducting 3 ft 0 9m from the maximum horizontal distance for the second 90o elbow Maintain clearances to combustibles as listed on pages 6 to 8 Horizontal flue must be supported every 3 feet 0 9 meters A flue guard should be ...

Страница 14: ...bows equal one 90o elbow as per diagram 1 The P36 is approved for a 37 ft 11 3m straight vertical including a 20 0 5m horizontal offset using two 90o elbow two 45o elbows equal one 90o elbow as per diagram 2 Flue must be supported at offsets Maintain clearances to combustibles Note Masport Co Axial Flue System Flex is only approved for horizontal terminations Diagram 1 Diagram 2 INSTALLATION ...

Страница 15: ...ht vertical as per the diagram 3 The shaded area in diagram 3 shows all allowable combinations of straight vertical and offset to vertical terminations Maximum two 45o elbows allowed Flue must be supported at offsets Maintain clearances to combustibles as listed on pages 6 to 8 Diagram 3 ...

Страница 16: ...1mm diameter for flex hole is acceptable Note a Thehorizontalrunoffluemustbe level or have a 1 4 inch rise for every 1 foot of run towards the termination Never allow the flue to run downward This could cause high temperatures and may present the possibility of a fire b The location of the horizontal flue termi nation on an exterior wall must meet all local and national building codes and must not...

Страница 17: ...p spacer must be installed in the floor or ceiling of every level To install the Firestop spacer in a flat ceiling or wall cut a 10 inch square hole Frame the hole as shown in Diagram 3 and install the firestop 4 Assemble the desired lengths of pipe and elbows Ensure that all pipes and elbow connections are in the fully twist locked position and sealed 5 Cut a hole in the roof centered on the smal...

Страница 18: ...you have an incorrect flame pat tern contact your Masport dealer for further instructions Incorrect flame pattern will have small probably yellow flames not coming into proper contact with the rear burner or thermopile or thermocouple AERATION ADJUSTMENT The air shutter can be adjusted Open the air shutter for a blue flame or close for a yellower flame The burner aeration is factory set but may ne...

Страница 19: ...are 4 Install the 2 brick retaining clips one on each side INSTALLATION LOG SET INSTALLATION Read the instructions below carefully and refer to the diagrams If logs are broken do not use the unit until they are replaced Broken logs can interfere with the pilot operation The gas log kit Part 512 930 contains the following pieces a 02 49 Rear Log 902 236 b 02 55 Middle Left Log 902 237 c 02 50 Front...

Страница 20: ... 53 02 49 02 51 02 53 02 55 02 53 02 50 02 55 02 53 02 50 02 55 02 53 02 49 02 51 02 53 02 51 02 54 Notch Bracket Bracket 02 49 02 51 02 49 02 51 4 Place Log 02 51 on the front right side of the burner Push the back of the log against the 2 brackets with the notch on the bottom right side of the log fitting into the right side of the grate 6 Place the bottom left front edge of Log 02 55 against th...

Страница 21: ... the backofthetoptrim piece and to the bottom trim piece then attach trim to thetopandbottom of Flush door FlushLouvres 1 Install the top louvre by sliding the two bracket clips into the brackets located un derneath the top of the firebox 2 The bottom louvre has a hinge that is at tached 2 screws per hinge to the lip on bottom of the unit Note Top and bottom louvres are different INSTALLATION 10 P...

Страница 22: ...th the Bay glass option The optional Bay door is an overlay on the flush front The standard flush door and glass must remain on the unit 1 Hook the top of the bay door over the flush door flange and swing the bottom against the bottom flange of the flush door 2 Secure to the flush door bottom bracket with 2 screws provided 3 Slide the valve extension knobs onto the valve knobs Note If any maintena...

Страница 23: ...w 4 Repeat step 3 for the right side faceplate Secure bottom of faceplate with screw 5 Slide top piece of faceplate into side faceplates by fitting mounting plates into brackets 6 Push in both side faceplate pieces and completely tighten screws 7 Re install top louver 8 Close bottom louver Side piece Faceplate Back View Bracket on back of side faceplate Top piece Faceplate NOTE Do not push in side...

Страница 24: ... 3 5 Install hinge to bracket then secure with screw New hinge bracket Left side shown 6 Place something underneath bottom grill to prevent scratching 7 Line up hinge holes in bottom grill holes 8 Place screws half way in do not secure completely Hinge 9 Place bracket over screws then push to the side against faceplate to lock in place as per diagram 10 Tighten screws Screws will easily be tighten...

Страница 25: ...r and the receptacle box protection from extreme heat is very im portant Run wires from the fireplace to that location Use Thermostat Wire Table 2 Connect the two wires to the gas valve See diagram below CAUTION Do not connect millivolt remote control wires for gas appliance to a 240V power supply 3 Install alkaline batteries in both the receiver and the transmitter Install the receiver and its co...

Страница 26: ...C power supply is needed for the fan blower operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges WARNING ElectricalGroundingInstructions This appliance is equipped with a three pronged grounding plug for your protectionagainstshockhazardandshouldbepluggeddirectlyintoaproperly grounded three prong receptacle Do not cut or remove the grounding prong fro...

Страница 27: ...our fan speed control Burner Tray The burner tray is positioned directly under the burner tube s and logs and is made of a different gauge material from the rest of the firebox and body Therefore the varying thick nesses of steel will expand and contract at slightly different rates which can cause tick ing and cracking sounds You should also be aware that as there are temperature changes within th...

Страница 28: ...1 1 Turn OFF the flame switch 2 Push in gas control knob slightly and turn to OFF position CAUTION Hotwhileinoperation Donottouch SevereBurnsmayresult Due tohighsurfacetemperatureskeepchildren clothingandfurniture gasoline and other liquids having fammable vapors away Keep burner and control compartment clean See installation and operating instructions accompanyingappliance LIGHTING INSTRUCTIONS A...

Страница 29: ...s not covered under warranty FIREBOX PAINT The interior of the firebox is subject to extremely high flame temperatures While the painted surface is designed for high durability the combustion conditions can cause deterioration of the paint finish This is not unique to Masport Gas Fires If the surface discolors or blisters simply scuff any loose paint from the firebox and lightly respray with Maspo...

Страница 30: ...ect the appliance per formance 9 Reinstall the 10 hold down screws 10 Hook up the 2 TP and 2 TH wires to the appropriate connections on the valve 11 Reinstall the front log stand 12 Install Burner grate assembly 13 Hook up the gas line and check for gas leaks with a soap and water solution or a gas leak detector Do not use open flame for leak testing 14 Fire up the unit temporarily 15 Check the ma...

Страница 31: ... Power Cord 240 V 14 510 026 Hinge Bracket Left Right 15 948 253 Door Handle 17 Wire Holder Clip 20 510 033 Top Nailing Strip 21 510 064 Side Nailing Strip 22 510 153 Baffle Plate 23 510 011 Standoff Top 24 511 044 Standoff Side Back 27 Outer Flue Collar 28 Inner Flue Collar Assembly 30 Gasket for Flue Collar 31 FlueMountingPlate 513 928 Brick Panel Set Optional 33 902 323 Brick Panel Back 34 902 ...

Страница 32: ...flame S I T 910 039 Pilot Assy LPG 3 way flame S I T 904 240 Orifice 37 NG Burner 904 390 Orifice 52 LPG Burner 910 036 Pilot Orifice NG 910 037 Pilot Orifice LPG 936 170 Orifice Gasket 67 PilotHolder 68 W840470 Pilot Assembly Gasket 79 512 525 Burner Assy NG 82 511 030 Burner Grate Assy 84 Rear Log Support Assy 85 512 930 Log Set 86 910 386 Thermocouple 87 910 341 Thermopile 92 902 236 Rear Log 9...

Страница 33: ...109 940 098 P Center Glass Decorative 111 902 285 Brick Panel Bay 510 938 Bay Front Trim Brass 510 949 Bay Door Trim Steel 112 Bay Front Trim Top Bottom 510 936 Bay Door Trim Gold 113 Bay Door Trim Gold Bottom 114 Bay Door Trim Gold Top 510 907 Bay Louvres Black 510 905 Bay Louvres Gold Black 510 906 Bay Louvres Brass Black 510 908 Bay Louvres Steel Black 115 Bay Louvre Assy Top 116 Bay Louvre Ass...

Страница 34: ...rround Black 146 Barcelona Assy 148 Barcelona Louvre Assy 510 932 Flush Glass Trim Gold 2 Set 150 Flush Glass Trim Gold 904 196 Magnet 1 round 510 934 Flush Glass Trim Brass 2 Set 510 947 Flush Glass Trim Steel 2 Set 152 Flush Glass Trim Brass 904 196 Magnet 1 round 510 950 Finishing Trim 3 piece Brass 510 986 Finishing Trim 3 piece Black 510 909 Finishing Trim 3 piece Steel 510 910 Finishing Trim...

Страница 35: ... Top 203 942 591 Cast Faceplate Left 513 991 Cast Grills Set Black Metallic 204 942 631 Top Grill Black Metallic 942 641 Bottom Grill Black Metallic 513 956 Cast Faceplates Set Black Enamel 201 942 586 Cast Faceplate Right 202 942 576 Cast Faceplate Top 203 942 596 Cast Faceplate Left 513 996 Cast Grills Set Black Enamel 205 942 636 Top Grill Black Enamel 942 646 Bottom Grill Black Enamel ...

Страница 36: ...___________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ _________________________________________________________...

Страница 37: ...___________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ _________________________________________________________...

Страница 38: ...___________________________________________ ______________________________________________________ _______________________________________________________________ ___________________________________________________________ __________________________________________________________ ____________________________________________________________ _________________________________________________________...

Страница 39: ...Service Agent This Express Warranty Does Not Cover 1 Defects malfunctions or failures caused by incorrect installation normal wear and tear misuse neglect accidental damage or failure to follow the fuel selection product operating and maintenance instructions or resulting from installations repairs or modifications to the equipment carried out by unauthorised persons 2 Defects malfunctions or fail...

Страница 40: ...Printed in Canada Copyright 2004 FPI Fireplace Products International Ltd All rights reserved ...

Отзывы: